{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV4LE115N6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV4LE115N6","canonicalUrl":"https://aoctrl.com/schneider/GV4LE115N6","factsUrl":"https://aoctrl.com/api/mcp/products/GV4LE115N6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric, TeSys Deca series, GV4LE115N6 motor circuit breaker, 3P, 115 A In, 100 kA Icu at 240 V AC, 50/60 Hz.","salesMarkdown":"It's a 3-pole unit with a toggle control, designed for motor protection in industrial control panels. The headline breaking capacity is 100 kA Icu at 220...240 V AC, dropping to 50 kA at 380...415 V AC and 15 kA at 525 V AC. That's enough SCCR headroom for most industrial service-entrance or sub-distribution boards fed by a transformer of moderate impedance. The magnetic trip is set at 480...1120 A, meaning it clears bolted faults fast while riding through normal motor inrush. ## Motor power and application fit The GV4LE115N6 covers a wide motor power band depending on the supply voltage: 37 kW at 400 V, 55 kW at 500 V, and up to 110 kW at 690 V. The trip unit is magnetic-electronic, so it provides both short-circuit and overload protection in a single device. For a 115 A motor circuit breaker, this is the range you'd expect for a 37–55 kW motor at common European voltages. Utilisation category is AC-3 per IEC 60947-4-1, which is the standard for squirrel-cage motors — starting, stopping, and occasional plugging. The electrical durability is 10,000 cycles at AC-3 at 440 V with half-rated current, and 5,000 cycles at full-rated current. Mechanical durability is 40,000 cycles. That's a solid service life for a motor branch circuit in a conveyor, pump, or fan application. The breaker measures 155 mm high by 81 mm wide by 116 mm deep. The connection pitch is 27 mm without spreaders, expanding to 35 mm with spreaders — important to note when laying out the gland plate and busbar runs in a dense panel. IP40 protection means it's fine inside a clean enclosure but not for washdown areas. The IK07 impact rating handles accidental tool drops. Operating altitude goes to 5000 m, which covers most high-altitude installations without derating. Terminals accept lugs or ring terminals for cable from 1.5 to 95 mm², with tightening torques of 5 N.m for the smaller range and 9 N.m for the larger. That's a robust connection range — enough for the 115 A rating with standard copper cable.","metaTitle":"Schneider Electric GV4LE115N6 TeSys Deca Motor Circuit Break","metaDescription":"Schneider Electric GV4LE115N6 TeSys Deca motor circuit breaker, 115 A rated current, 100 kA breaking capacity at 240 V. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"116 mm","Range":"TeSys Deca","Width":"81 mm","title":"GV4LE115N6","Colour":"Grey (RAL 7016)","Height":"155 mm","Standards":"EN/IEC 60947-4-1 EN/IEC 60947-2","Rated duty":"Continuous conforming to IEC 60947-4-1","description":"Motor circuit breaker, TeSys GV4, 3P, 115A, Icu 50kA, magnetic, lugs terminals","Control type":"Toggle","Product name":"TeSys GV4","Motor power kW":"37 kW at 400...415 V AC 50/60 Hz 45 kW at 400...415 V AC 50/60 Hz 55 kW at 400...415 V AC 50/60 Hz 45 kW at 500 V AC 50/60 Hz 55 kW at 500 V AC 50/60 Hz 75 kW at 500 V AC 50/60 Hz 75 kW at 660...690 V AC 50/60 Hz 90 kW at 660...690 V AC 50/60 Hz 110 kW at 660...690 V AC 50/60 Hz","Fire resistance":"960 °C conforming to IEC 60695-2-11","lifecycle_stage":"current","Connection pitch":"27 mm without spreaders 35 mm with spreaders","Pollution degree":"3","Range of product":"TeSys GV4","Breaking capacity":"100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"GV4L","Poles description":"3P","Tightening torque":"9 N.m for cable 16...95 mm² 5 N.m for cable 1.5...10 mm²","Climatic withstand":"conforming to IACS E10","Device application":"Motor protection","Operating altitude":"5000 m","Operating position":"Any position","[In] rated current":"115 A","Trip unit technology":"Magnetic Electronic","Utilisation category":"Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1","Electrical durability":"10000 cycles for AC-3 at 440 V In/2 5000 cycles for AC-3 at 440 V In","Mechanical durability":"40000 cycles","Mechanical robustness":"Vibrations: +/- 1 mm 2...13.2 Hz conforming to IEC 60068-2-6 Vibrations: 0.7 gn 13.2...100 Hz conforming to IEC 60068-2-6 Shocks: 15 gn 11 ms conforming to IEC 60068-2-27","Maximum Operating Rate":"25 cyc/h","Connections - terminals":"Lugs-ring terminals","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Magnetic tripping current":"480...1120 A","Product or component type":"Motor circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-1","Power dissipation per pole":"6.1 W","[Ui] rated insulation voltage":"800 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Uimp] rated impulse withstand voltage":"8 kV conforming to IEC 60947-2","[Ith] conventional free air thermal current":"115 A conforming to IEC 60947-4-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/ie/en/product/GV4LE115N6/motor-circuit-breaker-tesys-gv4-3p-115a-icu-50ka-magnetic-lugs-terminals/"},"ai":{"faq":[{"question":"What are the key ratings for this motor circuit breaker?","answer":"Rated current is 115 A. Breaking capacity is 100 kA Icu at 240 V AC, 50 kA at 415 V, and 15 kA at 525 V. The magnetic trip range is 480–1120 A. Motor power coverage goes from 37 kW at 400 V up to 110 kW at 690 V."},{"question":"What standards does the GV4LE115N6 comply with?","answer":"It is certified to EN/IEC 60947-4-1 (motor starters and controllers) and EN/IEC 60947-2 (circuit breakers). It is suitable for isolation per IEC 60947-1."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV4LE115N6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV4LE115N6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}