{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV3L736","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV3L736","canonicalUrl":"https://aoctrl.com/schneider/GV3L736","factsUrl":"https://aoctrl.com/api/mcp/products/GV3L736","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca motor circuit breaker, GV3L736, 3-pole, 73 A rated current, magnetic trip 1120 A, 65 kA breaking capacity at 230 V, IP20, dark grey.","salesMarkdown":"## Motor Protection Specifications The GV3L736 is a motor circuit breaker from the TeSys Deca range. Rated 73 A, magnetic trip set at 1120 A. Breaking capacity reaches 65 kA at 230/240 V AC and 50 kA at 400/415 V AC, so it stands up to high fault currents in industrial panels without requiring upstream fuses. Connection pitch is 17.5 mm without spreaders. Lug torque at 53.1 lbf·in (6 N·m). IP20 finger protection. Ambient storage range -40 to 80 °C, and it withstands 5 Gn shocks (open) and 30 Gn (closed) — tough enough for transport and machine vibration. Compliance coverage includes EN/IEC 60947-2, 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and IEC/EN 60335 series — covering motor protection, isolation, and appliance safety requirements.","metaTitle":"Schneider GV3L736 TeSys Deca Motor Circuit Breaker, 73 A","metaDescription":"Schneider GV3L736 TeSys Deca motor circuit breaker, 73 A, magnetic trip 1120 A, breaking capacity 65 kA. Active production, UL/CSA listed. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Color":"Dark grey","Depth":"5.4 in (136 mm)","Range":"TeSys Deca","Width":"2.2 in (55 mm)","Height":"5.2 in (132 mm)","Category":"US10I1122366","Standards":"EN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC/EN 60335-1:Clause 30.2 IEC/EN 60335-2-40:Annex JJ","Rated duty":"Uninterrupted IEC 60947-4-1","Fixing mode":"35 mm symmetrical DIN rail clipped Panel screwed with 3 x M4 screws)","Control Type":"Rotary handle","Network type":"AC","Product name":"TeSys GV3","Motor power kW":"37 kW 400/415 V AC 50/60 Hz 45 kW 500 V AC 50/60 Hz 55 kW 690 V AC 50/60 Hz","Fire resistance":"1760 °F (960 °C) IEC 60695-2-11","lifecycle_stage":"current","Connection pitch":"0.7 in (17.5 mm) without spreaders","Breaking capacity":"65 kA Icu 230/240 V AC 50/60 Hz 50 kA Icu 400/415 V AC 50/60 Hz 50 kA Icu 440 V AC 50/60 Hz 12 kA Icu 500 V AC 50/60 Hz 6 kA Icu 690 V AC 50/60 Hz","Device short name":"GV3L","Mounting position":"Horizontal Vertical","Network frequency":"50/60 Hz IEC 60947-2","Poles description":"3P","Tightening torque":"53.1 lbf.in (6 N.m) lugs-ring terminals","Climatic withstand":"IACS E10","Device Application":"Motor protection","Line Rated Current":"73 A","Operating altitude":"9842.52 ft (3000 m)","Trip unit technology":"Magnetic","Utilisation category":"Category A IEC 60947-2 AC-3 IEC 60947-4-1","Electrical durability":"20000 cycles AC-3 415 V In","Mechanical durability":"50000 cycles","Mechanical robustness":"Shocks 5 Gn for 11 ms contactor open Shocks 30 Gn for 11 ms contactor closed Vibrations 4 Gn, 5...300 Hz","Nbr. of units in pkg.":"1","IP degree of protection":"IP20 IEC 60529","Magnetic tripping current":"1120 A","Product or Component Type":"Motor circuit breaker","Suitability for isolation":"Yes IEC 60947-1","Power dissipation per pole":"8 W","[Ui] rated insulation voltage":"690 V AC 50/60 Hz IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz IEC 60947-2","Ambient Air Temperature for Storage":"-40...176 °F (-40...80 °C)","Ambient air temperature for operation":"-4...140 °F (-20...60 °C)","[Uimp] rated impulse withstand voltage":"6 kV IEC 60947-2","[Ith] conventional free air thermal current":"73 A IEC 60947-2","[Ics] rated service short-circuit breaking capacity":"100 % 230/240 V AC 50/60 Hz 60 % 400/415 V AC 50/60 Hz 60 % 440 V AC 50/60 Hz 50 % 500 V AC 50/60 Hz 50 % 690 V AC 50/60 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$468.00","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/59734dfcd4e04c4067884152e4134440.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/GV3L736/alternatives.json"},"ai":{"faq":[{"question":"What compliance standards does the GV3L736 meet?","answer":"It is listed under EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and IEC/EN 60335-1 Clause 30.2 / 60335-2-40 Annex JJ — covering motor circuit protection, isolation, and fire resistance."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV3L736","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV3L736 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}