{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV4LE02N","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV4LE02N","canonicalUrl":"https://aoctrl.com/schneider/GV4LE02N","factsUrl":"https://aoctrl.com/api/mcp/products/GV4LE02N","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca GV4L motor circuit breaker, GV4LE02N, 3-pole, 2 A rated current, magnetic-electronic trip, IP40, 100 kA breaking capacity.","salesMarkdown":"The magnetic trip range spans 12…28 A, so short-circuit or locked-rotor events above that threshold cause instantaneous opening, protecting the motor and downstream cable. Breaking capacity reaches 100 kA Icu at 220…240 V AC and 50 kA at 380…415 V AC per IEC 60947-2. Rated for AC-3 duty per IEC 60947-4-1, so it handles the inrush of a squirrel-cage motor during starting and the switching of the running load. IP40 protection means it is suited for indoor panel environments where tools or fingers are the main intrusion risk — no washdown tolerance. Operating temperature range is -25…70 °C, storage -50…85 °C. EverLink BTR screw terminals on top accept 1.5…70 mm² solid or 1.5…50 mm² flexible; bottom terminals accept 2.5…95 mm² solid or 2.5…70 mm² flexible. Tightening torque is 9 N·m for the larger cable range (16…95 mm²) and 5 N·m for 1.5…10 mm². The terminals are rated for 960 °C glow-wire test per IEC 60695-2-11.","metaTitle":"Schneider Electric GV4LE02N TeSys Deca Motor Circuit Breaker","metaDescription":"Schneider Electric GV4LE02N TeSys Deca motor circuit breaker, 2 A rated current, 3 poles, magnetic-electronic trip, 100 kA breaking capacity at 240 V. Current lifecycle stage. Sour","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"116 mm","Range":"TeSys Deca","Width":"81 mm","title":"GV4LE02N","Colour":"Grey (RAL 7016)","Height":"155 mm","Standards":"EN/IEC 60947-2 EN/IEC 60947-4-1","Rated duty":"Continuous conforming to IEC 60947-4-1","description":"Motor circuit breaker, TeSys GV4, 3P, 2A, Icu 50kA, magnetic, EverLink terminals","Control type":"Toggle","Product name":"TeSys GV4","Motor power kW":"0.25 kW at 400...415 V AC 50/60 Hz 0.37 kW at 400...415 V AC 50/60 Hz 0.55 kW at 400...415 V AC 50/60 Hz 0.75 kW at 400...415 V AC 50/60 Hz 0.37 kW at 500 V AC 50/60 Hz 0.55 kW at 500 V AC 50/60 Hz 0.75 kW at 500 V AC 50/60 Hz 1.1 kW at 500 V AC 50/60 Hz 0.55 kW at 660...690 V AC 50/60 Hz 0.75 kW at 660...690 V AC 50/60 Hz 1.1 kW at 660...690 V AC 50/60 Hz 1.5 kW at 660...690 V AC 50/60 Hz","Fire resistance":"960 °C conforming to IEC 60695-2-11","lifecycle_stage":"current","Pollution degree":"3","Range of product":"TeSys GV4","Breaking capacity":"100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"GV4L","Poles description":"3P","Tightening torque":"9 N.m for cable 16...95 mm² 5 N.m for cable 1.5...10 mm²","Climatic withstand":"conforming to IACS E10","Device application":"Motor protection","Operating altitude":"5000 m","Operating position":"Any position","[In] rated current":"2 A","Trip unit technology":"Magnetic Electronic","Utilisation category":"Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1","Electrical durability":"40000 cycles for AC-3 at 440 V In/2 40000 cycles for AC-3 at 440 V In","Mechanical durability":"40000 cycles","Mechanical robustness":"Vibrations: +/- 1 mm 2...13.2 Hz conforming to IEC 60068-2-6 Vibrations: 0.7 gn 13.2...100 Hz conforming to IEC 60068-2-6 Shocks: 15 gn 11 ms conforming to IEC 60068-2-27","Maximum Operating Rate":"25 cyc/h","Connections - terminals":"EverLink BTR screw connectors (top) 1 cable(s) 1.5...70 mm² - solid EverLink BTR screw connectors (top) 1 cable(s) 1.5...50 mm² - flexible EverLink BTR screw connectors (bottom) 1 cable(s) 2.5...95 mm² - solid EverLink BTR screw connectors (bottom) 1 cable(s) 2.5...70 mm² - flexible","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Magnetic tripping current":"12...28 A","Product or component type":"Motor circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-1","Power dissipation per pole":"6.1 W","[Ui] rated insulation voltage":"800 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Uimp] rated impulse withstand voltage":"8 kV conforming to IEC 60947-2","[Ith] conventional free air thermal current":"115 A conforming to IEC 60947-4-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$413.58","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/fce0e218253bef8347072b773fae6afa.pdf","sourceUrl":"https://www.se.com/ph/en/product/GV4LE02N/motor-circuit-breaker-tesys-gv4-3p-2a-icu-50ka-magnetic-everlink-terminals/"},"ai":{"faq":[{"question":"What is the breaking capacity of the GV4LE02N?","answer":"The GV4LE02N has a breaking capacity of 100 kA Icu at 220…240 V AC, 50 kA at 380…415 V AC, 50 kA at 440 V AC, 25 kA at 500 V AC, 15 kA at 525 V AC, and 8 kA at 660…690 V AC, all per IEC 60947-2."},{"question":"What standards does the GV4LE02N comply with?","answer":"The GV4LE02N complies with EN/IEC 60947-2 (circuit-breaker standard) and EN/IEC 60947-4-1 (contactor and motor-starter standard). It is also suitable for isolation per IEC 60947-1."},{"question":"What is the magnetic trip range on the GV4LE02N?","answer":"The magnetic tripping current is adjustable from 12 A to 28 A, providing short-circuit and locked-rotor protection for the motor branch circuit."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV4LE02N","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV4LE02N when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}