{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV4LE25B","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV4LE25B","canonicalUrl":"https://aoctrl.com/schneider/GV4LE25B","factsUrl":"https://aoctrl.com/api/mcp/products/GV4LE25B","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca GV4 series, GV4LE25B motor circuit breaker, 3-pole, 25 A rated current, magnetic-electronic trip, IP40.","salesMarkdown":"It's a 3-pole device with a magnetic-electronic trip unit — the magnetic part handles short-circuit trips (150...350 A threshold), while the electronic side manages overload protection. At 400 V you get 25 kA, still enough for most industrial distribution. That's the utilisation category that matters for motor switching — AC-1 resistive loads would be easier, but AC-3 is what you need for direct-on-line motor starts. The GV4LE25B is a panel-mount device — no DIN-rail clip on this one. It bolts into the enclosure on a mounting plate. Dimensions are 155 mm high, 81 mm wide, 116 mm deep. That 81 mm width is three pole spaces wide on a standard 27 mm/module grid, so it takes up the same footprint as a typical 3-pole contactor in the TeSys range. Terminals are EverLink BTR screw connectors. Top side accepts 1.5...70 mm² solid or 1.5...50 mm² flexible; bottom side takes 2.5...95 mm² solid or 2.5...70 mm² flexible. Tightening torque is 9 N·m for the larger cables (16...95 mm²) and 5 N·m for the smaller ones (1.5...10 mm²). That's a standard torque driver setting — no special tooling needed. IP40 protection means it's for indoor use in a closed panel — not for washdown areas or outdoor cabinets without a secondary enclosure. IK07 impact resistance handles light knocks during panel assembly, but don't drop a wrench on it. Compliance documentation is straightforward: it carries EN/IEC 60947-2 (circuit-breaker standard) and EN/IEC 60947-4-1 (motor-starter standard) approvals. That covers both the overcurrent protection and the motor-switching duty in one device. The 25 A rated current is the headline number, but the motor power table tells you what motor it actually drives: 5.5 kW at 400 V, 7.5 kW at 500 V, up to 18.5 kW at 690 V. Electrical durability is 40,000 cycles at AC-3 with half-rated current, and 20,000 cycles at full rated current. That's the mechanical life of the contacts under motor-switching duty. For a panel that cycles a conveyor motor once every two minutes, that's roughly 67 days of continuous operation at full load — plan spares accordingly if your duty cycle is high. The magnetic trip range of 150...350 A is adjustable (via internal settings) and sets the instantaneous short-circuit threshold. That's roughly 6 to 14 times the rated current — typical for motor inrush. If your motor's locked-rotor current is near the low end of that range, you may need to dial the trip up to avoid nuisance trips on start.","metaTitle":"Schneider GV4LE25B TeSys Deca Motor Circuit Breaker, 25 A, 3","metaDescription":"Schneider GV4LE25B TeSys Deca motor circuit breaker, 25 A rated current, 3-pole, 50 kA breaking capacity at 240 V. Active production. EN/IEC 60947-2/4-1. Source to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Color":"Grey (RAL 7016)","Depth":"116 mm","Width":"81 mm","Height":"155 mm","Voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","IP Rating":"IP40","Application":"Motor protection","Control Type":"Toggle","Product Status":"Active","Trip Unit Type":"Magnetic Electronic","Pollution Degree":"3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Breaking Capacity":"50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"800 V AC 50/60 Hz conforming to IEC 60947-2","Operating Position":"Any position","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Electrical Life Cycles":"40000 cycles for AC-3 at 440 V In/2 20000 cycles for AC-3 at 440 V In","Mechanical Life Cycles":"40000 cycles","Main Product Or Component Type":"Motor circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d0be5eb45d5942dd636ac3db2efbb5bd.pdf","sourceUrl":"https://www.se.com/au/en/product/GV4LE25B/motor-circuit-breaker-tesys-gv4-tesys-gv4-3p-25a-icu-25ka-magnetic-everlink-terminals/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV4LE25B/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV4LE25B","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV4LE25B when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}