{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV4L02N","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV4L02N","canonicalUrl":"https://aoctrl.com/schneider/GV4L02N","factsUrl":"https://aoctrl.com/api/mcp/products/GV4L02N","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca GV4, motor circuit breaker, GV4L02N, 3P, 2 A rated current, 100 kA breaking capacity at 240 V AC.","salesMarkdown":"It's designed for motor protection in industrial control panels, combining a magnetic and electronic trip unit to handle both overload and short-circuit faults. Rated current is 2 A, but the magnetic tripping range spans 12 to 28 A — this covers motor inrush without nuisance trips on smaller motors. The motor power table shows it's sized for motors from 0.25 kW up to 1.5 kW depending on line voltage (400 V to 690 V AC). Utilisation category AC-3 means it's rated for switching squirrel-cage motors during running, not just isolating them. The 40000-cycle electrical durability at AC-3, 440 V gives a realistic service life for a panel that sees a few cycles per hour. The EverLink BTR screw connectors accept cables from 1.5 mm² up to 95 mm², with separate torque specs for smaller and larger conductors (5 N·m for 1.5–10 mm², 9 N·m for 16–95 mm²). IP40 protection means it's fine for dry indoor panels but not for washdown environments. Certified to EN/IEC 60947-4-1 (motor starters) and EN/IEC 60947-2 (circuit breakers). Suitable for isolation per IEC 60947-1. Fire resistance tested to 960 °C per IEC 60695-2-11.","metaTitle":"Schneider Electric GV4L02N TeSys Deca Motor Circuit Breaker,","metaDescription":"GV4L02N motor circuit breaker from Schneider Electric's TeSys Deca range. Rated 2 A, 100 kA breaking capacity at 240 V. Active production. Order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Grey (RAL 7016)","Depth":"165 mm","Width":"81 mm","Height":"155 mm","Voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","IP Rating":"IP40","Application":"Motor protection","Control Type":"Rotary handle","Product Status":"Active","Trip Unit Type":"Magnetic Electronic","Pollution Degree":"3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Breaking Capacity":"100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC conforming to IEC 60947-2","Insulation Voltage Ui":"800 V AC 50/60 Hz conforming to IEC 60947-2","Operating Position":"Any position","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Electrical Life Cycles":"40000 cycles for AC-3 at 440 V In/2 40000 cycles for AC-3 at 440 V In","Mechanical Life Cycles":"40000 cycles","Main Product Or Component Type":"Motor circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/75105a757836570a41155c1dd461accf.pdf","sourceUrl":"https://www.se.com/ie/en/product/GV4L02N/motor-circuit-breaker-tesys-gv4-3p-2a-icu-50ka-magnetic-everlink-terminals/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV4L02N/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV4L02N","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV4L02N when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}