{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2RT05AE11TQ","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2RT05AE11TQ","canonicalUrl":"https://aoctrl.com/schneider/GV2RT05AE11TQ","factsUrl":"https://aoctrl.com/api/mcp/products/GV2RT05AE11TQ","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca GV2RT05AE11TQ motor circuit breaker, 3-pole, thermal-magnetic, 1 A rated current, 100 kA breaking capacity at 400 V AC.","salesMarkdown":"It uses a thermal-magnetic trip unit, with a rated current of 1 A and a magnetic tripping threshold of 22 A — meaning it protects against overloads (thermal) and short-circuits (magnetic) in one compact device. Rated for uninterrupted duty per IEC 60947-4-1, it is suitable for continuous motor loads. IP20 finger-safe protection (IEC 60529) and IK04 impact resistance suit it for enclosed panel installation. Climatic withstand per IACS covers marine and humid environments.","metaTitle":"Schneider TeSys GV2RT05AE11TQ Motor Circuit Breaker, 1 A, 10","metaDescription":"Schneider Electric TeSys GV2RT05AE11TQ motor circuit breaker, 1 A rated current, 100 kA breaking capacity at 400 V, thermal-magnetic trip, 3-pole, DIN rail mount, current lifecycle","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"78.5 mm","Range":"TeSys Deca","Width":"45 mm","Height":"89 mm","Standards":"EN/IEC 60947-2 EN/IEC 60947-4-1","Rated duty":"Uninterrupted conforming to IEC 60947-4-1","Fixing mode":"35 mm symmetrical DIN rail: clipped Panel: screwed (with adaptor plate)","Control type":"Toggle","Network type":"AC","Product name":"TeSys GV2","Motor power kW":"0.09 kW at 220/230 V AC 50/60 Hz motor protection high peak current 0.12 kW at 220/230 V AC 50/60 Hz motor protection high peak current 0.25 kW at 400/415 V AC 50/60 Hz motor protection high peak current 0.37 kW at 400/415 V AC 50/60 Hz motor protection high peak current 0.25 kW at 440 V AC 50/60 Hz motor protection high peak current 0.37 kW at 440 V AC 50/60 Hz motor protection high peak current 0.37 kW at 500 V AC 50/60 Hz motor protection high peak current 0.55 kW at 690 V AC 50/60 Hz motor protection high peak current 0.63 kW at 440 V AC 50/60 Hz transformer protection 0.63 kW at 500 V AC 50/60 Hz transformer protection 1 kW at 690 V AC 50/60 Hz transformer protection","Fire resistance":"960 °C conforming to IEC 60695-2-11","lifecycle_stage":"current","Quantity per set":"Set of 24","Breaking capacity":"100 kA Icu at 220/230 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"GV2RT","Mounting position":"Horizontal Vertical","Network frequency":"50/60 Hz conforming to IEC 60947-2","Poles description":"3P","Tightening torque":"1.7 N.m - on screw clamp terminal","Climatic withstand":"conforming to IACS E10","Device application":"Motor protection Transformer","Operating altitude":"<= 2000 m","[In] rated current":"1 A","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1 AC-3e conforming to IEC 60947-4-1","Electrical durability":"100000 cycles for AC-3 at 415 V In 100000 cycles for AC-3e at 415 V In","Mechanical durability":"100000 cycles","Mechanical robustness":"Shocks: 30 Gn for 11 ms Vibrations: 5 Gn, 5...150 Hz","Connections - terminals":"Power circuit: screw clamp terminal 2 cable(s) 1...6 mm²solid Power circuit: screw clamp terminal 2 cable(s) 1.5...6 mm²flexible without cable end Power circuit: screw clamp terminal 2 cable(s) 1...4 mm²flexible with cable end","IK degree of protection":"IK04","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping current":"22 A","Product or component type":"Motor circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-1","Power dissipation per pole":"2.5 W","Auxiliary contact composition":"1 NO + 1 NC front","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-40...80 °C","Thermal protection adjustment range":"0.63...1 A conforming to IEC 60947-2","Ambient air temperature for operation":"-20...60 °C","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","[Ith] conventional free air thermal current":"1 A conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/be/en/product/GV2RT05AE11TQ/motor-circuit-breaker-tesys-deca-3p-0-631-a-thermal-magnetic-screw-clamp-terminals-with-gvae11-tq-24-units/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV2RT05AE11TQ/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this motor circuit breaker?","answer":"Rated current 1 A, magnetic tripping at 22 A, breaking capacity 100 kA at 400 V AC (IEC 60947-2), suitable for motor protection up to 0.55 kW at 690 V AC."},{"question":"What is the mounting method?","answer":"Snap-on 35 mm DIN rail or panel-mount with an adaptor plate. Accepts horizontal or vertical orientation."},{"question":"Does it include auxiliary contacts?","answer":"Yes, it comes with 1 NO + 1 NC front-mounted auxiliary contacts built in."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2RT05AE11TQ","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2RT05AE11TQ when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}