{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV4L07N6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV4L07N6","canonicalUrl":"https://aoctrl.com/schneider/GV4L07N6","factsUrl":"https://aoctrl.com/api/mcp/products/GV4L07N6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys GV4 motor circuit breaker, GV4L07N6, 3-pole, 7 A rated current, 100 kA breaking capacity at 240 V AC, magnetic-electronic trip.","salesMarkdown":"## Motor power coverage and trip characteristics The GV4L07N6: This 7 A frame covers a wide motor power band depending on line voltage: 1.5 kW at 400 V, up to 4 kW at 500 V, and as high as 7.5 kW at 690 V. The magnetic trip threshold is adjustable between 42 and 98 A — that is the short-circuit / instantaneous trip, not the overload. The electronic overload element handles the thermal curve. The utilisation category is AC-3 (squirrel-cage motor starting) per IEC 60947-4-1, which is the standard for direct-on-line motor starting. ## Durability and environmental ratings for continuous duty Rated for continuous duty per IEC 60947-4-1. Electrical durability is 40,000 cycles at AC-3 at 440 V, both at In and at In/2 — that is the number of motor starts before the contacts need replacement. Mechanical durability matches at 40,000 cycles. The maximum operating rate is 25 cycles per hour, so it is sized for a machine that starts a motor every couple of minutes, not a high-speed jogging application. The enclosure is IP40 (finger-safe, no water ingress protection) and IK07 (impact resistance up to 2 J). ## Integration into the panel: dimensions, connections, and isolation Dimensions are 155 mm high, 81 mm wide, and 165 mm deep. The connection pitch is 27 mm without spreaders, 35 mm with spreaders — this matters when laying out multiple breakers on a DIN rail for busbar connection. Terminals accept lugs or ring terminals; tightening torque is 9 N·m for the main power cables (16–95 mm²) and 5 N·m for control wiring (1.5–10 mm²). Operating position is any, and the altitude rating goes to 5000 m, so it works in high-altitude installations without derating.","metaTitle":"Schneider Electric GV4L07N6 TeSys GV4 Motor Circuit Breaker,","metaDescription":"Schneider Electric GV4L07N6 TeSys GV4 motor circuit breaker, 7 A rated current, 100 kA breaking capacity at 240 V. Active production. Sourced to order. IEC 60947-4-1/2.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"165 mm","Range":"TeSys Deca","Width":"81 mm","title":"GV4L07N6","Colour":"Grey (RAL 7016)","Height":"155 mm","Standards":"EN/IEC 60947-4-1 EN/IEC 60947-2","Rated duty":"Continuous conforming to IEC 60947-4-1","description":"Motor circuit breaker, TeSys GV4, 3P, 7A, Icu 50kA, magnetic, lugs terminals","Control type":"Rotary handle","Product name":"TeSys GV4","Motor power kW":"1.5 kW at 400...415 V AC 50/60 Hz 2.2 kW at 400...415 V AC 50/60 Hz 2.5 kW at 400...415 V AC 50/60 Hz 3 kW at 400...415 V AC 50/60 Hz 2.2 kW at 500 V AC 50/60 Hz 2.5 kW at 500 V AC 50/60 Hz 3 kW at 500 V AC 50/60 Hz 4 kW at 500 V AC 50/60 Hz 3 kW at 660...690 V AC 50/60 Hz 4 kW at 660...690 V AC 50/60 Hz 5.5 kW at 660...690 V AC 50/60 Hz 7.5 kW at 660...690 V AC 50/60 Hz","Fire resistance":"960 °C conforming to IEC 60695-2-11","lifecycle_stage":"current","Connection pitch":"27 mm without spreaders 35 mm with spreaders","Pollution degree":"3","Range of product":"TeSys GV4","Breaking capacity":"100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"GV4L","Poles description":"3P","Tightening torque":"9 N.m for cable 16...95 mm² 5 N.m for cable 1.5...10 mm²","Climatic withstand":"conforming to IACS E10","Device application":"Motor protection","Operating altitude":"5000 m","Operating position":"Any position","[In] rated current":"7 A","Trip unit technology":"Magnetic Electronic","Utilisation category":"Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1","Electrical durability":"40000 cycles for AC-3 at 440 V In/2 40000 cycles for AC-3 at 440 V In","Mechanical durability":"40000 cycles","Mechanical robustness":"Vibrations: +/- 1 mm 2...13.2 Hz conforming to IEC 60068-2-6 Vibrations: 0.7 gn 13.2...100 Hz conforming to IEC 60068-2-6 Shocks: 15 gn 11 ms conforming to IEC 60068-2-27","Maximum Operating Rate":"25 cyc/h","Connections - terminals":"Lugs-ring terminals","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Magnetic tripping current":"42...98 A","Product or component type":"Motor circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-1","Power dissipation per pole":"6.1 W","[Ui] rated insulation voltage":"800 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Uimp] rated impulse withstand voltage":"8 kV conforming to IEC 60947-2","[Ith] conventional free air thermal current":"115 A conforming to IEC 60947-4-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8308e34ff9d458eba7298a8856e4d2d4.pdf","sourceUrl":"https://www.se.com/ie/en/product/GV4L07N6/motor-circuit-breaker-tesys-gv4-3p-7a-icu-50ka-magnetic-lugs-terminals/"},"ai":{"faq":[{"question":"What is the breaking capacity of the GV4L07N6?","answer":"The breaking capacity (Icu) is 100 kA at 220–240 V AC, 50 kA at 380–415 V AC, 50 kA at 440 V AC, 25 kA at 500 V AC, 15 kA at 525 V AC, and 8 kA at 660–690 V AC, all per IEC 60947-2."},{"question":"What motor power can the GV4L07N6 protect?","answer":"At 400–415 V AC, it covers 1.5 kW to 3 kW. At 500 V AC, it covers 2.2 kW to 4 kW. At 660–690 V AC, it covers 3 kW to 7.5 kW."},{"question":"What standards does the GV4L07N6 comply with?","answer":"It complies with EN/IEC 60947-4-1 (motor protection) and EN/IEC 60947-2 (circuit breakers). It is also suitable for isolation per IEC 60947-1."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV4L07N6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV4L07N6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}