{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV4LE25N6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV4LE25N6","canonicalUrl":"https://aoctrl.com/schneider/GV4LE25N6","factsUrl":"https://aoctrl.com/api/mcp/products/GV4LE25N6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys GV4, motor circuit breaker, 3P, 25 A, magnetic electronic trip, 100 kA breaking capacity, EN/IEC 60947-4-1 and 60947-2.","salesMarkdown":"The Schneider Electric TeSys GV4LE25N6 is a 3-pole motor circuit breaker rated 25 A continuous, with a magnetic electronic trip unit that operates between 150 and 350 A. That 25 A figure governs the full-load motor current it can carry without nuisance tripping — size it to the motor nameplate, not the upstream feeder. The 100 kA breaking capacity at 240 V AC (Icu per IEC 60947-2) means it can safely interrupt a fault up to that level without the arc flashing over to adjacent devices; at 415 V the rating drops to 50 kA, still sufficient for most distribution-side faults in a 400 V panel. Certified to EN/IEC 60947-4-1 for motor starters and EN/IEC 60947-2 for circuit breakers, so it serves as both the disconnecting means and the short-circuit protection in a single enclosure. The GV4LE25N6 mounts in any position and occupies a 81 mm wide footprint on the DIN rail or panel. Depth is 116 mm, height 155 mm. Connection pitch is 27 mm without spreaders, 35 mm with — plan the gland plate and wireway clearance accordingly. Terminals accept lugs or ring terminals; tightening torque is 9 N·m for the main power cables (16–95 mm²) and 5 N·m for the control wiring (1.5–10 mm²). The IP40 enclosure keeps dust out but is not rated for washdown; install inside a sealed panel for wet environments. IK07 impact resistance handles accidental tool drops during commissioning. Fully documented compliance: certified to EN/IEC 60947-4-1 (motor starters) and EN/IEC 60947-2 (circuit breakers). Climatic withstand per IACS. Fire resistance tested to 960 °C per IEC 60695-2-11. Operating altitude up to 5000 m without derating.","metaTitle":"Schneider TeSys GV4LE25N6 Motor Circuit Breaker, 25 A, 100 k","metaDescription":"Schneider Electric TeSys GV4LE25N6 motor circuit breaker, 25 A rated current, 100 kA breaking capacity at 240 V, EN/IEC 60947-4-1 and 60947-2 certified. Active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"116 mm","Range":"TeSys Deca","Width":"81 mm","title":"GV4LE25N6","Colour":"Grey (RAL 7016)","Height":"155 mm","Standards":"EN/IEC 60947-4-1 EN/IEC 60947-2","Rated duty":"Continuous conforming to IEC 60947-4-1","description":"Motor circuit breaker, TeSys GV4, 3P, 25A, Icu 50kA, magnetic, lugs terminals","Control type":"Toggle","Product name":"TeSys GV4","Motor power kW":"7.5 kW at 660...690 V AC 50/60 Hz 5.5 kW at 400...415 V AC 50/60 Hz 7.5 kW at 500 V AC 50/60 Hz 9 kW at 660...690 V AC 50/60 Hz 11 kW at 660...690 V AC 50/60 Hz 7.5 kW at 400...415 V AC 50/60 Hz 9 kW at 400...415 V AC 50/60 Hz 11 kW at 400...415 V AC 50/60 Hz 9 kW at 500 V AC 50/60 Hz 11 kW at 500 V AC 50/60 Hz 15 kW at 500 V AC 50/60 Hz 15 kW at 660...690 V AC 50/60 Hz 18.5 kW at 660...690 V AC 50/60 Hz","Fire resistance":"960 °C conforming to IEC 60695-2-11","lifecycle_stage":"current","Connection pitch":"27 mm without spreaders 35 mm with spreaders","Pollution degree":"3","Range of product":"TeSys GV4","Breaking capacity":"100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"GV4L","Poles description":"3P","Tightening torque":"9 N.m for cable 16...95 mm² 5 N.m for cable 1.5...10 mm²","Climatic withstand":"conforming to IACS E10","Device application":"Motor protection","Operating altitude":"5000 m","Operating position":"Any position","[In] rated current":"25 A","Trip unit technology":"Magnetic Electronic","Utilisation category":"Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1","Electrical durability":"40000 cycles for AC-3 at 440 V In/2 20000 cycles for AC-3 at 440 V In","Mechanical durability":"40000 cycles","Mechanical robustness":"Vibrations: +/- 1 mm 2...13.2 Hz conforming to IEC 60068-2-6 Vibrations: 0.7 gn 13.2...100 Hz conforming to IEC 60068-2-6 Shocks: 15 gn 11 ms conforming to IEC 60068-2-27","Maximum Operating Rate":"25 cyc/h","Connections - terminals":"Lugs-ring terminals","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Magnetic tripping current":"150...350 A","Product or component type":"Motor circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-1","Power dissipation per pole":"6.1 W","[Ui] rated insulation voltage":"800 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Uimp] rated impulse withstand voltage":"8 kV conforming to IEC 60947-2","[Ith] conventional free air thermal current":"115 A conforming to IEC 60947-4-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0c55a060c5737e11bd15cd89891ebc5c.pdf","sourceUrl":"https://www.se.com/ie/en/product/GV4LE25N6/motor-circuit-breaker-tesys-gv4-3p-25a-icu-50ka-magnetic-lugs-terminals/"},"ai":{"faq":[{"question":"What breaking capacity does it offer at 415 V?","answer":"At 380–415 V AC, the Icu is 50 kA per IEC 60947-2. This drops to 15 kA at 525 V and 8 kA at 690 V."},{"question":"What is the closest alternative in the TeSys Deca family?","answer":"Within the same TeSys GV4 range, the GV4LE20N6 is the nearest sibling — identical form factor and breaking capacity, but with a 20 A rated current and a magnetic trip range of 120–280 A. The choice between the two is driven solely by the motor full-load current: use the 25 A for a 7.5 kW motor at 400 V, the 20 A for a 5.5 kW motor at the same voltage."},{"question":"What compliance documentation is available?","answer":"The GV4LE25N6 carries declarations of conformity to EN/IEC 60947-4-1 and EN/IEC 60947-2. It is suitable for isolation per IEC 60947-1, and its fire resistance is certified to 960 °C per IEC 60695-2-11. Climatic withstand is per IACS. Standard RoHS and REACH compliance documentation is provided by Schneider Electric."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV4LE25N6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV4LE25N6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}