{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2RT05","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2RT05","canonicalUrl":"https://aoctrl.com/schneider/GV2RT05","factsUrl":"https://aoctrl.com/api/mcp/products/GV2RT05","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca GV2RT05 Motor Circuit Breaker, 3-Pole, 1A, Thermal-Magnetic, 100 kA Icu, IP20.","salesMarkdown":"## Panel-Side Specs at a Glance Breaking capacity hits 100 kA Icu across the 220–690 V AC range, so it meets high-fault panels without extra upstream fusing. Control is via toggle, and the enclosure is IP20 for basic finger-safe protection. Power terminals accept 1–6 mm² solid or 1.5–6 mm² flexible wire. Tightening torque is 1.7 N·m. ## Compliance & Certifications Marked as suitable for isolation per IEC 60947-1. Also meets glow-wire test at 960°C per IEC 60695-2-11. Rated operational voltage 690 V AC, insulation voltage 690 V AC. Power dissipation at rated current is 2.5 W per pole — factor that into panel thermal calculations.","metaTitle":"Schneider Electric GV2RT05 Motor Circuit Breaker, 1A","metaDescription":"GV2RT05 TeSys Deca motor circuit breaker, 1 A rated, 3-pole, thermal-magnetic, 100 kA Icu. Active production. Complies with IEC 60947-2/4-1. Order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"3.09 in (78.5 mm)","Range":"TeSys Deca","Width":"1.8 in (45 mm)","Height":"3.5 in (89 mm)","Category":"US10I1122367","Standards":"EN/IEC 60947-2 EN/IEC 60947-4-1","Rated duty":"Uninterrupted IEC 60947-4-1","Fixing mode":"35 mm symmetrical DIN rail clipped Panel screwed with adaptor plate)","Control Type":"Toggle","Network type":"AC","Product name":"TeSys GV2","Motor power kW":"0.09 kW 220/230 V AC 50/60 Hz motor protection high peak current 0.12 kW 220/230 V AC 50/60 Hz motor protection high peak current 0.25 kW 400/415 V AC 50/60 Hz motor protection high peak current 0.37 kW 400/415 V AC 50/60 Hz motor protection high peak current 0.25 kW 440 V AC 50/60 Hz motor protection high peak current 0.37 kW 440 V AC 50/60 Hz motor protection high peak current 0.37 kW 500 V AC 50/60 Hz motor protection high peak current 0.55 kW 690 V AC 50/60 Hz motor protection high peak current 0.63 kW 440 V AC 50/60 Hz transformer protection 0.63 kW 500 V AC 50/60 Hz transformer protection 1 kW 690 V AC 50/60 Hz transformer protection","Fire resistance":"1760 °F (960 °C) IEC 60695-2-11","lifecycle_stage":"current","Breaking capacity":"100 kA Icu 220/230 V AC 50/60 Hz IEC 60947-2 100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 100 kA Icu 440 V AC 50/60 Hz IEC 60947-2 100 kA Icu 500 V AC 50/60 Hz IEC 60947-2 100 kA Icu 690 V AC 50/60 Hz IEC 60947-2","Device short name":"GV2RT","Mounting position":"Horizontal Vertical","Network frequency":"50/60 Hz IEC 60947-2","Poles description":"3P","Tightening torque":"15.05 lbf.in (1.7 N.m) screw clamp terminal","Climatic withstand":"IACS E10","Device Application":"Motor protection Transformer","Line Rated Current":"1 A","Operating altitude":"<= 6561.68 ft (2000 m)","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A IEC 60947-2 AC-3 IEC 60947-4-1 AC-3e IEC 60947-4-1","Electrical durability":"100000 cycles AC-3 415 V In 100000 cycles AC-3e 415 V In","Mechanical durability":"100000 cycles","Mechanical robustness":"Shocks 30 Gn for 11 ms Vibrations 5 Gn, 5...150 Hz","Nbr. of units in pkg.":"1","Connections - terminals":"Power circuit screw clamp terminal 2 0.002...0.009 in² (1...6 mm²)solid Power circuit screw clamp terminal 2 0.002...0.009 in² (1.5...6 mm²)flexible without cable end Power circuit screw clamp terminal 2 0.002...0.006 in² (1...4 mm²)flexible with cable end","IK degree of protection":"IK04","IP degree of protection":"IP20 IEC 60529","Magnetic tripping current":"22 A","Product or Component Type":"Motor circuit breaker","Suitability for isolation":"Yes IEC 60947-1","Power dissipation per pole":"2.5 W","[Ui] rated insulation voltage":"690 V AC 50/60 Hz IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz IEC 60947-2","Ambient Air Temperature for Storage":"-40...176 °F (-40...80 °C)","Thermal protection adjustment range":"0.63...1 A IEC 60947-2","Ambient air temperature for operation":"-4...140 °F (-20...60 °C)","[Uimp] rated impulse withstand voltage":"6 kV IEC 60947-2","[Ith] conventional free air thermal current":"1 A IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$38.10","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/374b4183068226eb65a40123574d7942.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/GV2RT05/alternatives.json"},"ai":{"faq":[{"question":"What is the GV2RT05's depth?","answer":"Depth is 3.09 inches (78.5 mm). Combined with a height of 3.5 inches and width of 1.8 inches, it fits standard DIN-rail envelopes."},{"question":"What standards does the GV2RT05 comply with?","answer":"It is certified to EN/IEC 60947-2 for circuit-breaker performance and EN/IEC 60947-4-1 for motor-starter coordination. It also carries an IEC 60947-1 suitability-for-isolation marking."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2RT05","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2RT05 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}