{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV4L115S","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV4L115S","canonicalUrl":"https://aoctrl.com/schneider/GV4L115S","factsUrl":"https://aoctrl.com/api/mcp/products/GV4L115S","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca GV4L115S, 3-pole motor circuit breaker, 115 A rated current, AC-3 duty, up to 120 kA breaking capacity, IP40, grey (RAL 7016).","salesMarkdown":"## What the 115 A rating means for your motor branch The GV4L115S is a 3-pole motor circuit breaker from the TeSys Deca range, rated 115 A continuous and built for motor protection under IEC 60947-4-1 and IEC 60947-2. That 115 A is the thermal-magnetic continuous current — it carries the full motor load without nuisance tripping, while the magnetic trip unit operates between 690 and 1610 A to handle short-circuit events. For a 400 V supply, this breaker covers motor power from 37 kW up to 55 kW depending on the exact voltage and configuration; at 690 V it can handle up to 110 kW. The breaking capacity is substantial: 120 kA Icu at 240 V, 100 kA at 415 V, and still 10 kA at 690 V. The breaker measures 81 mm wide, 155 mm high, 165 mm deep — a standard panel footprint for this class. It accepts EverLink BTR screw terminals: top side takes 1.5–70 mm² solid or 1.5–50 mm² flexible; bottom side takes 2.5–95 mm² solid or 2.5–70 mm² flexible. Tightening torque is 9 N·m for the larger cable range, 5 N·m for the smaller. IP40 enclosure protection means it's suited for clean indoor panels — not washdown environments. ## What the standards tell you Compliance with IEC 60947-4-1 (motor starters) and IEC 60947-2 (circuit breakers) means this single device combines motor protection and short-circuit protection in one package — no separate contactor needed for the protection function, though a contactor is still required for normal switching duty. Electrical durability is 10,000 cycles at AC-3 at 440 V at half rated current, and 5,000 cycles at full rated current — enough for most fixed-speed motor applications.","metaTitle":"Schneider Electric GV4L115S TeSys GV4 Motor Circuit Breaker,","metaDescription":"Schneider Electric GV4L115S TeSys GV4 motor circuit breaker, 115 A rated current, 3-pole, up to 120 kA breaking capacity, AC-3 duty, active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"165 mm","Range":"TeSys Deca","Width":"81 mm","Colour":"Grey (RAL 7016)","Height":"155 mm","Standards":"EN/IEC 60947-4-1 EN/IEC 60947-2","Rated duty":"Continuous conforming to IEC 60947-4-1","Control type":"Rotary handle","Product name":"TeSys GV4","Motor power kW":"37 kW at 400...415 V AC 50/60 Hz 45 kW at 400...415 V AC 50/60 Hz 55 kW at 400...415 V AC 50/60 Hz 45 kW at 500 V AC 50/60 Hz 55 kW at 500 V AC 50/60 Hz 75 kW at 500 V AC 50/60 Hz 75 kW at 660...690 V AC 50/60 Hz 90 kW at 660...690 V AC 50/60 Hz 110 kW at 660...690 V AC 50/60 Hz","Fire resistance":"960 °C conforming to IEC 60695-2-11","lifecycle_stage":"current","Pollution degree":"3","Range of product":"TeSys GV4","Breaking capacity":"120 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 18 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"GV4L","Poles description":"3P","Tightening torque":"9 N.m for cable 16...95 mm² 5 N.m for cable 1.5...10 mm²","Climatic withstand":"conforming to IACS E10","Device application":"Motor protection","Operating altitude":"5000 m","Operating position":"Any position","[In] rated current":"115 A","Trip unit technology":"Magnetic Electronic","Utilisation category":"Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1","Electrical durability":"10000 cycles for AC-3 at 440 V In/2 5000 cycles for AC-3 at 440 V In","Mechanical durability":"40000 cycles","Mechanical robustness":"Vibrations: +/- 1 mm 2...13.2 Hz conforming to IEC 60068-2-6 Vibrations: 0.7 gn 13.2...100 Hz conforming to IEC 60068-2-6 Shocks: 15 gn 11 ms conforming to IEC 60068-2-27","Maximum Operating Rate":"25 cyc/h","Connections - terminals":"EverLink BTR screw connectors (top) 1 cable(s) 1.5...70 mm² - solid EverLink BTR screw connectors (top) 1 cable(s) 1.5...50 mm² - flexible EverLink BTR screw connectors (bottom) 1 cable(s) 2.5...95 mm² - solid EverLink BTR screw connectors (bottom) 1 cable(s) 2.5...70 mm² - flexible","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Magnetic tripping current":"690...1610 A","Product or component type":"Motor circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-1","Power dissipation per pole":"6.1 W","[Ui] rated insulation voltage":"800 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Uimp] rated impulse withstand voltage":"8 kV conforming to IEC 60947-2","[Ith] conventional free air thermal current":"115 A conforming to IEC 60947-4-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/th/en/product/GV4L115S/motor-circuit-breaker-tesys-gv4-3p-115a-icu-100ka-magnetic-everlink-terminals/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV4L115S/alternatives.json"},"ai":{"faq":[{"question":"What motor power does the GV4L115S cover at 400 V?","answer":"At 400–415 V AC, it covers 37 kW, 45 kW, and 55 kW depending on the exact rating selected. At 500 V it covers 45–75 kW; at 690 V it covers 75–110 kW."},{"question":"What is the magnetic trip range on this breaker?","answer":"The magnetic trip unit operates between 690 A and 1610 A — that's 6 to 14 times the 115 A rated current, which is typical for motor-starting inrush without nuisance tripping."},{"question":"What approvals and standards does the GV4L115S carry?","answer":"It complies with EN/IEC 60947-4-1 (motor starters) and EN/IEC 60947-2 (circuit breakers), and is suitable for isolation per IEC 60947-1. Climatic withstand conforms to IACS."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV4L115S","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV4L115S when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}