{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV3L50","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV3L50","canonicalUrl":"https://aoctrl.com/schneider/GV3L50","factsUrl":"https://aoctrl.com/api/mcp/products/GV3L50","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric GV3L50, TeSys Deca motor circuit breaker, 3-pole, 50 A magnetic trip, 22 kW at 400 V AC-3 duty.","salesMarkdown":"It handles motor loads up to 22 kW at 400 V AC-3, and breaking capacity reaches 100 kA at 240 V. IP20 finger-safe terminals. Ships as a single unit. Fixing options: clip to 35 mm symmetrical DIN rail, or panel mount with three M4 screws at 44.3 lbf·in (5 N·m) torque. Width 55 mm (2.2 in) on the rail. Rotary handle control. Horizontal or vertical mounting allowed. Meets EN/IEC 60947-2 and 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, plus IEC/EN 60335-1 Clause 30.2 and 60335-2-40 Annex JJ for thermal aging. Fire resistance tested at 960 °C (IEC 60695-2-11). Climatic withstand per IACS.","metaTitle":"Schneider GV3L50 TeSys Deca Motor Circuit Breaker 50A","metaDescription":"Motor circuit breaker, 50 A rated current, 22 kW at 400 V AC-3 duty. Breaking capacity 100 kA at 240 V. Active production, sourced to order. UL/CSA/IEC listed.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Dark grey","Depth":"5.4 in (136 mm)","Range":"TeSys Deca","Width":"2.2 in (55 mm)","Height":"5.2 in (132 mm)","Category":"US10I1122366","Standards":"EN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC/EN 60335-1:Clause 30.2 IEC/EN 60335-2-40:Annex JJ","Rated duty":"Uninterrupted IEC 60947-4-1","Fixing mode":"35 mm symmetrical DIN rail clipped Panel screwed with 3 x M4 screws)","Control Type":"Rotary handle","Network type":"AC","Product name":"TeSys GV3","Motor power kW":"22 kW 400/415 V AC 50/60 Hz 30 kW 500 V AC 50/60 Hz 45 kW 690 V AC 50/60 Hz","Product Weight":"2.12 lb(US) (0.96 kg)","Fire resistance":"1760 °F (960 °C) IEC 60695-2-11","lifecycle_stage":"current","Breaking capacity":"100 kA Icu 230/240 V AC 50/60 Hz 50 kA Icu 400/415 V AC 50/60 Hz 50 kA Icu 440 V AC 50/60 Hz 12 kA Icu 500 V AC 50/60 Hz 6 kA Icu 690 V AC 50/60 Hz","Device short name":"GV3L","Mounting position":"Horizontal Vertical","Network frequency":"50/60 Hz IEC 60947-2","Poles description":"3P","Tightening torque":"44.3 lbf.in (5 N.m) screw clamp terminal","Climatic withstand":"IACS E10","Device Application":"Motor protection","Line Rated Current":"50 A","Operating altitude":"9842.52 ft (3000 m)","Trip unit technology":"Magnetic","Utilisation category":"Category A IEC 60947-2 AC-3 IEC 60947-4-1","Electrical durability":"50000 cycles AC-3 415 V In","Mechanical durability":"50000 cycles","Mechanical robustness":"Shocks 15 Gn for 11 ms contactor open Shocks 30 Gn for 11 ms contactor closed Vibrations 4 Gn, 5...300 Hz","Nbr. of units in pkg.":"1","IP degree of protection":"IP20 IEC 60529","Magnetic tripping current":"700 A","Product or Component Type":"Motor circuit breaker","Suitability for isolation":"Yes IEC 60947-1","Power dissipation per pole":"8 W","[Ui] rated insulation voltage":"690 V AC 50/60 Hz IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz IEC 60947-2","Ambient Air Temperature for Storage":"-40...176 °F (-40...80 °C)","Ambient air temperature for operation":"-4...140 °F (-20...60 °C)","[Uimp] rated impulse withstand voltage":"6 kV IEC 60947-2","[Ith] conventional free air thermal current":"50 A IEC 60947-2","[Ics] rated service short-circuit breaking capacity":"100 % 230/240 V AC 50/60 Hz 100 % 400/415 V AC 50/60 Hz 100 % 440 V AC 50/60 Hz 50 % 500 V AC 50/60 Hz 50 % 690 V AC 50/60 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$411.00","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/05bb2e9516a159b1fafdf45bdf78de62.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/GV3L50/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation does this brand provide for GV3L50?","answer":"The GV3L50 carries certifications to EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and IEC/EN 60335-1 Clause 30.2 and 60335-2-40 Annex JJ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV3L50","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV3L50 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}