{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2RT053","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2RT053","canonicalUrl":"https://aoctrl.com/schneider/GV2RT053","factsUrl":"https://aoctrl.com/api/mcp/products/GV2RT053","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca GV2RT053 motor circuit breaker, 3-pole, thermal-magnetic, In 1 A, 100 kA breaking capacity, spring terminals, DIN rail mount.","salesMarkdown":"It provides motor and transformer protection, with a thermal adjustment range of 0.63...1 A, so the 1 A setting is the top end of the adjustment band — set it to match the motor full-load current, not the breaker's own rating. Breaking capacity is 100 kA Icu across the full voltage range (220...690 V AC, 50/60 Hz), certified to IEC 60947-2. The 45 mm width and 89 mm height keep the panel fill factor tight — three of these side by side take 135 mm of rail. Spring terminals accept 1...6 mm² solid or 1.5...4 mm² flexible with cable end, so it wires directly into the motor branch circuit without lug adaptors. IP20 finger-safe enclosure (IK04 impact rating) suits it for enclosed panels, not washdown zones. Ambient operating range -20...60 °C, storage -40...80 °C, with 2.5 W power dissipation per pole — factor that into enclosure thermal calculations if you're packing several breakers in a small cabinet. Rated operational voltage (Ue) 690 V AC, insulation voltage (Ui) 690 V AC, impulse withstand (Uimp) 6 kV. Suitability for isolation per IEC 60947-1 — it can serve as a disconnecting means in the motor circuit. Electrical durability 100,000 cycles at AC-3/AC-3e at 415 V; mechanical durability 100,000 cycles. Magnetic trip fixed at 22 A, so short-circuit protection is independent of the thermal dial. Motor power ratings span 0.09 kW at 230 V up to 0.55 kW at 690 V (high peak current motor protection), and up to 1 kW for transformer protection at 690 V. The 1 A thermal setting covers small motors and control transformers in the sub-1 kW range.","metaTitle":"Schneider TeSys GV2RT053 Motor Circuit Breaker, 1 A, 100 kA","metaDescription":"Schneider Electric TeSys GV2RT053 motor circuit breaker, 1 A rated current, thermal-magnetic trip, 100 kA breaking capacity, DIN rail mount. Active lifecycle, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"78.5 mm","Range":"TeSys Deca","Width":"45 mm","Height":"89 mm","Standards":"EN/IEC 60947-2 EN/IEC 60947-4-1","Rated duty":"Uninterrupted conforming to IEC 60947-4-1","Fixing mode":"35 mm symmetrical DIN rail: clipped Panel: screwed (with adaptor plate)","Control type":"Toggle","Network type":"AC","Product name":"TeSys GV2","Motor power kW":"0.09 kW at 220/230 V AC 50/60 Hz motor protection high peak current 0.12 kW at 220/230 V AC 50/60 Hz motor protection high peak current 0.25 kW at 400/415 V AC 50/60 Hz motor protection high peak current 0.37 kW at 400/415 V AC 50/60 Hz motor protection high peak current 0.25 kW at 440 V AC 50/60 Hz motor protection high peak current 0.37 kW at 440 V AC 50/60 Hz motor protection high peak current 0.37 kW at 500 V AC 50/60 Hz motor protection high peak current 0.55 kW at 690 V AC 50/60 Hz motor protection high peak current 0.63 kW at 440 V AC 50/60 Hz transformer protection 0.63 kW at 500 V AC 50/60 Hz transformer protection 1 kW at 690 V AC 50/60 Hz transformer protection","Fire resistance":"960 °C conforming to IEC 60695-2-11","lifecycle_stage":"current","Breaking capacity":"100 kA Icu at 220/230 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"GV2RT","Mounting position":"Horizontal Vertical","Network frequency":"50/60 Hz conforming to IEC 60947-2","Poles description":"3P","Climatic withstand":"conforming to IACS E10","Device application":"Motor protection Transformer","Operating altitude":"<= 2000 m","[In] rated current":"1 A","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1 AC-3e conforming to IEC 60947-4-1","Electrical durability":"100000 cycles for AC-3 at 415 V In 100000 cycles for AC-3e at 415 V In","Mechanical durability":"100000 cycles","Mechanical robustness":"Shocks: 30 Gn for 11 ms Vibrations: 5 Gn, 5...150 Hz","Connections - terminals":"Power circuit: spring terminals 2 cable(s) 1...6 mm²solid Power circuit: spring terminals 2 cable(s) 1.5...4 mm²flexible without cable end Power circuit: spring terminals 2 cable(s) 1...4 mm²flexible with cable end","IK degree of protection":"IK04","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping current":"22 A","Product or component type":"Motor circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-1","Power dissipation per pole":"2.5 W","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-40...80 °C","Thermal protection adjustment range":"0.63...1 A conforming to IEC 60947-2","Ambient air temperature for operation":"-20...60 °C","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","[Ith] conventional free air thermal current":"1 A conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/4ea6ea207168d820113a8f6fa1d846de.pdf","sourceUrl":"https://www.se.com/th/en/product/GV2RT053/motor-circuit-breakertesys-deca3p0-631athermal-magneticspring-terminalstoggle-handle/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV2RT053/alternatives.json"},"ai":{"faq":[{"question":"What is the closest alternative to GV2RT053 in the same family?","answer":"Within the TeSys Deca GV2RT range, the closest peer is the GV2RT05 (0.63...1 A thermal adjustment, same 1 A In) — functionally identical for the 1 A setting. The GV2RT053 is the standard order code; the GV2RT05 may be a different packaging or regional variant. Confirm the exact order code against your BOM before substituting."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2RT053","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2RT053 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}