{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV3L32","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV3L32","canonicalUrl":"https://aoctrl.com/schneider/GV3L32","factsUrl":"https://aoctrl.com/api/mcp/products/GV3L32","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca GV3L32 motor circuit breaker, 32 A, 100 kA Icu, magnetic trip 448 A, IP20, for DIN rail or panel mount.","salesMarkdown":"## What a 100 kA breaker with a fixed 448 A trip means for your panel The 32 A GV3L32 from Schneider’s TeSys Deca range is a magnetic-only motor circuit breaker with a fixed trip at 448 A and 100 kA breaking capacity at 230/240 V. The magnetic trip unit responds only to short circuits; for overload protection, pair it with a separate thermal overload relay. ## Lifecycle, sourcing, and compliance For compliance documentation, the breaker holds approvals per EN/IEC 60947-2 and 60947-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1. That covers the major certification bodies for industrial motor circuits.","metaTitle":"Schneider GV3L32 Motor Circuit Breaker, 32 A","metaDescription":"Schneider GV3L32 TeSys Deca motor circuit breaker, 32 A rated current, 100 kA breaking capacity at 230/240 V. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Dark grey","Depth":"5.4 in (136 mm)","Range":"TeSys Deca","Width":"2.2 in (55 mm)","Height":"5.2 in (132 mm)","Category":"US10I1122366","Standards":"EN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC/EN 60335-1:Clause 30.2 IEC/EN 60335-2-40:Annex JJ","Rated duty":"Uninterrupted IEC 60947-4-1","Fixing mode":"35 mm symmetrical DIN rail clipped Panel screwed with 3 x M4 screws)","Control Type":"Rotary handle","Network type":"AC","Product name":"TeSys GV3","Motor power kW":"15 kW 400/415 V AC 50/60 Hz 18.5 kW 500 V AC 50/60 Hz 22 kW 690 V AC 50/60 Hz","Fire resistance":"1760 °F (960 °C) IEC 60695-2-11","lifecycle_stage":"current","Breaking capacity":"100 kA Icu 230/240 V AC 50/60 Hz 100 kA Icu 400/415 V AC 50/60 Hz 50 kA Icu 440 V AC 50/60 Hz 12 kA Icu 500 V AC 50/60 Hz 6 kA Icu 690 V AC 50/60 Hz","Device short name":"GV3L","Mounting position":"Horizontal Vertical","Network frequency":"50/60 Hz IEC 60947-2","Poles description":"3P","Tightening torque":"44.3 lbf.in (5 N.m) screw clamp terminal","Climatic withstand":"IACS E10","Device Application":"Motor protection","Line Rated Current":"32 A","Operating altitude":"9842.52 ft (3000 m)","Trip unit technology":"Magnetic","Utilisation category":"Category A IEC 60947-2 AC-3 IEC 60947-4-1","Electrical durability":"50000 cycles AC-3 415 V In","Mechanical durability":"50000 cycles","Mechanical robustness":"Shocks 15 Gn for 11 ms contactor open Shocks 30 Gn for 11 ms contactor closed Vibrations 4 Gn, 5...300 Hz","Nbr. of units in pkg.":"1","IP degree of protection":"IP20 IEC 60529","Magnetic tripping current":"448 A","Product or Component Type":"Motor circuit breaker","Suitability for isolation":"Yes IEC 60947-1","Power dissipation per pole":"8 W","[Ui] rated insulation voltage":"690 V AC 50/60 Hz IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz IEC 60947-2","Ambient Air Temperature for Storage":"-40...176 °F (-40...80 °C)","Ambient air temperature for operation":"-4...140 °F (-20...60 °C)","[Uimp] rated impulse withstand voltage":"6 kV IEC 60947-2","[Ith] conventional free air thermal current":"32 A IEC 60947-2","[Ics] rated service short-circuit breaking capacity":"100 % 230/240 V AC 50/60 Hz 100 % 400/415 V AC 50/60 Hz 100 % 440 V AC 50/60 Hz 50 % 500 V AC 50/60 Hz 50 % 690 V AC 50/60 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$58.42","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/da9ba0ac030f5b5772e46008aac3849a.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/GV3L32/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation does this brand provide for GV3L32?","answer":"The GV3L32 is certified to EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1, among others."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV3L32","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV3L32 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}