{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2RT163","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2RT163","canonicalUrl":"https://aoctrl.com/schneider/GV2RT163","factsUrl":"https://aoctrl.com/api/mcp/products/GV2RT163","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca GV2RT163 motor circuit breaker, thermal-magnetic, 3-pole, 14 A rated current, spring terminals, DIN rail mount.","salesMarkdown":"Its thermal-magnetic trip unit combines a bimetallic overload element adjustable from 9 to 14 A with a fixed magnetic trip set at 280 A, so it handles both sustained overloads and short-circuit faults in one package. Rated for uninterrupted duty per IEC 60947-4-1, it carries a 14 A continuous current and is listed for motor protection at 2.2 kW on 230 V AC up to 11 kW on 690 V AC. For transformer protection, the same unit covers 4 kW at 230/240 V AC up to 12.5 kW at 690 V AC. The breaking capacity (Icu) per IEC 60947-2 is 100 kA at 230 V AC, dropping to 15 kA at 400/415 V, 8 kA at 440 V, 6 kA at 500 V, and 3 kA at 690 V. The 45 mm width (one standard modular unit) slots into a crowded enclosure without stealing extra space. Horizontal or vertical orientation is permitted. Power connections are spring terminals accepting 1 to 6 mm² solid or 1.5 to 4 mm² flexible wire (with or without ferrules). No screwdriver torque check needed — the spring cage holds the conductor firmly and resists vibration loosening. IP20 finger-safe protection on the front face; IK04 impact resistance. The enclosure is self-extinguishing at 960 °C per IEC 60695-2-11. No substitution guesswork needed — this is the active, current-build part. Altitude limited to 2000 m without derating. Climatic withstand conforms to IACS for marine and humid environments. Rated for 100,000 mechanical cycles and 100,000 electrical cycles under AC-3 duty at 415 V. Shock tested to 30 Gn for 11 ms, vibration to 5 Gn across 5–150 Hz — suitable for installation on machinery subject to moderate impact or continuous vibration. Power dissipation is 2.5 W per pole, so total heat load in the enclosure is 7.5 W at rated current.","metaTitle":"TeSys GV2RT163 Motor Circuit Breaker, 14 A, Thermal-Magnetic","metaDescription":"GV2RT163 motor circuit breaker from TeSys Deca range. Rated 14 A, thermal-magnetic trip, 100 kA breaking capacity at 230 V AC. Active production. DIN rail mount. Spring terminals.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"78.5 mm","Range":"TeSys Deca","Width":"45 mm","Height":"89 mm","Standards":"EN/IEC 60947-2 EN/IEC 60947-4-1","Rated duty":"Uninterrupted conforming to IEC 60947-4-1","Fixing mode":"35 mm symmetrical DIN rail: clipped Panel: screwed (with adaptor plate)","Control type":"Toggle","Network type":"AC","Product name":"TeSys GV2","Motor power kW":"2.2 kW at 220/230 V AC 50/60 Hz motor protection high peak current 3 kW at 220/230 V AC 50/60 Hz motor protection high peak current 5.5 kW at 400/415 V AC 50/60 Hz motor protection high peak current 5.5 kW at 440 V AC 50/60 Hz motor protection high peak current 7.5 kW at 440 V AC 50/60 Hz motor protection high peak current 7.5 kW at 500 V AC 50/60 Hz motor protection high peak current 9 kW at 690 V AC 50/60 Hz motor protection high peak current 11 kW at 690 V AC 50/60 Hz motor protection high peak current 4 kW at 230/240 V AC 50/60 Hz transformer protection 6.3 kW at 400/415 V AC 50/60 Hz transformer protection 10 kW at 690 V AC 50/60 Hz transformer protection 12.5 kW at 690 V AC 50/60 Hz transformer protection","Fire resistance":"960 °C conforming to IEC 60695-2-11","lifecycle_stage":"current","Breaking capacity":"100 kA Icu at 220/230 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 6 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"GV2RT","Mounting position":"Horizontal Vertical","Network frequency":"50/60 Hz conforming to IEC 60947-2","Poles description":"3P","Climatic withstand":"conforming to IACS E10","Device application":"Motor protection Transformer","Operating altitude":"<= 2000 m","[In] rated current":"14 A","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1 AC-3e conforming to IEC 60947-4-1","Electrical durability":"100000 cycles for AC-3 at 415 V In 100000 cycles for AC-3e at 415 V In","Mechanical durability":"100000 cycles","Mechanical robustness":"Shocks: 30 Gn for 11 ms Vibrations: 5 Gn, 5...150 Hz","Connections - terminals":"Power circuit: spring terminals 2 cable(s) 1...6 mm²solid Power circuit: spring terminals 2 cable(s) 1.5...4 mm²flexible without cable end Power circuit: spring terminals 2 cable(s) 1...4 mm²flexible with cable end","IK degree of protection":"IK04","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping current":"280 A","Product or component type":"Motor circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-1","Power dissipation per pole":"2.5 W","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-40...80 °C","Thermal protection adjustment range":"9...14 A conforming to IEC 60947-2","Ambient air temperature for operation":"-20...60 °C","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","[Ith] conventional free air thermal current":"14 A conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/65b0ef435bb5ebf917af3fade58b160f.pdf","sourceUrl":"https://www.se.com/th/en/product/GV2RT163/motor-circuit-breakertesys-deca3p914athermal-magneticspring-terminalstoggle-handle/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV2RT163/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for the GV2RT163?","answer":"Rated current is 14 A with a thermal adjustment range of 9 to 14 A. Magnetic trip is fixed at 280 A. Breaking capacity reaches 100 kA at 230 V AC and 15 kA at 400/415 V AC. It is a 3-pole thermal-magnetic motor circuit breaker rated for 690 V AC insulation voltage."},{"question":"What compliance documentation does Schneider provide for the GV2RT163?","answer":"The GV2RT163 is certified to EN/IEC 60947-2 and EN/IEC 60947-4-1. It carries IP20 protection per IEC 60529, IK04 impact rating, and fire resistance at 960 °C per IEC 60695-2-11. It is suitable for isolation per IEC 60947-1. The manufacturer provides standard declarations of conformity for CE marking; specific RoHS and REACH documentation is available through the Schneider Electric compliance portal."},{"question":"What is the GV2RT163's depth?","answer":"The depth is 78.5 mm. Width is 45 mm and height is 89 mm, so it occupies a single modular unit on a DIN rail."},{"question":"What is the GV2RT163's range?","answer":"It belongs to the TeSys Deca range, specifically the GV2RT device short name series. This is the standard motor circuit breaker family from Schneider Electric for motor and transformer protection."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2RT163","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2RT163 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}