{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV4L115B6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV4L115B6","canonicalUrl":"https://aoctrl.com/schneider/GV4L115B6","factsUrl":"https://aoctrl.com/api/mcp/products/GV4L115B6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca GV4L115B6, motor circuit breaker, 115 A rated current, 37–110 kW motor power, 50 kA breaking capacity at 240 V AC.","salesMarkdown":"## What the 115 A rating means for fit The GV4L115B6 is a 3-pole motor circuit breaker rated at 115 A continuous current, sized for motor loads between 37 kW and 110 kW depending on supply voltage. The 115 A frame is the selection anchor — it determines the upstream contactor and cable sizing, not just the motor full-load amps. Breaking capacity is 50 kA Icu at 240 V AC, 25 kA at 415 V, 20 kA at 440 V, and 10 kA at 500 V. ## Motor protection and trip characteristics Uses magnetic-electronic trip technology with a magnetic tripping range of 690...1610 A. That's the instantaneous short-circuit pickup — adjustable within that band to coordinate with downstream contactors and avoid nuisance trips on motor inrush. Rated for continuous duty per IEC 60947-4-1, so it handles sustained motor loads without derating. Fire resistance rated at 960 °C per IEC 60695-2-11. ## Panel and mounting notes Dimensions: 155 mm high, 81 mm wide, 165 mm deep. Connection pitch is 27 mm without spreaders, 35 mm with spreaders. Terminals accept lugs or ring terminals — tightening torque 9 N·m for 16...95 mm² cable, 5 N·m for 1.5...10 mm². IP40 enclosure protection, IK07 impact resistance. Operating altitude up to 5000 m.","metaTitle":"Schneider Electric GV4L115B6 TeSys Deca Motor Circuit Breake","metaDescription":"Schneider Electric GV4L115B6 motor circuit breaker, 115 A rated current, 37–110 kW motor power, 50 kA breaking capacity. Active production. Order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Grey (RAL 7016)","Depth":"165 mm","Width":"81 mm","Height":"155 mm","Voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","IP Rating":"IP40","Application":"Motor protection","Control Type":"Rotary handle","Product Status":"Active","Terminal Pitch":"27 mm without spreaders 35 mm with spreaders","Trip Unit Type":"Magnetic Electronic","Pollution Degree":"3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Insulation Voltage Ui":"800 V AC 50/60 Hz conforming to IEC 60947-2","Operating Position":"Any position","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Electrical Life Cycles":"10000 cycles for AC-3 at 440 V In/2 5000 cycles for AC-3 at 440 V In","Mechanical Life Cycles":"40000 cycles","Main Product Or Component Type":"Motor circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/th/en/product/GV4L115B6/motor-circuit-breaker-tesys-gv4-3p-115a-icu-25ka-magnetic-lugs-terminals/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV4L115B6/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV4L115B6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV4L115B6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}