{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV4LE07N6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV4LE07N6","canonicalUrl":"https://aoctrl.com/schneider/GV4LE07N6","factsUrl":"https://aoctrl.com/api/mcp/products/GV4LE07N6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys GV4 series, motor circuit breaker, GV4LE07N6, 3P, 7 A In, 100 kA Icu at 240 V AC, magnetic-electronic trip.","salesMarkdown":"It's a 3-pole unit with a rated current of 7 A and uses a combined magnetic and electronic trip unit technology. Its primary job is to protect motor feeders against short-circuits and overloads, and it's rated for continuous duty per IEC 60947-4-1. The magnetic trip is adjustable between 42 and 98 A, covering a range of motor sizes. The breaker is rated for isolation per IEC 60947-1, meaning it can be used as a disconnecting means in the motor branch circuit. The headline breaking capacity is 100 kA Icu at 220-240 V AC, which drops to 50 kA at 380-415 V and 15 kA at 525 V. The motor power ratings span from 1.5 kW at 400 V up to 7.5 kW at 690 V, so it fits a range of small to medium induction motors. For a 400 V line, it covers 1.5 to 3 kW motors depending on the exact rating. Utilization category is AC-3 per IEC 60947-4-1, which is the standard for squirrel-cage motor starting — switching motors during running, not just isolating them. It's also Category A per IEC 60947-2 for general circuit protection. Electrical durability is rated at 40,000 cycles under AC-3 at 440 V, both at full load and at half load. Mechanical durability matches at 40,000 cycles. That's a solid service life for a motor starter duty cycle in most industrial applications. Power dissipation per pole is 6.1 W, so total heat load in the enclosure is about 18.3 W. Dimensions are 155 mm high, 81 mm wide, and 116 mm deep. It's designed for panel mounting with lugs or ring terminals, accepting cables from 1.5 to 95 mm². Tightening torque is 9 N.m for the larger cable range and 5 N.m for the smaller. The connection pitch is 27 mm without spreaders, or 35 mm with them — useful to know when laying out busbars or cable ducts in the enclosure. IK07 impact resistance handles light mechanical knocks during installation. The GV4LE07N6 complies with EN/IEC 60947-2 (circuit-breaker standard) and EN/IEC 60947-4-1 (contactor and motor-starter standard). It also meets IEC 60695-2-11 for glow-wire fire resistance at 960 °C, and IACS for climatic withstand.","metaTitle":"Schneider Electric GV4LE07N6 TeSys GV4 Motor Circuit Breaker","metaDescription":"Schneider Electric GV4LE07N6 TeSys GV4 motor circuit breaker, 7 A rated current, 100 kA breaking capacity at 240 V. EN/IEC 60947-2 and 60947-4-1. Current production. Sourced to ord","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"116 mm","Range":"TeSys Deca","Width":"81 mm","Colour":"Grey (RAL 7016)","Height":"155 mm","Standards":"EN/IEC 60947-2 EN/IEC 60947-4-1","Rated duty":"Continuous conforming to IEC 60947-4-1","Control type":"Toggle","Product name":"TeSys GV4","Motor power kW":"1.5 kW at 400...415 V AC 50/60 Hz 2.2 kW at 400...415 V AC 50/60 Hz 2.5 kW at 400...415 V AC 50/60 Hz 3 kW at 400...415 V AC 50/60 Hz 2.2 kW at 500 V AC 50/60 Hz 2.5 kW at 500 V AC 50/60 Hz 3 kW at 500 V AC 50/60 Hz 4 kW at 500 V AC 50/60 Hz 3 kW at 660...690 V AC 50/60 Hz 4 kW at 660...690 V AC 50/60 Hz 5.5 kW at 660...690 V AC 50/60 Hz 7.5 kW at 660...690 V AC 50/60 Hz","Fire resistance":"960 °C conforming to IEC 60695-2-11","lifecycle_stage":"current","Connection pitch":"27 mm without spreaders 35 mm with spreaders","Pollution degree":"3","Range of product":"TeSys GV4","Breaking capacity":"100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"GV4L","Poles description":"3P","Tightening torque":"9 N.m for cable 16...95 mm² 5 N.m for cable 1.5...10 mm²","Climatic withstand":"conforming to IACS E10","Device application":"Motor protection","Operating altitude":"5000 m","Operating position":"Any position","[In] rated current":"7 A","Trip unit technology":"Magnetic Electronic","Utilisation category":"Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1","Electrical durability":"40000 cycles for AC-3 at 440 V In/2 40000 cycles for AC-3 at 440 V In","Mechanical durability":"40000 cycles","Mechanical robustness":"Vibrations: +/- 1 mm 2...13.2 Hz conforming to IEC 60068-2-6 Vibrations: 0.7 gn 13.2...100 Hz conforming to IEC 60068-2-6 Shocks: 15 gn 11 ms conforming to IEC 60068-2-27","Maximum Operating Rate":"25 cyc/h","Connections - terminals":"Lugs-ring terminals","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Magnetic tripping current":"42...98 A","Product or component type":"Motor circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-1","Power dissipation per pole":"6.1 W","[Ui] rated insulation voltage":"800 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Uimp] rated impulse withstand voltage":"8 kV conforming to IEC 60947-2","[Ith] conventional free air thermal current":"115 A conforming to IEC 60947-4-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/3a3c78050cd49b4802fd55f742032c42.pdf","sourceUrl":"https://www.se.com/ie/en/product/GV4LE07N6/motor-circuit-breaker-tesys-gv4-3p-7a-icu-50ka-magnetic-lugs-terminals/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV4LE07N6/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings I need to check for fit?","answer":"The GV4LE07N6 is a 3-pole motor circuit breaker rated at 7 A continuous current, with a magnetic trip range of 42-98 A. Its breaking capacity is 100 kA at 240 V AC, 50 kA at 415 V, and 15 kA at 525 V. It covers motor power from 1.5 kW to 7.5 kW depending on line voltage."},{"question":"What compliance documentation does Schneider provide for this part?","answer":"The GV4LE07N6 is certified to EN/IEC 60947-2 and EN/IEC 60947-4-1. It also meets IEC 60695-2-11 glow-wire test at 960 °C and IACS climatic withstand. Standard documentation includes the Declaration of Conformity and test certificates per these standards."},{"question":"What is the closest alternative to the GV4LE07N6 in the TeSys GV4 family?","answer":"Within the TeSys GV4 family, the closest alternative would be a different amp rating — for example, the GV4LE08N6 at 8 A or GV4LE06N6 at 6 A. These are form-fit-function identical in dimensions and breaking capacity, differing only in the continuous current rating and magnetic trip range. There is no pin-compatible alternate outside the GV4 series; the GV4L is the standard motor circuit breaker platform."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV4LE07N6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV4LE07N6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}