{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV4L25N6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV4L25N6","canonicalUrl":"https://aoctrl.com/schneider/GV4L25N6","factsUrl":"https://aoctrl.com/api/mcp/products/GV4L25N6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys GV4 motor circuit breaker, GV4L25N6, 3-pole, 25 A rated current, magnetic-electronic trip, 100 kA breaking capacity at 240 V AC.","salesMarkdown":"The GV4L25N6 is a 3-pole motor circuit breaker from the TeSys GV4 range, rated at 25 A continuous current (In) and designed for motor protection under AC-3 utilisation category per IEC 60947-4-1. The 25 A rating means it directly protects a motor drawing up to that full-load current — for a 400 V supply that translates to roughly 5.5 kW, while at 690 V it covers up to 7.5 kW. The magnetic-electronic trip unit provides adjustable magnetic tripping between 150 and 350 A, so you set the instantaneous pickup to ride through motor inrush without nuisance trips. The part is rated for isolation (IEC 60947-1), so it doubles as a disconnect under load. Connection pitch is 27 mm without spreaders and 35 mm with them, which matters when laying out busbars or cable ducts in a crowded enclosure. Terminals accept lugs or ring terminals for cable sizes from 1.5 to 95 mm², with tightening torques of 5 N·m for smaller cables and 9 N·m for the larger ones. The IP40 front face and IK07 impact rating mean it is suited for general industrial panel environments where occasional tool drops or dust ingress are concerns. Pollution degree 3 confirms it for conductive environments typical of factory floors. Climatic withstand conforms to IACS for marine environments. Fire resistance is tested to 960 °C per IEC 60695-2-11. Storage temperature range is -50 to 85 °C.","metaTitle":"Schneider Electric GV4L25N6 TeSys GV4 Motor Circuit Breaker,","metaDescription":"Schneider Electric GV4L25N6 motor circuit breaker, 25 A rated current, 100 kA breaking capacity at 240 V. Active lifecycle. Sourced to order. RFQ for pricing and lead time.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"165 mm","Range":"TeSys Deca","Width":"81 mm","title":"GV4L25N6","Colour":"Grey (RAL 7016)","Height":"155 mm","Standards":"EN/IEC 60947-4-1 EN/IEC 60947-2","Rated duty":"Continuous conforming to IEC 60947-4-1","description":"Motor circuit breaker, TeSys GV4, TeSys GV4, 3P, 25A, Icu 50kA, magnetic, lugs terminals","Control type":"Rotary handle","Product name":"TeSys GV4","Motor power kW":"7.5 kW at 660...690 V AC 50/60 Hz 5.5 kW at 400...415 V AC 50/60 Hz 7.5 kW at 500 V AC 50/60 Hz 9 kW at 660...690 V AC 50/60 Hz 11 kW at 660...690 V AC 50/60 Hz 7.5 kW at 400...415 V AC 50/60 Hz 9 kW at 400...415 V AC 50/60 Hz 11 kW at 400...415 V AC 50/60 Hz 9 kW at 500 V AC 50/60 Hz 11 kW at 500 V AC 50/60 Hz 15 kW at 500 V AC 50/60 Hz 15 kW at 660...690 V AC 50/60 Hz 18.5 kW at 660...690 V AC 50/60 Hz","Fire resistance":"960 °C conforming to IEC 60695-2-11","lifecycle_stage":"current","Connection pitch":"27 mm without spreaders 35 mm with spreaders","Pollution degree":"3","Range of product":"TeSys GV4","Breaking capacity":"100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"GV4L","Poles description":"3P","Tightening torque":"9 N.m for cable 16...95 mm² 5 N.m for cable 1.5...10 mm²","Climatic withstand":"conforming to IACS E10","Device application":"Motor protection","Operating altitude":"5000 m","Operating position":"Any position","[In] rated current":"25 A","Trip unit technology":"Magnetic Electronic","Utilisation category":"Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1","Electrical durability":"40000 cycles for AC-3 at 440 V In/2 20000 cycles for AC-3 at 440 V In","Mechanical durability":"40000 cycles","Mechanical robustness":"Vibrations: +/- 1 mm 2...13.2 Hz conforming to IEC 60068-2-6 Vibrations: 0.7 gn 13.2...100 Hz conforming to IEC 60068-2-6 Shocks: 15 gn 11 ms conforming to IEC 60068-2-27","Maximum Operating Rate":"25 cyc/h","Connections - terminals":"Lugs-ring terminals","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Magnetic tripping current":"150...350 A","Product or component type":"Motor circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-1","Power dissipation per pole":"6.1 W","[Ui] rated insulation voltage":"800 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Uimp] rated impulse withstand voltage":"8 kV conforming to IEC 60947-2","[Ith] conventional free air thermal current":"115 A conforming to IEC 60947-4-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/197f7e748eeff78383a052baf7d9c8fd.pdf","sourceUrl":"https://www.se.com/au/en/product/GV4L25N6/motor-circuit-breaker-tesys-gv4-tesys-gv4-3p-25a-icu-50ka-magnetic-lugs-terminals/"},"ai":{"faq":[{"question":"What is the closest alternative to GV4L25N6 in the TeSys GV4 family?","answer":"Within the TeSys GV4 range, the closest peer is the GV4L20N6 (20 A) and GV4L32N6 (32 A). The GV4L25N6 sits at 25 A, so the choice depends on the motor full-load current. The frame size, breaking capacity, and trip technology are identical across the GV4L series; only the thermal-magnetic trip setting differs."},{"question":"What is the depth of the GV4L25N6?","answer":"The GV4L25N6 has a depth of 165 mm."},{"question":"What product range does the GV4L25N6 belong to?","answer":"The GV4L25N6 is part of the TeSys Deca range, specifically the TeSys GV4 series of motor circuit breakers."},{"question":"What compliance documentation is available for the GV4L25N6?","answer":"The GV4L25N6 is certified to EN/IEC 60947-4-1 and EN/IEC 60947-2. It is suitable for isolation per IEC 60947-1 and has climatic withstand conforming to IACS. Fire resistance is tested to 960 °C per IEC 60695-2-11. Standard Schneider Electric documentation includes a declaration of conformity covering CE, UKCA, and EAC marks. RoHS and REACH compliance is standard for the TeSys GV4 family."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV4L25N6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV4L25N6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}