{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2RT10","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2RT10","canonicalUrl":"https://aoctrl.com/schneider/GV2RT10","factsUrl":"https://aoctrl.com/api/mcp/products/GV2RT10","rawCanonicalId":null},"summary":{"shortDescription":"Schneider TeSys Deca GV2RT10 motor circuit breaker, 3-pole thermal-magnetic, 6.3 A rated, 100 kA breaking capacity at 230 V AC, 45 mm wide, IP20.","salesMarkdown":"Schneider GV2RT10 is a TeSys Deca motor circuit breaker – a three-pole thermal-magnetic device rated at 6.3 A continuous line current. It's built to protect motor circuits per IEC 60947-4-1 and serve as a disconnect with isolation capability per IEC 60947-2. The magnetic trip is fixed at 138 A, so inrush holds for most standard induction motors up to 1.1 kW at 230 V or 2.2 kW at 400 V. Breaking capacity hits 100 kA at 230/400 V, dropping to 3 kA at 690 V – enough for most industrial panel feeds. That's the same 45 mm width as the rest of the TeSys Deca line, so it slides into a populated DIN rail without re-spacing. ## Breaking Capacity and Durability Rated for uninterrupted duty per IEC 60947-4-1 with utilisation category AC-3 and AC-3e (motor switching). Breaking capacity varies by voltage: 100 kA at 220/230 V, 100 kA at 400/415 V, 50 kA at 440 V and 500 V, and 3 kA at 690 V – all under IEC 60947-2. Electrical durability is 100,000 cycles at rated current in AC-3; mechanical durability also 100,000 cycles. 2.5 W power dissipation per pole at full load – negligible for most cabinets but worth summing if you're packing a dense row of breakers.","metaTitle":"Schneider GV2RT10 TeSys Deca Motor Circuit Breaker, 6.3 A","metaDescription":"Active 3-pole thermal-magnetic motor circuit breaker, 6.3 A rated, 100 kA breaking capacity. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"3.09 in (78.5 mm)","Range":"TeSys Deca","Width":"1.8 in (45 mm)","Height":"3.5 in (89 mm)","Category":"US10I1122367","Standards":"EN/IEC 60947-2 EN/IEC 60947-4-1","Rated duty":"Uninterrupted IEC 60947-4-1","Fixing mode":"35 mm symmetrical DIN rail clipped Panel screwed with adaptor plate)","Control Type":"Toggle","Network type":"AC","Product name":"TeSys GV2","Motor power kW":"1.1 kW 220/230 V AC 50/60 Hz motor protection high peak current 2.2 kW 400/415 V AC 50/60 Hz motor protection high peak current 2.2 kW 440 V AC 50/60 Hz motor protection high peak current 3 kW 440 V AC 50/60 Hz motor protection high peak current 3 kW 500 V AC 50/60 Hz motor protection high peak current 4 kW 690 V AC 50/60 Hz motor protection high peak current 1.6 kW 230/240 V AC 50/60 Hz transformer protection 2 kW 230/240 V AC 50/60 Hz transformer protection 2.5 kW 400/415 V AC 50/60 Hz transformer protection 2.5 kW 440 V AC 50/60 Hz transformer protection 4 kW 440 V AC 50/60 Hz transformer protection 4 kW 500 V AC 50/60 Hz transformer protection 4 kW 690 V AC 50/60 Hz transformer protection 5 kW 690 V AC 50/60 Hz transformer protection 6.3 kW 690 V AC 50/60 Hz transformer protection","Fire resistance":"1760 °F (960 °C) IEC 60695-2-11","lifecycle_stage":"current","Breaking capacity":"100 kA Icu 220/230 V AC 50/60 Hz IEC 60947-2 100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 50 kA Icu 440 V AC 50/60 Hz IEC 60947-2 50 kA Icu 500 V AC 50/60 Hz IEC 60947-2 3 kA Icu 690 V AC 50/60 Hz IEC 60947-2","Device short name":"GV2RT","Mounting position":"Horizontal Vertical","Network frequency":"50/60 Hz IEC 60947-2","Poles description":"3P","Tightening torque":"15.05 lbf.in (1.7 N.m) screw clamp terminal","Climatic withstand":"IACS E10","Device Application":"Motor protection Transformer","Line Rated Current":"6.3 A","Operating altitude":"<= 6561.68 ft (2000 m)","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A IEC 60947-2 AC-3 IEC 60947-4-1 AC-3e IEC 60947-4-1","Electrical durability":"100000 cycles AC-3 415 V In 100000 cycles AC-3e 415 V In","Mechanical durability":"100000 cycles","Mechanical robustness":"Shocks 30 Gn for 11 ms Vibrations 5 Gn, 5...150 Hz","Nbr. of units in pkg.":"1","Connections - terminals":"Power circuit screw clamp terminal 2 0.002...0.009 in² (1...6 mm²)solid Power circuit screw clamp terminal 2 0.002...0.009 in² (1.5...6 mm²)flexible without cable end Power circuit screw clamp terminal 2 0.002...0.006 in² (1...4 mm²)flexible with cable end","IK degree of protection":"IK04","IP degree of protection":"IP20 IEC 60529","Magnetic tripping current":"138 A","Product or Component Type":"Motor circuit breaker","Suitability for isolation":"Yes IEC 60947-1","Power dissipation per pole":"2.5 W","[Ui] rated insulation voltage":"690 V AC 50/60 Hz IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz IEC 60947-2","Ambient Air Temperature for Storage":"-40...176 °F (-40...80 °C)","Thermal protection adjustment range":"4...6.3 A IEC 60947-2","Ambient air temperature for operation":"-4...140 °F (-20...60 °C)","[Uimp] rated impulse withstand voltage":"6 kV IEC 60947-2","[Ith] conventional free air thermal current":"6.3 A IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$38.10","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/870eb39e167e3567e6d3036f7612dbd2.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/GV2RT10/alternatives.json"},"ai":{"faq":[{"question":"What is the mounting depth of the GV2RT10?","answer":"The depth is 3.09 inches (78.5 mm). That's the body depth, not including handle projection or terminal clearance."},{"question":"What range does the GV2RT10 belong to?","answer":"It's part of the TeSys Deca range from Schneider Electric."},{"question":"What compliance standards does the GV2RT10 meet?","answer":"It complies with EN/IEC 60947-2 and EN/IEC 60947-4-1, has fire resistance at 960 °C (IEC 60695-2-11), IP20 and IK04 protection, and is suitable for isolation per IEC 60947-1."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2RT10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2RT10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}