{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV4L07N","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV4L07N","canonicalUrl":"https://aoctrl.com/schneider/GV4L07N","factsUrl":"https://aoctrl.com/api/mcp/products/GV4L07N","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca GV4L, motor circuit breaker, GV4L07N, 3-pole, 7 A rated current, 100 kA breaking capacity at 240 V AC, rotary handle control.","salesMarkdown":"It combines magnetic and electronic trip technology, with a magnetic tripping window of 42 to 98 A, so it handles inrush without nuisance trips but clears a hard fault fast. Rated breaking capacity hits 100 kA Icu at 240 V AC and 50 kA at 415 V AC per IEC 60947-2, which means it can interrupt a bolted fault on a 400 V line without upstream fuses having to clear — a real advantage when you're packing breakers into a compact MCC bucket. The rotary handle gives positive isolation indication — it's marked suitable for isolation per IEC 60947-1 — so a padlockable OFF position counts as a visible break for LOTO procedures. ## Where it lands in a panel At 81 mm wide, 155 mm tall, and 165 mm deep, it fits standard DIN-rail enclosures without crowding adjacent devices. The EverLink BTR screw terminals on top accept up to 70 mm² solid or 50 mm² flexible; the bottom side goes up to 95 mm² solid or 70 mm² flexible. Tightening torque is 9 N·m for the larger cables, 5 N·m for the smaller ones — no special tool needed beyond a decent torque screwdriver. IP40 front-of-panel protection and IK07 impact resistance mean it's fine for general industrial enclosure use, but not washdown zones. Pollution degree 3 per IEC 60947-2 — that's the standard for conductive pollution in industrial environments, so no special conformal coating or sealed enclosure required for most factory floors. Compliance documentation covers EN/IEC 60947-4-1 and EN/IEC 60947-2, plus fire resistance tested to 960 °C per IEC 60695-2-11 and climatic withstand per IACS. The grey RAL 7016 housing is standard across the TeSys Deca line. ## Sizing and selection notes Motor power coverage at 400-415 V AC: 1.5 kW through 3 kW depending on the exact voltage and frequency. At 690 V it covers up to 7.5 kW. Electrical durability is 40,000 cycles at AC-3 duty at 440 V, both at full load and at half-load In/2. That's enough for frequent start-stop applications like a cycling compressor or a batch conveyor. Power dissipation per pole is 6.1 W, so total heat load for the three poles is about 18.3 W at rated current — factor that into your enclosure thermal calculation if you're packing multiple breakers in a small cabinet.","metaTitle":"Schneider GV4L07N TeSys Deca Motor Circuit Breaker, 7 A","metaDescription":"Schneider Electric GV4L07N motor circuit breaker, 7 A rated current, 100 kA breaking capacity at 240 V. TeSys Deca range, 3-pole, rotary handle. Active production. RFQ for sourcing","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"165 mm","Range":"TeSys Deca","Width":"81 mm","title":"GV4L07N","Colour":"Grey (RAL 7016)","Height":"155 mm","Standards":"EN/IEC 60947-4-1 EN/IEC 60947-2","Rated duty":"Continuous conforming to IEC 60947-4-1","description":"Motor circuit breaker, TeSys GV4, 3P, 7A, Icu 50kA, magnetic, EverLink terminals","Control type":"Rotary handle","Product name":"TeSys GV4","Motor power kW":"1.5 kW at 400...415 V AC 50/60 Hz 2.2 kW at 400...415 V AC 50/60 Hz 2.5 kW at 400...415 V AC 50/60 Hz 3 kW at 400...415 V AC 50/60 Hz 2.2 kW at 500 V AC 50/60 Hz 2.5 kW at 500 V AC 50/60 Hz 3 kW at 500 V AC 50/60 Hz 4 kW at 500 V AC 50/60 Hz 3 kW at 660...690 V AC 50/60 Hz 4 kW at 660...690 V AC 50/60 Hz 5.5 kW at 660...690 V AC 50/60 Hz 7.5 kW at 660...690 V AC 50/60 Hz","Fire resistance":"960 °C conforming to IEC 60695-2-11","lifecycle_stage":"current","Pollution degree":"3","Range of product":"TeSys GV4","Breaking capacity":"100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"GV4L","Poles description":"3P","Tightening torque":"9 N.m for cable 16...95 mm² 5 N.m for cable 1.5...10 mm²","Climatic withstand":"conforming to IACS E10","Device application":"Motor protection","Operating altitude":"5000 m","Operating position":"Any position","[In] rated current":"7 A","Trip unit technology":"Magnetic Electronic","Utilisation category":"Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1","Electrical durability":"40000 cycles for AC-3 at 440 V In/2 40000 cycles for AC-3 at 440 V In","Mechanical durability":"40000 cycles","Mechanical robustness":"Vibrations: +/- 1 mm 2...13.2 Hz conforming to IEC 60068-2-6 Vibrations: 0.7 gn 13.2...100 Hz conforming to IEC 60068-2-6 Shocks: 15 gn 11 ms conforming to IEC 60068-2-27","Maximum Operating Rate":"25 cyc/h","Connections - terminals":"EverLink BTR screw connectors (top) 1 cable(s) 1.5...70 mm² - solid EverLink BTR screw connectors (top) 1 cable(s) 1.5...50 mm² - flexible EverLink BTR screw connectors (bottom) 1 cable(s) 2.5...95 mm² - solid EverLink BTR screw connectors (bottom) 1 cable(s) 2.5...70 mm² - flexible","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Magnetic tripping current":"42...98 A","Product or component type":"Motor circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-1","Power dissipation per pole":"6.1 W","[Ui] rated insulation voltage":"800 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Uimp] rated impulse withstand voltage":"8 kV conforming to IEC 60947-2","[Ith] conventional free air thermal current":"115 A conforming to IEC 60947-4-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1f6b494c04a250386166546f365e286f.pdf","sourceUrl":"https://www.se.com/nz/en/product/GV4L07N/motor-circuit-breaker-tesys-gv4-3p-7a-icu-50ka-magnetic-everlink-terminals/"},"ai":{"faq":[{"question":"What are the key ratings I need to check for fit?","answer":"Rated current is 7 A continuous. Magnetic tripping threshold is 42 to 98 A. Breaking capacity is 100 kA at 240 V AC, 50 kA at 415 V AC. Motor power at 400 V is 1.5 to 3 kW depending on the exact supply voltage."},{"question":"What compliance documentation is available for this part?","answer":"The part is certified to EN/IEC 60947-4-1 and EN/IEC 60947-2. Fire resistance tested to 960 °C per IEC 60695-2-11. Climatic withstand per IACS. Pollution degree 3."},{"question":"What is the closest alternative in the same family?","answer":"No official pin-compatible direct substitute is published by Schneider. The GV4L07N is the specific 7 A variant in the TeSys Deca GV4L series. For a different current rating, you would select a different GV4L order code — the family shares the same form factor and terminal layout."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV4L07N","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV4L07N when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}