{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV4LE02N","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV4LE02N","canonicalUrl":"https://aoctrl.com/schneider/GV4LE02N","factsUrl":"https://aoctrl.com/api/mcp/products/GV4LE02N","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca GV4L motor circuit breaker, GV4LE02N, 3-pole, 2 A rated current, magnetic-electronic trip, IP40, 100 kA breaking capacity.","salesMarkdown":"The magnetic trip range spans 12…28 A, so short-circuit or locked-rotor events above that threshold cause instantaneous opening, protecting the motor and downstream cable. Breaking capacity reaches 100 kA Icu at 220…240 V AC and 50 kA at 380…415 V AC per IEC 60947-2. Rated for AC-3 duty per IEC 60947-4-1, so it handles the inrush of a squirrel-cage motor during starting and the switching of the running load. IP40 protection means it is suited for indoor panel environments where tools or fingers are the main intrusion risk — no washdown tolerance. Operating temperature range is -25…70 °C, storage -50…85 °C. EverLink BTR screw terminals on top accept 1.5…70 mm² solid or 1.5…50 mm² flexible; bottom terminals accept 2.5…95 mm² solid or 2.5…70 mm² flexible. Tightening torque is 9 N·m for the larger cable range (16…95 mm²) and 5 N·m for 1.5…10 mm². The terminals are rated for 960 °C glow-wire test per IEC 60695-2-11.","metaTitle":"Schneider Electric GV4LE02N TeSys Deca Motor Circuit Breaker","metaDescription":"Schneider Electric GV4LE02N TeSys Deca motor circuit breaker, 2 A rated current, 3 poles, magnetic-electronic trip, 100 kA breaking capacity at 240 V. Current lifecycle stage. Sour","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Grey (RAL 7016)","Depth":"116 mm","Width":"81 mm","Height":"155 mm","Voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","IP Rating":"IP40","Application":"Motor protection","Control Type":"Toggle","Product Status":"Active","Trip Unit Type":"Magnetic Electronic","Pollution Degree":"3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Insulation Voltage Ui":"800 V AC 50/60 Hz conforming to IEC 60947-2","Operating Position":"Any position","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Electrical Life Cycles":"40000 cycles for AC-3 at 440 V In/2 40000 cycles for AC-3 at 440 V In","Mechanical Life Cycles":"40000 cycles","Main Product Or Component Type":"Motor circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$413.58","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/fce0e218253bef8347072b773fae6afa.pdf","sourceUrl":"https://www.se.com/ph/en/product/GV4LE02N/motor-circuit-breaker-tesys-gv4-3p-2a-icu-50ka-magnetic-everlink-terminals/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV4LE02N/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV4LE02N","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV4LE02N when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}