{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV4LE02S6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV4LE02S6","canonicalUrl":"https://aoctrl.com/schneider/GV4LE02S6","factsUrl":"https://aoctrl.com/api/mcp/products/GV4LE02S6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca GV4L motor circuit breaker, GV4LE02S6, 3-pole, 2 A rated current, magnetic-electronic trip, 120 kA breaking capacity at 240 V AC.","salesMarkdown":"Rated at 2 A continuous (In), this breaker protects small motors — think fractional-horsepower pumps, fans, or conveyors — across a wide voltage range: it covers 0.25 kW at 400 V up to 1.5 kW at 690 V. That 2 A figure is the trip rating, not the load current you set it to; you'd dial it to match the motor's full-load amps, and the magnetic trip kicks in between 12 and 28 A for short-circuit protection. The GV4LE02S6 carries a 120 kA Icu at 240 V AC, dropping to 100 kA at 415 V, 70 kA at 440 V, and 10 kA at 690 V. It meets both EN/IEC 60947-2 (circuit breaker standard) and EN/IEC 60947-4-1 (motor starter standard), so it's certified for motor branch circuit protection as a combined motor protector — not just a distribution breaker. ## Panel integration and mechanical fit Mounts in any position, so you're not locked into a specific orientation inside the enclosure. The 27 mm connection pitch without spreaders (35 mm with) matches typical motor starter layouts; you'll need ring-terminal lugs on the power cables, with a 9 N·m torque for the main terminals (16–95 mm² cable) and 5 N·m for the control terminals (1.5–10 mm²). IP40 front-of-panel protection, IK07 impact resistance — fine for a dry indoor cabinet, but not washdown-rated. The grey RAL 7016 housing is standard for the TeSys Deca line.","metaTitle":"Schneider TeSys GV4LE02S6 Motor Circuit Breaker, 2 A, 120 kA","metaDescription":"Schneider Electric TeSys GV4LE02S6 motor circuit breaker, 2 A rated current, 120 kA breaking capacity at 240 V. Active production. IEC 60947-2/4-1. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"116 mm","Range":"TeSys Deca","Width":"81 mm","title":"GV4LE02S6","Colour":"Grey (RAL 7016)","Height":"155 mm","Standards":"EN/IEC 60947-2 EN/IEC 60947-4-1","Rated duty":"Continuous conforming to IEC 60947-4-1","description":"Motor circuit breaker, TeSys GV4, 3P, 2A, Icu 100kA, magnetic, lugs terminals","Control type":"Toggle","Product name":"TeSys GV4","Motor power kW":"0.25 kW at 400...415 V AC 50/60 Hz 0.37 kW at 400...415 V AC 50/60 Hz 0.55 kW at 400...415 V AC 50/60 Hz 0.75 kW at 400...415 V AC 50/60 Hz 0.37 kW at 500 V AC 50/60 Hz 0.55 kW at 500 V AC 50/60 Hz 0.75 kW at 500 V AC 50/60 Hz 1.1 kW at 500 V AC 50/60 Hz 0.55 kW at 660...690 V AC 50/60 Hz 0.75 kW at 660...690 V AC 50/60 Hz 1.1 kW at 660...690 V AC 50/60 Hz 1.5 kW at 660...690 V AC 50/60 Hz","Fire resistance":"960 °C conforming to IEC 60695-2-11","lifecycle_stage":"current","Connection pitch":"27 mm without spreaders 35 mm with spreaders","Pollution degree":"3","Range of product":"TeSys GV4","Breaking capacity":"120 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 18 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"GV4L","Poles description":"3P","Tightening torque":"9 N.m for cable 16...95 mm² 5 N.m for cable 1.5...10 mm²","Climatic withstand":"conforming to IACS E10","Device application":"Motor protection","Operating altitude":"5000 m","Operating position":"Any position","[In] rated current":"2 A","Trip unit technology":"Magnetic Electronic","Utilisation category":"Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1","Electrical durability":"40000 cycles for AC-3 at 440 V In/2 40000 cycles for AC-3 at 440 V In","Mechanical durability":"40000 cycles","Mechanical robustness":"Vibrations: +/- 1 mm 2...13.2 Hz conforming to IEC 60068-2-6 Vibrations: 0.7 gn 13.2...100 Hz conforming to IEC 60068-2-6 Shocks: 15 gn 11 ms conforming to IEC 60068-2-27","Maximum Operating Rate":"25 cyc/h","Connections - terminals":"Lugs-ring terminals","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Magnetic tripping current":"12...28 A","Product or component type":"Motor circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-1","Power dissipation per pole":"6.1 W","[Ui] rated insulation voltage":"800 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Uimp] rated impulse withstand voltage":"8 kV conforming to IEC 60947-2","[Ith] conventional free air thermal current":"115 A conforming to IEC 60947-4-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e429c798b116412d5207f932c5a1beb0.pdf","sourceUrl":"https://www.se.com/za/en/product/GV4LE02S6/motor-circuit-breaker-tesys-gv4-3p-2a-icu-100ka-magnetic-lugs-terminals/"},"ai":{"faq":[{"question":"What is the closest alternative to GV4LE02S6 in the TeSys family?","answer":"Within the same TeSys Deca GV4L family, the closest alternative would be a different current rating — for example, the GV4LE03S6 at 3 A or GV4LE01S6 at 1 A. They share the same physical footprint, breaking capacity, and trip technology; only the 2 A In rating differs. There is no pin-compatible drop-in from the older GV2 or GV3 series because the mounting hole pattern and terminal pitch changed with the Deca line."},{"question":"What compliance documentation does Schneider provide for GV4LE02S6?","answer":"The part is certified to EN/IEC 60947-2 and EN/IEC 60947-4-1. Climatic withstand conforms to IACS. Fire resistance tested to 960 °C per IEC 60695-2-11. It is suitable for isolation per IEC 60947-1. The manufacturer typically provides a Declaration of Performance (DoP), CE/UKCA declaration, and UL/CSA recognition on request — these are standard for the TeSys Deca line."},{"question":"What are the key specifications for panel fit?","answer":"Dimensions are 155 mm high, 81 mm wide, 116 mm deep. Mounts in any position on 35 mm DIN rail or via screw lugs. Connection pitch is 27 mm without spreaders, 35 mm with. Terminal torque: 9 N·m for 16–95 mm² cable, 5 N·m for 1.5–10 mm² cable. IP40 front protection, IK07 impact resistance."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV4LE02S6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV4LE02S6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}