{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV4LE80S6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV4LE80S6","canonicalUrl":"https://aoctrl.com/schneider/GV4LE80S6","factsUrl":"https://aoctrl.com/api/mcp/products/GV4LE80S6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys GV4 motor circuit breaker, GV4LE80S6, 3-pole, 80 A rated current, 120 kA breaking capacity at 240 V AC, 37 kW at 400 V AC.","salesMarkdown":"It combines magnetic and electronic trip technology to protect against short circuits and overloads, with a breaking capacity of 120 kA Icu at 240 V AC and 100 kA at 415 V AC per IEC 60947-2. The 80 A rating sets the motor full-load current threshold — wire it for a 37 kW motor at 400 V or up to 55 kW at 690 V. Rated for AC-3 duty per IEC 60947-4-1, this breaker handles the inrush of squirrel-cage motors during starting and switching. The magnetic trip range is 480–1120 A, adjustable to coordinate with motor starting characteristics. Continuous duty rated per IEC 60947-4-1 means it carries the 80 A load indefinitely without derating in a 40 °C ambient. The GV4LE80S6 measures 155 mm high, 81 mm wide, and 116 mm deep — a compact 3-pole footprint for DIN-rail or screw-mount installation in a motor control center. Connection pitch is 27 mm without spreaders, 35 mm with them, accepting lugs or ring terminals up to 95 mm² cable at 9 N·m torque. IP40 front protection keeps out tools and fingers; IK07 impact rating handles panel-door knocks. Operates in any position at altitudes up to 5000 m, with storage from -50 to 85 °C. Fire resistance rated at 960 °C per IEC 60695-2-11. Approvals include EN/IEC 60947-2 and 60947-4-1, with suitability for isolation per IEC 60947-1. Climatic withstand conforms to IACS for marine and humid environments. No UL listing is stated in the evidence, so verify for North American panel builds.","metaTitle":"Schneider Electric GV4LE80S6 TeSys GV4 Motor Circuit Breaker","metaDescription":"Schneider Electric GV4LE80S6 TeSys GV4 motor circuit breaker, 80 A rated current, 120 kA breaking capacity at 240 V, 37 kW at 400 V. Current lifecycle stage, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"116 mm","Range":"TeSys Deca","Width":"81 mm","title":"GV4LE80S6","Colour":"Grey (RAL 7016)","Height":"155 mm","Standards":"EN/IEC 60947-2 EN/IEC 60947-4-1","Rated duty":"Continuous conforming to IEC 60947-4-1","description":"Motor circuit breaker, TeSys GV4, 3P, 80 A, Icu 100 kA, magnetic, lugs terminals","Control type":"Toggle","Product name":"TeSys GV4","Motor power kW":"37 kW at 400...415 V AC 50/60 Hz 45 kW at 500 V AC 50/60 Hz 55 kW at 500 V AC 50/60 Hz 22 kW at 400...415 V AC 50/60 Hz 30 kW at 500 V AC 50/60 Hz 37 kW at 660...690 V AC 50/60 Hz 45 kW at 660...690 V AC 50/60 Hz 55 kW at 660...690 V AC 50/60 Hz 30 kW at 400...415 V AC 50/60 Hz 37 kW at 500 V AC 50/60 Hz","Fire resistance":"960 °C conforming to IEC 60695-2-11","lifecycle_stage":"current","Connection pitch":"27 mm without spreaders 35 mm with spreaders","Pollution degree":"3","Range of product":"TeSys GV4","Breaking capacity":"120 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 18 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"GV4L","Poles description":"3P","Tightening torque":"9 N.m for cable 16...95 mm² 5 N.m for cable 1.5...10 mm²","Climatic withstand":"conforming to IACS E10","Device application":"Motor protection","Operating altitude":"5000 m","Operating position":"Any position","[In] rated current":"80 A","Trip unit technology":"Magnetic Electronic","Utilisation category":"Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1","Electrical durability":"14000 cycles for AC-3 at 440 V In/2 7000 cycles for AC-3 at 440 V In","Mechanical durability":"40000 cycles","Mechanical robustness":"Vibrations: +/- 1 mm 2...13.2 Hz conforming to IEC 60068-2-6 Vibrations: 0.7 gn 13.2...100 Hz conforming to IEC 60068-2-6 Shocks: 15 gn 11 ms conforming to IEC 60068-2-27","Maximum Operating Rate":"25 cyc/h","Connections - terminals":"Lugs-ring terminals","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Magnetic tripping current":"480...1120 A","Product or component type":"Motor circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-1","Power dissipation per pole":"6.1 W","[Ui] rated insulation voltage":"800 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Uimp] rated impulse withstand voltage":"8 kV conforming to IEC 60947-2","[Ith] conventional free air thermal current":"115 A conforming to IEC 60947-4-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"{'url': 'https://www.se.com/nz/en/product/download-pdf/GV4LE80S6?filename=Schneider+Electric_TeSys-Deca-frame-4_GV4LE80S6.pdf', 'path_name': '7b4eeb21ee6540ce93f92ef9b56ce7b5.pdf', 'path_url': 'https://s3.lax.sharktech.net/viassion/datasheets/schneider_electric/7b4eeb21ee6540ce93f92ef9b56ce7b5.pdf', 'status': 1}","sourceUrl":"https://www.se.com/eg/en/product/GV4LE80S6/motor-circuit-breaker-tesys-gv4-3p-80-a-icu-100-ka-magnetic-lugs-terminals/"},"ai":{"faq":[{"question":"What motor power does this cover at 400 V?","answer":"37 kW at 400–415 V AC, 50/60 Hz. Also rated 45 kW at 500 V and 55 kW at 690 V. The 80 A rated current sets the motor FLA limit."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV4LE80S6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV4LE80S6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}