{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV4LE80B","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV4LE80B","canonicalUrl":"https://aoctrl.com/schneider/GV4LE80B","factsUrl":"https://aoctrl.com/api/mcp/products/GV4LE80B","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca GV4LE80B motor circuit breaker, 3-pole, 80 A rated current, magnetic electronic trip, 50 kA Icu breaking capacity at 240 V AC.","salesMarkdown":"It is rated at 80 A continuous current and carries motor power ratings of 37 kW at 400–415 V AC, 45 kW at 500 V AC, and 55 kW at 660–690 V AC, all at 50/60 Hz. The magnetic electronic trip unit provides adjustable magnetic tripping from 480 to 1120 A, covering inrush and locked-rotor conditions on the connected motor. Breaking capacity reaches 50 kA Icu at 240 V AC, 25 kA at 415 V, and 10 kA at 500 V, certified per IEC 60947-2. The utilisation category is AC-3 per IEC 60947-4-1, meaning it is rated for switching squirrel-cage motors during starting and running — the standard duty for motor circuit breakers in industrial lines. It also qualifies as Category A (no intentional short-time delay) per IEC 60947-2, appropriate for motor branch circuit protection where coordination with downstream contactors is handled separately. Dimensions are 155 mm high, 81 mm wide, and 116 mm deep, fitting a standard DIN-rail enclosure footprint. The EverLink BTR screw terminals on top accept 1.5–70 mm² solid or 1.5–50 mm² flexible cable; bottom terminals accept 2.5–95 mm² solid or 2.5–70 mm² flexible. Tightening torque is 9 N·m for the larger (16–95 mm²) cable range and 5 N·m for the smaller (1.5–10 mm²) range. IP40 protection suits dry indoor panel environments; IK07 impact rating handles incidental tool contact during commissioning. Climatic withstand conforms to IACS for marine environments, so it can be specified for shipboard auxiliary panels. If a second-source gate review is required, the TeSys Deca range includes other frame sizes at different current ratings, but the 80 A GV4LE80B is the direct fit for a 37 kW (400 V) motor branch. The 80 A rated current (In) sets the continuous thermal capacity — this breaker will carry 80 A indefinitely without tripping, per IEC 60947-4-1 continuous duty. The magnetic electronic trip unit responds to short-circuit currents between 480 and 1120 A (6 to 14 times In), covering the typical locked-rotor current of a 37 kW motor while riding through normal starting inrush. For overload protection, the electronic trip provides adjustable time-current curves, though the specific thermal setting range is not listed here; the breaker is designed to coordinate with a downstream TeSys contactor for full motor starter functionality. Electrical durability is 14,000 cycles at AC-3 duty with half rated current (In/2) and 7,000 cycles at full rated current (In) at 440 V. Mechanical durability is 40,000 cycles. These numbers define the maintenance interval: at one start per hour, the electrical contacts last roughly 2–3 years before replacement is prudent. The maximum operating rate of 25 cycles per hour sets a hard limit for jogging or rapid cycling applications. Power dissipation per pole is 6.1 W at rated current, totaling 18.3 W for the three poles. This heat must be considered in enclosure sizing — a sealed panel with multiple breakers may require forced ventilation or derating. The fire resistance rating of 960 °C per IEC 60695-2-11 ensures the enclosure material will not propagate a flame under fault conditions.","metaTitle":"Schneider Electric GV4LE80B TeSys Deca Motor Circuit Breaker","metaDescription":"Schneider Electric GV4LE80B motor circuit breaker, 80 A rated current, TeSys Deca range. Active production. Motor protection with magnetic electronic trip. 50 kA Icu at 240 V AC. S","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Grey (RAL 7016)","Depth":"116 mm","Width":"81 mm","Height":"155 mm","Voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","IP Rating":"IP40","Application":"Motor protection","Control Type":"Toggle","Product Status":"Active","Trip Unit Type":"Magnetic Electronic","Pollution Degree":"3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Breaking Capacity":"50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"800 V AC 50/60 Hz conforming to IEC 60947-2","Operating Position":"Any position","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Electrical Life Cycles":"14000 cycles for AC-3 at 440 V In/2 7000 cycles for AC-3 at 440 V In","Mechanical Life Cycles":"40000 cycles","Main Product Or Component Type":"Motor circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$341.18","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/ie/en/product/GV4LE80B/motor-circuit-breaker-tesys-gv4-3p-80a-icu-25ka-magnetic-everlink-terminals/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV4LE80B/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV4LE80B","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV4LE80B when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}