{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV4L25B","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV4L25B","canonicalUrl":"https://aoctrl.com/schneider/GV4L25B","factsUrl":"https://aoctrl.com/api/mcp/products/GV4L25B","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca GV4L25B, motor circuit breaker, 3P, 25 A rated current, 50 kA Icu at 240 V AC, EverLink BTR screw terminals, IP40.","salesMarkdown":"## What the 25 A rating means for your motor branch circuit That 25 A figure is the thermal continuous rating — the breaker will carry that current indefinitely in a 40 °C ambient without nuisance tripping, which is the baseline for sizing it to a motor's full-load amps. The magnetic trip is set at 150...350 A, so it handles motor inrush (typically 6–8× FLA) without dropping out, but clears a bolted fault fast. The utilisation category is AC-3 per IEC 60947-4-1, meaning it is tested for switching squirrel-cage motors — starting, stopping, and plugging. Category A per IEC 60947-2 covers general distribution faults. The combination means this single device serves both motor control and branch-circuit protection in one enclosure, which is the point of a motor circuit breaker over a separate contactor plus MCCB. The GV4L25B delivers 50 kA Icu at 220...240 V AC, 25 kA at 380...415 V, 20 kA at 440 V, and 10 kA at 500 V. These are the ultimate short-circuit breaking capacities — the breaker can clear one fault at these levels and still be serviceable afterward. The standards are EN/IEC 60947-2 (circuit-breaker performance) and EN/IEC 60947-4-1 (contactor/motor-starter coordination). That dual certification is what lets a single device serve both as a disconnecting means and as motor overload protection — it is listed for both roles, not just one. ## Motor power coverage across common voltages The GV4L25B covers a range of motor power ratings depending on supply voltage: 5.5 kW at 400...415 V, 7.5 kW at 500 V, and up to 18.5 kW at 660...690 V. That spread reflects the fact that at higher voltages the same 25 A carries more power. For a 400 V line, the 5.5 kW rating is the one to use for BOM matching; for a 690 V mining or marine installation, it reaches 18.5 kW. ## Termination and environmental fit Terminals are EverLink BTR screw type — top accepts 1.5...70 mm² solid or 1.5...50 mm² flexible; bottom accepts 2.5...95 mm² solid or 2.5...70 mm² flexible. Tightening torque is 9 N·m for the larger cables (16...95 mm²) and 5 N·m for smaller ones (1.5...10 mm²). The EverLink design uses a clamping plate that maintains contact pressure over temperature cycles, which reduces the need for retorquing during commissioning. Operating altitude up to 5000 m without derating — useful for high-altitude installations where air density affects arc extinction. Mechanical durability is rated at 40,000 cycles, electrical durability at 40,000 cycles for AC-3 at 440 V at half rated current (In/2), and 20,000 cycles at full rated current (In). That is typical for a motor circuit breaker in this class — the electrical endurance at full load is half the mechanical figure, which is the number to use when calculating maintenance intervals on a frequently cycled load like a conveyor or a compressor.","metaTitle":"Schneider GV4L25B TeSys Deca Motor Circuit Breaker, 25 A","metaDescription":"Schneider Electric GV4L25B TeSys Deca motor circuit breaker, 25 A rated current, 3-pole, 50 kA breaking capacity at 240 V. EN/IEC 60947-2 and 60947-4-1. Current lifecycle stage. So","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Color":"Grey (RAL 7016)","Depth":"165 mm","Width":"81 mm","Height":"155 mm","Voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","IP Rating":"IP40","Application":"Motor protection","Control Type":"Rotary handle","Product Status":"Active","Trip Unit Type":"Magnetic Electronic","Pollution Degree":"3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Breaking Capacity":"50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"800 V AC 50/60 Hz conforming to IEC 60947-2","Operating Position":"Any position","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Electrical Life Cycles":"40000 cycles for AC-3 at 440 V In/2 20000 cycles for AC-3 at 440 V In","Mechanical Life Cycles":"40000 cycles","Main Product Or Component Type":"Motor circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/767018526c5273872d22666518fe779b.pdf","sourceUrl":"https://www.se.com/za/en/product/GV4L25B/motor-circuit-breaker-tesys-gv4-3p-25a-icu-25ka-magnetic-everlink-terminals/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV4L25B/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV4L25B","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV4L25B when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}