{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV4L07N","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV4L07N","canonicalUrl":"https://aoctrl.com/schneider/GV4L07N","factsUrl":"https://aoctrl.com/api/mcp/products/GV4L07N","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca GV4L, motor circuit breaker, GV4L07N, 3-pole, 7 A rated current, 100 kA breaking capacity at 240 V AC, rotary handle control.","salesMarkdown":"It combines magnetic and electronic trip technology, with a magnetic tripping window of 42 to 98 A, so it handles inrush without nuisance trips but clears a hard fault fast. Rated breaking capacity hits 100 kA Icu at 240 V AC and 50 kA at 415 V AC per IEC 60947-2, which means it can interrupt a bolted fault on a 400 V line without upstream fuses having to clear — a real advantage when you're packing breakers into a compact MCC bucket. The rotary handle gives positive isolation indication — it's marked suitable for isolation per IEC 60947-1 — so a padlockable OFF position counts as a visible break for LOTO procedures. ## Where it lands in a panel At 81 mm wide, 155 mm tall, and 165 mm deep, it fits standard DIN-rail enclosures without crowding adjacent devices. The EverLink BTR screw terminals on top accept up to 70 mm² solid or 50 mm² flexible; the bottom side goes up to 95 mm² solid or 70 mm² flexible. Tightening torque is 9 N·m for the larger cables, 5 N·m for the smaller ones — no special tool needed beyond a decent torque screwdriver. IP40 front-of-panel protection and IK07 impact resistance mean it's fine for general industrial enclosure use, but not washdown zones. Pollution degree 3 per IEC 60947-2 — that's the standard for conductive pollution in industrial environments, so no special conformal coating or sealed enclosure required for most factory floors. Compliance documentation covers EN/IEC 60947-4-1 and EN/IEC 60947-2, plus fire resistance tested to 960 °C per IEC 60695-2-11 and climatic withstand per IACS. The grey RAL 7016 housing is standard across the TeSys Deca line. ## Sizing and selection notes Motor power coverage at 400-415 V AC: 1.5 kW through 3 kW depending on the exact voltage and frequency. At 690 V it covers up to 7.5 kW. Electrical durability is 40,000 cycles at AC-3 duty at 440 V, both at full load and at half-load In/2. That's enough for frequent start-stop applications like a cycling compressor or a batch conveyor. Power dissipation per pole is 6.1 W, so total heat load for the three poles is about 18.3 W at rated current — factor that into your enclosure thermal calculation if you're packing multiple breakers in a small cabinet.","metaTitle":"Schneider GV4L07N TeSys Deca Motor Circuit Breaker, 7 A","metaDescription":"Schneider Electric GV4L07N motor circuit breaker, 7 A rated current, 100 kA breaking capacity at 240 V. TeSys Deca range, 3-pole, rotary handle. Active production. RFQ for sourcing","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Grey (RAL 7016)","Depth":"165 mm","Width":"81 mm","Height":"155 mm","Voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","IP Rating":"IP40","Application":"Motor protection","Control Type":"Rotary handle","Product Status":"Active","Trip Unit Type":"Magnetic Electronic","Pollution Degree":"3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Breaking Capacity":"100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"800 V AC 50/60 Hz conforming to IEC 60947-2","Operating Position":"Any position","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Electrical Life Cycles":"40000 cycles for AC-3 at 440 V In/2 40000 cycles for AC-3 at 440 V In","Mechanical Life Cycles":"40000 cycles","Main Product Or Component Type":"Motor circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1f6b494c04a250386166546f365e286f.pdf","sourceUrl":"https://www.se.com/nz/en/product/GV4L07N/motor-circuit-breaker-tesys-gv4-3p-7a-icu-50ka-magnetic-everlink-terminals/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV4L07N/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV4L07N","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV4L07N when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}