{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV4LE25S6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV4LE25S6","canonicalUrl":"https://aoctrl.com/schneider/GV4LE25S6","factsUrl":"https://aoctrl.com/api/mcp/products/GV4LE25S6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys GV4 motor circuit breaker, 3-pole, 25 A rated current, magnetic-electronic trip, 120 kA breaking capacity at 240 V, IP40, current production.","salesMarkdown":"It is designed for motor protection, combining magnetic and electronic trip technology in a single device. Rated at 25 A continuous duty (In), it handles motor loads up to 7.5 kW at 400...415 V AC and up to 18.5 kW at 660...690 V AC, with a rated operational voltage (Ue) of 690 V AC and insulation voltage (Ui) of 800 V AC. The magnetic tripping window is set at 150...350 A, meaning it clears short-circuit faults fast while riding through normal motor inrush. Breaking capacity (Icu) reaches 120 kA at 240 V AC, 100 kA at 415 V, and 10 kA at 690 V, all per IEC 60947-2. Electrical durability is 40,000 cycles at AC-3 with half rated current (In/2) and 20,000 cycles at full In at 440 V. That sets the service life expectation for a motor-starting application. Power dissipation per pole is 6.1 W, so total heat load in the enclosure is roughly 18.3 W at rated current. Factor that into your thermal budget — especially in a sealed, non-ventilated panel. Suitable for indoor panel mounting, not washdown environments. IK07 impact resistance handles routine panel knocks. Compliance documentation includes EN/IEC 60947-4-1 and 60947-2 certification, fire resistance to 960 °C (IEC 60695-2-11), climatic withstand per IACS, and suitability for isolation per IEC 60947-1. That covers the main regulatory requirements for industrial control panels in most jurisdictions.","metaTitle":"Schneider Electric GV4LE25S6 TeSys GV4 Motor Circuit Breaker","metaDescription":"Schneider Electric TeSys GV4 motor circuit breaker, 25 A rated current, 120 kA breaking capacity at 240 V. EN/IEC 60947-4-1 and 60947-2. Current production. Sourced to order via au","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"116 mm","Range":"TeSys Deca","Width":"81 mm","title":"GV4LE25S6","Colour":"Grey (RAL 7016)","Height":"155 mm","Standards":"EN/IEC 60947-4-1 EN/IEC 60947-2","Rated duty":"Continuous conforming to IEC 60947-4-1","description":"Motor circuit breaker, TeSys GV4, 3P, 25A, Icu 100kA, magnetic, lugs terminals","Control type":"Toggle","Product name":"TeSys GV4","Motor power kW":"7.5 kW at 660...690 V AC 50/60 Hz 5.5 kW at 400...415 V AC 50/60 Hz 7.5 kW at 500 V AC 50/60 Hz 9 kW at 660...690 V AC 50/60 Hz 11 kW at 660...690 V AC 50/60 Hz 7.5 kW at 400...415 V AC 50/60 Hz 9 kW at 400...415 V AC 50/60 Hz 11 kW at 400...415 V AC 50/60 Hz 9 kW at 500 V AC 50/60 Hz 11 kW at 500 V AC 50/60 Hz 15 kW at 500 V AC 50/60 Hz 15 kW at 660...690 V AC 50/60 Hz 18.5 kW at 660...690 V AC 50/60 Hz","Fire resistance":"960 °C conforming to IEC 60695-2-11","lifecycle_stage":"current","Connection pitch":"27 mm without spreaders 35 mm with spreaders","Pollution degree":"3","Range of product":"TeSys GV4","Breaking capacity":"120 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 18 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"GV4L","Poles description":"3P","Tightening torque":"9 N.m for cable 16...95 mm² 5 N.m for cable 1.5...10 mm²","Climatic withstand":"conforming to IACS E10","Device application":"Motor protection","Operating altitude":"5000 m","Operating position":"Any position","[In] rated current":"25 A","Trip unit technology":"Magnetic Electronic","Utilisation category":"Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1","Electrical durability":"40000 cycles for AC-3 at 440 V In/2 20000 cycles for AC-3 at 440 V In","Mechanical durability":"40000 cycles","Mechanical robustness":"Vibrations: +/- 1 mm 2...13.2 Hz conforming to IEC 60068-2-6 Vibrations: 0.7 gn 13.2...100 Hz conforming to IEC 60068-2-6 Shocks: 15 gn 11 ms conforming to IEC 60068-2-27","Maximum Operating Rate":"25 cyc/h","Connections - terminals":"Lugs-ring terminals","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Magnetic tripping current":"150...350 A","Product or component type":"Motor circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-1","Power dissipation per pole":"6.1 W","[Ui] rated insulation voltage":"800 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Uimp] rated impulse withstand voltage":"8 kV conforming to IEC 60947-2","[Ith] conventional free air thermal current":"115 A conforming to IEC 60947-4-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/442db9ebfbbd03a99a0e09da428ac197.pdf","sourceUrl":"https://www.se.com/ie/en/product/GV4LE25S6/motor-circuit-breaker-tesys-gv4-3p-25a-icu-100ka-magnetic-lugs-terminals/"},"ai":{"faq":[{"question":"What are the key ratings for this motor circuit breaker?","answer":"Rated current 25 A, rated operational voltage 690 V AC, insulation voltage 800 V AC. Breaking capacity ranges from 120 kA at 240 V AC down to 10 kA at 690 V AC. Magnetic trip set at 150...350 A."},{"question":"What compliance documentation is available for GV4LE25S6?","answer":"It is certified to EN/IEC 60947-4-1 and 60947-2, with fire resistance to 960 °C (IEC 60695-2-11), climatic withstand per IACS, and isolation suitability per IEC 60947-1."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV4LE25S6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV4LE25S6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}