{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV4LE25B6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV4LE25B6","canonicalUrl":"https://aoctrl.com/schneider/GV4LE25B6","factsUrl":"https://aoctrl.com/api/mcp/products/GV4LE25B6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys GV4 motor circuit breaker, GV4LE25B6, 25 A rated current, 3-pole, 50 kA breaking capacity at 240 V AC, AC-3 utilization category.","salesMarkdown":"It combines magnetic and electronic trip technology, with a magnetic tripping range of 150...350 A to handle inrush without nuisance trips on starting. Breaking capacity hits 50 kA Icu at 220...240 V AC, tapering to 10 kA Icu at 500 V AC — enough for most low-voltage distribution fault levels downstream of a transformer. The motor power table shows it handles 5.5 kW at 400...415 V and up to 18.5 kW at 660...690 V, so match your motor nameplate to the voltage row. The GV4LE25B6 is a 3-pole unit in a grey (RAL 7016) enclosure, 155 mm high, 81 mm wide, 116 mm deep. Connection pitch is 27 mm without spreaders, 35 mm with — plan your busbar or lug-ring terminal layout accordingly. Tightening torque is 9 N·m for cable 16...95 mm², 5 N·m for 1.5...10 mm². IK07 impact resistance handles accidental tool drops during commissioning. Operating position is any position, and it's rated for altitudes up to 5000 m — useful for installations in high-altitude plants where air density affects cooling and arc extinction. Standards compliance covers EN/IEC 60947-4-1 (motor starters) and EN/IEC 60947-2 (circuit breakers), plus suitability for isolation per IEC 60947-1. Climatic withstand conforms to IACS for marine environments. Fire resistance at 960 °C per IEC 60695-2-11. ## Durability and thermal management Mechanical durability is 40,000 cycles; electrical durability for AC-3 at 440 V is 40,000 cycles at half rated current (In/2) and 20,000 cycles at full In. Maximum operating rate is 25 cycles per hour — fine for intermittent motor starting, not for high-speed jogging. Power dissipation is 6.1 W per pole, so at 25 A continuous you're looking at about 18.3 W total heat to vent from the enclosure. Vibration resistance covers ±1 mm at 2...13.2 Hz and 0.7 gn at 13.2...100 Hz per IEC 60068-2-6; shock rating is 15 gn for 11 ms. Ambient operating temperature isn't listed in this spec set, but the continuous duty rating per IEC 60947-4-1 implies standard 40 °C ambient with derating above.","metaTitle":"Schneider Electric GV4LE25B6 TeSys GV4 Motor Circuit Breaker","metaDescription":"Schneider Electric GV4LE25B6 TeSys GV4 motor circuit breaker, 25 A rated current, 50 kA breaking capacity at 240 V AC. AC-3 utilization, EN/IEC 60947-4-1 and 60947-2. Current lifec","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Color":"Grey (RAL 7016)","Depth":"116 mm","Width":"81 mm","Height":"155 mm","Voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","IP Rating":"IP40","Application":"Motor protection","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"27 mm without spreaders 35 mm with spreaders","Trip Unit Type":"Magnetic Electronic","Pollution Degree":"3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Breaking Capacity":"50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"800 V AC 50/60 Hz conforming to IEC 60947-2","Operating Position":"Any position","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Electrical Life Cycles":"40000 cycles for AC-3 at 440 V In/2 20000 cycles for AC-3 at 440 V In","Mechanical Life Cycles":"40000 cycles","Main Product Or Component Type":"Motor circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8b6252e83512d2491ec965089b5b39f7.pdf","sourceUrl":"https://www.se.com/ie/en/product/GV4LE25B6/motor-circuit-breaker-tesys-gv4-3p-25a-icu-25ka-magnetic-lugs-terminals/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV4LE25B6/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV4LE25B6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV4LE25B6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}