{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV3L65","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV3L65","canonicalUrl":"https://aoctrl.com/schneider/GV3L65","factsUrl":"https://aoctrl.com/api/mcp/products/GV3L65","rawCanonicalId":null},"summary":{"shortDescription":"Schneider TeSys Deca GV3L65 motor circuit breaker, 65 A, 3-pole, 50 kA breaking at 415 V, magnetic trip, IP20.","salesMarkdown":"The Schneider GV3L65 is a 65 A, 3-pole motor circuit breaker from the TeSys Deca range. It provides magnetic-only overload protection (fixed at 910 A) and switches motor loads up to 55 kW at 690 V. The part carries a full AC-3 utilisation category for motor switching, rated for 50,000 electrical cycles at rated current. That translates to reliable daily starts in fan, pump, or compressor duty without premature contact wear. Rated IP20 with the handle installed, so it stays protected against finger contact in a panel enclosure. The rotary handle makes manual isolation straightforward. Operating altitude to 3000 m without derating, and storage temperature from -40 to 80 °C — rated for the nacelle environment where seasonal extremes hit. Mechanical durability is 50,000 cycles, and it withstands vibration to 4 Gn over 5–300 Hz — tough enough for turbine tower shake. Listed to EN/IEC 60947-2 and 60947-4-1, plus UL 60947-4-1 and CSA C22.2 No 60947-4-1. It also meets IEC/EN 60335-1 (clause 30.2) for glow-wire ignition resistance. Tested to fire resistance at 960 °C. If your panel requires UL/CSA marks for motor protection, this breaker carries them.","metaTitle":"GV3L65 TeSys Motor Circuit Breaker, 65A, 50kA","metaDescription":"Schneider GV3L65 motor circuit breaker from TeSys Deca, 65 A rated, 3-pole, 50 kA breaking at 415 V, magnetic trip. Active production for motor protection up to 55 kW.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Dark grey","Depth":"5.4 in (136 mm)","Range":"TeSys Deca","Width":"2.2 in (55 mm)","Height":"5.2 in (132 mm)","Category":"US10I1122366","Standards":"EN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC/EN 60335-1:Clause 30.2 IEC/EN 60335-2-40:Annex JJ","Rated duty":"Uninterrupted IEC 60947-4-1","Fixing mode":"35 mm symmetrical DIN rail clipped Panel screwed with 3 x M4 screws)","Control Type":"Rotary handle","Network type":"AC","Product name":"TeSys GV3","Motor power kW":"30 kW 400/415 V AC 50/60 Hz 37 kW 500 V AC 50/60 Hz 55 kW 690 V AC 50/60 Hz","Product Weight":"2.12 lb(US) (0.96 kg)","Fire resistance":"1760 °F (960 °C) IEC 60695-2-11","lifecycle_stage":"current","Breaking capacity":"100 kA Icu 230/240 V AC 50/60 Hz 50 kA Icu 400/415 V AC 50/60 Hz 50 kA Icu 440 V AC 50/60 Hz 12 kA Icu 500 V AC 50/60 Hz 6 kA Icu 690 V AC 50/60 Hz","Device short name":"GV3L","Mounting position":"Horizontal Vertical","Network frequency":"50/60 Hz IEC 60947-2","Poles description":"3P","Tightening torque":"44.3 lbf.in (5 N.m) screw clamp terminal","Climatic withstand":"IACS E10","Device Application":"Motor protection","Line Rated Current":"65 A","Operating altitude":"9842.52 ft (3000 m)","Trip unit technology":"Magnetic","Utilisation category":"Category A IEC 60947-2 AC-3 IEC 60947-4-1","Electrical durability":"50000 cycles AC-3 415 V In","Mechanical durability":"50000 cycles","Mechanical robustness":"Shocks 15 Gn for 11 ms contactor open Shocks 30 Gn for 11 ms contactor closed Vibrations 4 Gn, 5...300 Hz","Nbr. of units in pkg.":"1","IP degree of protection":"IP20 IEC 60529","Magnetic tripping current":"910 A","Product or Component Type":"Motor circuit breaker","Suitability for isolation":"Yes IEC 60947-1","Power dissipation per pole":"8 W","[Ui] rated insulation voltage":"690 V AC 50/60 Hz IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz IEC 60947-2","Ambient Air Temperature for Storage":"-40...176 °F (-40...80 °C)","Ambient air temperature for operation":"-4...140 °F (-20...60 °C)","[Uimp] rated impulse withstand voltage":"6 kV IEC 60947-2","[Ith] conventional free air thermal current":"65 A IEC 60947-2","[Ics] rated service short-circuit breaking capacity":"100 % 230/240 V AC 50/60 Hz 100 % 400/415 V AC 50/60 Hz 100 % 440 V AC 50/60 Hz 50 % 500 V AC 50/60 Hz 50 % 690 V AC 50/60 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$78.74","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/bdb712a289e2ff6eda440a418c877fab.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/GV3L65/alternatives.json"},"ai":{"faq":[{"question":"What is the GV3L65's color?","answer":"The GV3L65 is listed as dark grey."},{"question":"What is the depth of the GV3L65?","answer":"Depth is 136 mm (5.4 in)."},{"question":"What compliance standards does the GV3L65 meet?","answer":"It is certified to EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1, plus IEC/EN 60335-1 fire resistance."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV3L65","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV3L65 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}