{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2RT06","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2RT06","canonicalUrl":"https://aoctrl.com/schneider/GV2RT06","factsUrl":"https://aoctrl.com/api/mcp/products/GV2RT06","rawCanonicalId":null},"summary":{"shortDescription":"TeSys Deca GV2RT06 motor circuit breaker, 1.6 A rated current, thermal-magnetic trip, 3 poles, 100 kA breaking capacity at 400 V.","salesMarkdown":"TeSys Deca GV2RT06 motor circuit breaker, 1.6 A line rated current, thermal-magnetic trip — three poles, isolation rated per IEC 60947-1. That isolation rating means a visible break when the handle is off; no floating contact that could leave a motor half-fed and a signal line live. 1.6 A thermal setting covers a 0.18 kW motor at 230 V or a 0.37 kW at 400 V. The magnetic trip is fixed at 33 A, and power dissipation is 2.5 W per pole. Breaking capacity holds 100 kA all the way up to 690 V (IEC 60947-2). Utilisation category AC-3 and AC-3e covers standard squirrel-cage motors and high-efficiency types. Mounts horizontal or vertical—no derating required for orientation. Terminals accept 1–6 mm² solid or 1.5–6 mm² flexible without ferrules; with ferrules, 1–4 mm². Tightening torque 1.7 N·m on the screw clamp. IP20 finger-safe when installed; IK04 impact rating handles tool drops. The GV2RT family is the current standard.","metaTitle":"TeSys Deca GV2RT06 Motor Circuit Breaker, 1.6 A","metaDescription":"TeSys Deca GV2RT06 motor circuit breaker, 1.6 A thermal-magnetic, 3P, 100 kA breaking capacity. Isolation rated. Active production. Source via RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"3.09 in (78.5 mm)","Range":"TeSys Deca","Width":"1.8 in (45 mm)","Height":"3.5 in (89 mm)","Category":"US10I1122367","Standards":"EN/IEC 60947-2 EN/IEC 60947-4-1","Rated duty":"Uninterrupted IEC 60947-4-1","Fixing mode":"35 mm symmetrical DIN rail clipped Panel screwed with adaptor plate)","Control Type":"Toggle","Network type":"AC","Product name":"TeSys GV2","Motor power kW":"0.18 kW 220/230 V AC 50/60 Hz motor protection high peak current 0.25 kW 220/230 V AC 50/60 Hz motor protection high peak current 0.37 kW 400/415 V AC 50/60 Hz motor protection high peak current 0.55 kW 400/415 V AC 50/60 Hz motor protection high peak current 0.37 kW 440 V AC 50/60 Hz motor protection high peak current 0.55 kW 440 V AC 50/60 Hz motor protection high peak current 0.37 kW 500 V AC 50/60 Hz motor protection high peak current 0.55 kW 500 V AC 50/60 Hz motor protection high peak current 0.75 kW 500 V AC 50/60 Hz motor protection high peak current 0.75 kW 690 V AC 50/60 Hz motor protection high peak current 1.1 kW 690 V AC 50/60 Hz motor protection high peak current 0.4 kW 230/240 V AC 50/60 Hz transformer protection 0.63 kW 400/415 V AC 50/60 Hz transformer protection","Fire resistance":"1760 °F (960 °C) IEC 60695-2-11","lifecycle_stage":"current","Breaking capacity":"100 kA Icu 220/230 V AC 50/60 Hz IEC 60947-2 100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 100 kA Icu 440 V AC 50/60 Hz IEC 60947-2 100 kA Icu 500 V AC 50/60 Hz IEC 60947-2 100 kA Icu 690 V AC 50/60 Hz IEC 60947-2","Device short name":"GV2RT","Mounting position":"Horizontal Vertical","Network frequency":"50/60 Hz IEC 60947-2","Poles description":"3P","Tightening torque":"15.05 lbf.in (1.7 N.m) screw clamp terminal","Climatic withstand":"IACS E10","Device Application":"Motor protection Transformer","Line Rated Current":"1.6 A","Operating altitude":"<= 6561.68 ft (2000 m)","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A IEC 60947-2 AC-3 IEC 60947-4-1 AC-3e IEC 60947-4-1","Electrical durability":"100000 cycles AC-3 415 V In 100000 cycles AC-3e 415 V In","Mechanical durability":"100000 cycles","Mechanical robustness":"Shocks 30 Gn for 11 ms Vibrations 5 Gn, 5...150 Hz","Nbr. of units in pkg.":"1","Connections - terminals":"Power circuit screw clamp terminal 2 0.002...0.009 in² (1...6 mm²)solid Power circuit screw clamp terminal 2 0.002...0.009 in² (1.5...6 mm²)flexible without cable end Power circuit screw clamp terminal 2 0.002...0.006 in² (1...4 mm²)flexible with cable end","IK degree of protection":"IK04","IP degree of protection":"IP20 IEC 60529","Magnetic tripping current":"33 A","Product or Component Type":"Motor circuit breaker","Suitability for isolation":"Yes IEC 60947-1","Power dissipation per pole":"2.5 W","[Ui] rated insulation voltage":"690 V AC 50/60 Hz IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz IEC 60947-2","Ambient Air Temperature for Storage":"-40...176 °F (-40...80 °C)","Thermal protection adjustment range":"1...1.6 A IEC 60947-2","Ambient air temperature for operation":"-4...140 °F (-20...60 °C)","[Uimp] rated impulse withstand voltage":"6 kV IEC 60947-2","[Ith] conventional free air thermal current":"1.6 A IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$39.09","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/374b4183068226eb65a40123574d7942.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/GV2RT06/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings of the GV2RT06?","answer":"1.6 A line rated current, thermal-magnetic trip, 3 poles, 100 kA breaking capacity at 230–690 V AC, isolation rated, enclosure IP20."},{"question":"What is the depth of the GV2RT06?","answer":"3.09 inches (78.5 mm) deep."},{"question":"What range is the GV2RT06 part of?","answer":"TeSys Deca range."},{"question":"What compliance standards does the GV2RT06 meet?","answer":"Meets EN/IEC 60947-2 and EN/IEC 60947-4-1. Fire resistance tested at 960 °C (IEC 60695-2-11). Protection class IP20, impact rating IK04. Suitable for isolation per IEC 60947-1."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2RT06","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2RT06 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}