{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV4LE03N","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV4LE03N","canonicalUrl":"https://aoctrl.com/schneider/GV4LE03N","factsUrl":"https://aoctrl.com/api/mcp/products/GV4LE03N","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys GV4 motor circuit breaker, GV4LE03N, 3-pole, 3.5 A rated current, magnetic-electronic trip, 100 kA breaking capacity at 240 V.","salesMarkdown":"The GV4LE03N is a 3-pole motor circuit breaker from the Schneider Electric TeSys GV4 range, rated at 3.5 A continuous current for motor protection. The 3.5 A In sets the continuous current the breaker will carry without tripping — match this to the motor full-load current. The magnetic trip range of 21...49 A provides instantaneous short-circuit protection; the electronic overload handles the thermal curve. Motor power ratings span 0.55 kW at 400 V up to 2.2 kW at 690 V, so one breaker covers a range of motor sizes depending on line voltage. The utilisation category AC-3 confirms it is rated for switching squirrel-cage motors — starting and stopping under load. Suitability for isolation per IEC 60947-1 means this breaker can serve as a visible-disconnect point — no separate isolator needed upstream. The GV4LE03N occupies a 81 x 155 x 116 mm footprint on the DIN rail. EverLink BTR screw terminals accept up to 95 mm² on the bottom (load side) and 70 mm² on the top (line side), with tightening torques of 9 N·m for larger cables and 5 N·m for smaller ones. IK07 impact rating handles incidental tool drops during commissioning. Maximum operating rate is 25 cycles per hour — enough for manual start/stop but not for high-speed jogging. Mechanical durability is 40,000 cycles; electrical durability is also 40,000 cycles at AC-3 rated current.","metaTitle":"GV4LE03N TeSys GV4 Motor Circuit Breaker, 3.5 A, 3P","metaDescription":"Schneider Electric TeSys GV4 motor circuit breaker GV4LE03N, 3.5 A In, 3-pole, 100 kA breaking capacity, active production. Sourced to order via authorized channel.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"116 mm","Range":"TeSys Deca","Width":"81 mm","title":"GV4LE03N","Colour":"Grey (RAL 7016)","Height":"155 mm","Standards":"EN/IEC 60947-4-1 EN/IEC 60947-2","Rated duty":"Continuous conforming to IEC 60947-4-1","description":"Motor circuit breaker, TeSys GV4, 3P, 3.5A, Icu 50kA, magnetic, EverLink terminals","Control type":"Toggle","Product name":"TeSys GV4","Motor power kW":"0.55 kW at 400...415 V AC 50/60 Hz 0.75 kW at 400...415 V AC 50/60 Hz 0.75 kW at 500 V AC 50/60 Hz 1.1 kW at 500 V AC 50/60 Hz 1.1 kW at 660...690 V AC 50/60 Hz 1.5 kW at 660...690 V AC 50/60 Hz 1.5 kW at 500 V AC 50/60 Hz 2.2 kW at 660...690 V AC 50/60 Hz 1.1 kW at 400...415 V AC 50/60 Hz","Fire resistance":"960 °C conforming to IEC 60695-2-11","lifecycle_stage":"current","Pollution degree":"3","Range of product":"TeSys GV4","Breaking capacity":"100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"GV4L","Poles description":"3P","Tightening torque":"9 N.m for cable 16...95 mm² 5 N.m for cable 1.5...10 mm²","Climatic withstand":"conforming to IACS E10","Device application":"Motor protection","Operating altitude":"5000 m","Operating position":"Any position","[In] rated current":"3.5 A","Trip unit technology":"Magnetic Electronic","Utilisation category":"Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1","Electrical durability":"40000 cycles for AC-3 at 440 V In/2 40000 cycles for AC-3 at 440 V In","Mechanical durability":"40000 cycles","Mechanical robustness":"Vibrations: +/- 1 mm 2...13.2 Hz conforming to IEC 60068-2-6 Vibrations: 0.7 gn 13.2...100 Hz conforming to IEC 60068-2-6 Shocks: 15 gn 11 ms conforming to IEC 60068-2-27","Maximum Operating Rate":"25 cyc/h","Connections - terminals":"EverLink BTR screw connectors (top) 1 cable(s) 1.5...70 mm² - solid EverLink BTR screw connectors (top) 1 cable(s) 1.5...50 mm² - flexible EverLink BTR screw connectors (bottom) 1 cable(s) 2.5...95 mm² - solid EverLink BTR screw connectors (bottom) 1 cable(s) 2.5...70 mm² - flexible","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Magnetic tripping current":"21...49 A","Product or component type":"Motor circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-1","Power dissipation per pole":"6.1 W","[Ui] rated insulation voltage":"800 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Uimp] rated impulse withstand voltage":"8 kV conforming to IEC 60947-2","[Ith] conventional free air thermal current":"115 A conforming to IEC 60947-4-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$391.17","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f88b72117ba22e17a3e819b6c15762ea.pdf","sourceUrl":"https://www.se.com/ph/en/product/GV4LE03N/motor-circuit-breaker-tesys-gv4-3p-3-5a-icu-50ka-magnetic-everlink-terminals/"},"ai":{"faq":[{"question":"What is the breaking capacity of the GV4LE03N?","answer":"Breaking capacity is 100 kA Icu at 220...240 V AC, 50 kA at 380...415 V AC, 50 kA at 440 V AC, 25 kA at 500 V AC, 15 kA at 525 V AC, and 8 kA at 660...690 V AC, all per IEC 60947-2."},{"question":"What motor power range does the GV4LE03N cover?","answer":"It covers 0.55 kW at 400...415 V up to 2.2 kW at 660...690 V AC, depending on supply voltage. Specific ratings: 0.55 kW at 400 V, 0.75 kW at 500 V, 1.1 kW at 690 V, and 2.2 kW at 690 V."},{"question":"What compliance standards does the GV4LE03N meet?","answer":"It is certified to EN/IEC 60947-4-1 (motor starter) and EN/IEC 60947-2 (circuit breaker). It also meets IACS for climatic withstand and IEC 60068-2-6/27 for vibration and shock."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV4LE03N","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV4LE03N when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}