{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2RT043","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2RT043","canonicalUrl":"https://aoctrl.com/schneider/GV2RT043","factsUrl":"https://aoctrl.com/api/mcp/products/GV2RT043","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca GV2RT043, motor circuit breaker, 3P, 0.63 A rated current, thermal-magnetic trip, 100 kA Icu at 400 V AC.","salesMarkdown":"The GV2RT043 is a 3-pole motor circuit breaker from the TeSys Deca range, rated at 0.63 A with a thermal protection adjustment range of 0.4...0.63 A. The 45 mm width and 89 mm height keep it compact for a crowded enclosure. Spring terminals on the power circuit accept 1...6 mm² solid or 1.5...4 mm² flexible with cable end — no screwdriver torque check needed, which speeds up panel wiring. ## Motor protection ratings Rated for motor protection at 0.12 kW at 400/415 V AC and 0.37 kW at 690 V AC. The utilisation category is AC-3 and AC-3e per IEC 60947-4-1, which means it's designed for starting and stopping squirrel-cage motors — the AC-3e suffix indicates enhanced electrical durability for high-cycle applications. Electrical durability is rated at 100,000 cycles for AC-3 at 415 V In, matching the mechanical durability figure.","metaTitle":"GV2RT043 TeSys Deca Motor Circuit Breaker, 0.63 A, 100 kA","metaDescription":"GV2RT043 motor circuit breaker, 0.63 A rated current, thermal-magnetic trip, 100 kA breaking capacity at 400 V. TeSys Deca range. Current lifecycle stage.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"78.5 mm","Range":"TeSys Deca","Width":"45 mm","Height":"89 mm","Standards":"EN/IEC 60947-2 EN/IEC 60947-4-1","Rated duty":"Uninterrupted conforming to IEC 60947-4-1","Fixing mode":"35 mm symmetrical DIN rail: clipped Panel: screwed (with adaptor plate)","Control type":"Toggle","Network type":"AC","Product name":"TeSys GV2","Motor power kW":"0.12 kW at 400/415 V AC 50/60 Hz motor protection high peak current 0.18 kW at 400/415 V AC 50/60 Hz motor protection high peak current 0.18 kW at 440 V AC 50/60 Hz motor protection high peak current 0.37 kW at 690 V AC 50/60 Hz motor protection high peak current","Fire resistance":"960 °C conforming to IEC 60695-2-11","lifecycle_stage":"current","Breaking capacity":"100 kA Icu at 220/230 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"GV2RT","Mounting position":"Horizontal Vertical","Network frequency":"50/60 Hz conforming to IEC 60947-2","Poles description":"3P","Climatic withstand":"conforming to IACS E10","Device application":"Motor protection Transformer","Operating altitude":"<= 2000 m","[In] rated current":"0.63 A","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1 AC-3e conforming to IEC 60947-4-1","Electrical durability":"100000 cycles for AC-3 at 415 V In 100000 cycles for AC-3e at 415 V In","Mechanical durability":"100000 cycles","Mechanical robustness":"Shocks: 30 Gn for 11 ms Vibrations: 5 Gn, 5...150 Hz","Connections - terminals":"Power circuit: spring terminals 2 cable(s) 1...6 mm²solid Power circuit: spring terminals 2 cable(s) 1.5...4 mm²flexible without cable end Power circuit: spring terminals 2 cable(s) 1...4 mm²flexible with cable end","IK degree of protection":"IK04","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping current":"13 A","Product or component type":"Motor circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-1","Power dissipation per pole":"2.5 W","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-40...80 °C","Thermal protection adjustment range":"0.4...0.63 A conforming to IEC 60947-2","Ambient air temperature for operation":"-20...60 °C","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","[Ith] conventional free air thermal current":"0.63 A conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/20d6bee8b579fd26b2c2be202165539d.pdf","sourceUrl":"https://www.se.com/vn/en/product/GV2RT043/motor-circuit-breaker-tesys-deca-3p-0-40-63-a-thermal-magnetic-spring-terminals/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV2RT043/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for GV2RT043?","answer":"Rated current 0.63 A, thermal protection adjustment range 0.4...0.63 A, breaking capacity 100 kA Icu at 400/415 V AC, rated operational voltage 690 V AC, and it meets EN/IEC 60947-2 and EN/IEC 60947-4-1."},{"question":"What compliance documentation does Schneider Electric provide for GV2RT043?","answer":"The part is certified to EN/IEC 60947-2 and EN/IEC 60947-4-1, and carries a fire resistance rating of 960 °C per IEC 60695-2-11. Climatic withstand conforms to IACS. The IP degree of protection is IP20 per IEC 60529."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2RT043","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2RT043 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}