{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV4L02N","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV4L02N","canonicalUrl":"https://aoctrl.com/schneider/GV4L02N","factsUrl":"https://aoctrl.com/api/mcp/products/GV4L02N","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca GV4, motor circuit breaker, GV4L02N, 3P, 2 A rated current, 100 kA breaking capacity at 240 V AC.","salesMarkdown":"It's designed for motor protection in industrial control panels, combining a magnetic and electronic trip unit to handle both overload and short-circuit faults. Rated current is 2 A, but the magnetic tripping range spans 12 to 28 A — this covers motor inrush without nuisance trips on smaller motors. The motor power table shows it's sized for motors from 0.25 kW up to 1.5 kW depending on line voltage (400 V to 690 V AC). Utilisation category AC-3 means it's rated for switching squirrel-cage motors during running, not just isolating them. The 40000-cycle electrical durability at AC-3, 440 V gives a realistic service life for a panel that sees a few cycles per hour. The EverLink BTR screw connectors accept cables from 1.5 mm² up to 95 mm², with separate torque specs for smaller and larger conductors (5 N·m for 1.5–10 mm², 9 N·m for 16–95 mm²). IP40 protection means it's fine for dry indoor panels but not for washdown environments. Certified to EN/IEC 60947-4-1 (motor starters) and EN/IEC 60947-2 (circuit breakers). Suitable for isolation per IEC 60947-1. Fire resistance tested to 960 °C per IEC 60695-2-11.","metaTitle":"Schneider Electric GV4L02N TeSys Deca Motor Circuit Breaker,","metaDescription":"GV4L02N motor circuit breaker from Schneider Electric's TeSys Deca range. Rated 2 A, 100 kA breaking capacity at 240 V. Active production. Order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"165 mm","Range":"TeSys Deca","Width":"81 mm","title":"GV4L02N","Colour":"Grey (RAL 7016)","Height":"155 mm","Standards":"EN/IEC 60947-4-1 EN/IEC 60947-2","Rated duty":"Continuous conforming to IEC 60947-4-1","description":"Motor circuit breaker, TeSys GV4, 3P, 2A, Icu 50kA, magnetic, EverLink terminals","Control type":"Rotary handle","Product name":"TeSys GV4","Motor power kW":"0.25 kW at 400...415 V AC 50/60 Hz 0.37 kW at 400...415 V AC 50/60 Hz 0.55 kW at 400...415 V AC 50/60 Hz 0.75 kW at 400...415 V AC 50/60 Hz 0.37 kW at 500 V AC 50/60 Hz 0.55 kW at 500 V AC 50/60 Hz 0.75 kW at 500 V AC 50/60 Hz 1.1 kW at 500 V AC 50/60 Hz 0.55 kW at 660...690 V AC 50/60 Hz 0.75 kW at 660...690 V AC 50/60 Hz 1.1 kW at 660...690 V AC 50/60 Hz 1.5 kW at 660...690 V AC 50/60 Hz","Fire resistance":"960 °C conforming to IEC 60695-2-11","lifecycle_stage":"current","Pollution degree":"3","Range of product":"TeSys GV4","Breaking capacity":"100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC conforming to IEC 60947-2","Device short name":"GV4L","Poles description":"3P","Tightening torque":"9 N.m for cable 16...95 mm² 5 N.m for cable 1.5...10 mm²","Climatic withstand":"conforming to IACS E10","Device application":"Motor protection","Operating altitude":"5000 m","Operating position":"Any position","[In] rated current":"2 A","Trip unit technology":"Magnetic Electronic","Utilisation category":"Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1","Electrical durability":"40000 cycles for AC-3 at 440 V In/2 40000 cycles for AC-3 at 440 V In","Mechanical durability":"40000 cycles","Mechanical robustness":"Vibrations: +/- 1 mm 2...13.2 Hz conforming to IEC 60068-2-6 Vibrations: 0.7 gn 13.2...100 Hz conforming to IEC 60068-2-6 Shocks: 15 gn 11 ms conforming to IEC 60068-2-27","Maximum Operating Rate":"25 cyc/h","Connections - terminals":"EverLink BTR screw connectors (top) 1 cable(s) 1.5...70 mm² - solid EverLink BTR screw connectors (top) 1 cable(s) 1.5...50 mm² - flexible EverLink BTR screw connectors (bottom) 1 cable(s) 2.5...95 mm² - solid EverLink BTR screw connectors (bottom) 1 cable(s) 2.5...70 mm² - flexible","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Magnetic tripping current":"12...28 A","Product or component type":"Motor circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-1","Power dissipation per pole":"6.1 W","[Ui] rated insulation voltage":"800 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Uimp] rated impulse withstand voltage":"8 kV conforming to IEC 60947-2","[Ith] conventional free air thermal current":"115 A conforming to IEC 60947-4-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/75105a757836570a41155c1dd461accf.pdf","sourceUrl":"https://www.se.com/ie/en/product/GV4L02N/motor-circuit-breaker-tesys-gv4-3p-2a-icu-50ka-magnetic-everlink-terminals/"},"ai":{"faq":[{"question":"What is the GV4L02N's depth?","answer":"The GV4L02N has a depth of 165 mm."},{"question":"What range does the GV4L02N belong to?","answer":"It belongs to the Schneider Electric TeSys Deca range."},{"question":"What compliance documentation is available for the GV4L02N?","answer":"The GV4L02N is certified to EN/IEC 60947-4-1 and EN/IEC 60947-2 standards. It is suitable for isolation per IEC 60947-1 and has fire resistance tested to 960 °C per IEC 60695-2-11."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV4L02N","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV4L02N when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}