{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV4LE03S6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV4LE03S6","canonicalUrl":"https://aoctrl.com/schneider/GV4LE03S6","factsUrl":"https://aoctrl.com/api/mcp/products/GV4LE03S6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys GV4 motor circuit breaker, GV4LE03S6, 3.5 A rated current, 120 kA breaking capacity at 240 V AC, 3-pole, magnetic-electronic trip.","salesMarkdown":"The Schneider Electric GV4LE03S6 is a 3-pole motor circuit breaker from the TeSys GV4 series, rated for 3.5 A continuous current. That 3.5 A is the motor full-load current it protects — pair it with a contactor sized for the same motor FLA. The magnetic-electronic trip unit gives it a magnetic trip window of 21 to 49 A, so it handles inrush without nuisance tripping on a 0.55 kW motor at 400 V. Breaking capacity is the headline here: 120 kA Icu at 240 V AC, 100 kA at 415 V, and still 10 kA at 690 V. That means it can sit upstream of a fault with enough interrupting capacity to clear a bolted short without the upstream feeder breaker having to open — selectivity without a bigger frame. Rated for isolation per IEC 60947-1, so it doubles as a visible disconnect. The GV4L frame takes a 27 mm connection pitch without spreaders, 35 mm with. That's a standard DIN-rail footprint — snaps onto the rail, no screws. The toggle control and lugs/ring terminals mean a panel builder can land 16 to 95 mm² cable at 9 N·m torque, or 1.5 to 10 mm² at 5 N·m. IP40 front-of-panel protection, IK07 impact rating — it's a panel-mount device, not a washdown unit. The grey RAL 7016 housing is the standard TeSys Deca colour. Operating altitude up to 5000 m means it's fine for high-altitude installations without derating.","metaTitle":"Schneider GV4LE03S6 TeSys GV4 Motor Circuit Breaker, 3.5 A","metaDescription":"Schneider Electric GV4LE03S6 motor circuit breaker, 3.5 A rated current, 120 kA breaking capacity at 240 V. TeSys GV4 series, current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"116 mm","Range":"TeSys Deca","Width":"81 mm","Colour":"Grey (RAL 7016)","Height":"155 mm","Standards":"EN/IEC 60947-2 EN/IEC 60947-4-1","Rated duty":"Continuous conforming to IEC 60947-4-1","Control type":"Toggle","Product name":"TeSys GV4","Motor power kW":"0.55 kW at 400...415 V AC 50/60 Hz 0.75 kW at 400...415 V AC 50/60 Hz 0.75 kW at 500 V AC 50/60 Hz 1.1 kW at 500 V AC 50/60 Hz 1.1 kW at 660...690 V AC 50/60 Hz 1.5 kW at 660...690 V AC 50/60 Hz 1.5 kW at 500 V AC 50/60 Hz 2.2 kW at 660...690 V AC 50/60 Hz 1.1 kW at 400...415 V AC 50/60 Hz","Fire resistance":"960 °C conforming to IEC 60695-2-11","lifecycle_stage":"current","Connection pitch":"27 mm without spreaders 35 mm with spreaders","Pollution degree":"3","Range of product":"TeSys GV4","Breaking capacity":"120 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 18 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"GV4L","Poles description":"3P","Tightening torque":"9 N.m for cable 16...95 mm² 5 N.m for cable 1.5...10 mm²","Climatic withstand":"conforming to IACS E10","Device application":"Motor protection","Operating altitude":"5000 m","Operating position":"Any position","[In] rated current":"3.5 A","Trip unit technology":"Magnetic Electronic","Utilisation category":"Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1","Electrical durability":"40000 cycles for AC-3 at 440 V In/2 40000 cycles for AC-3 at 440 V In","Mechanical durability":"40000 cycles","Mechanical robustness":"Vibrations: +/- 1 mm 2...13.2 Hz conforming to IEC 60068-2-6 Vibrations: 0.7 gn 13.2...100 Hz conforming to IEC 60068-2-6 Shocks: 15 gn 11 ms conforming to IEC 60068-2-27","Maximum Operating Rate":"25 cyc/h","Connections - terminals":"Lugs-ring terminals","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Magnetic tripping current":"21...49 A","Product or component type":"Motor circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-1","Power dissipation per pole":"6.1 W","[Ui] rated insulation voltage":"800 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Uimp] rated impulse withstand voltage":"8 kV conforming to IEC 60947-2","[Ith] conventional free air thermal current":"115 A conforming to IEC 60947-4-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/bad8fed23144a54763ae9bdf77a3c9cd.pdf","sourceUrl":"https://www.se.com/za/en/product/GV4LE03S6/motor-circuit-breaker-tesys-gv4-3p-3-5a-icu-100ka-magnetic-lugs-terminals/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV4LE03S6/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings I need to check for fit?","answer":"The rated current is 3.5 A (motor FLA). Breaking capacity is 120 kA at 240 V AC, 100 kA at 415 V, 70 kA at 440 V, 30 kA at 500 V, 18 kA at 525 V, and 10 kA at 690 V. Magnetic trip threshold is 21 to 49 A. It's a 3-pole device rated for 690 V operational voltage and 800 V insulation voltage."},{"question":"What standards does the GV4LE03S6 comply with?","answer":"It complies with EN/IEC 60947-2 (circuit-breaker standard) and EN/IEC 60947-4-1 (contactor/motor-starter standard). It is rated for isolation per IEC 60947-1 and has a pollution degree of 3."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV4LE03S6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV4LE03S6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}