{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV4P115N","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV4P115N","canonicalUrl":"https://aoctrl.com/schneider/GV4P115N","factsUrl":"https://aoctrl.com/api/mcp/products/GV4P115N","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys GV4 motor circuit breaker, GV4P115N, 3-pole, 115A, electronic/thermal-magnetic trip, gray RAL 7016.","salesMarkdown":"The GV4P115N is a 115 A motor circuit breaker from the TeSys Deca range, combining electronic and thermal-magnetic trip technology for AC-3 motor switching duty. Phase-failure detection is built in, and it is approved for isolation per IEC 60947-1. ## Fault performance and environmental rating The 115 A continuous carries a 4.6 W per pole dissipation, so panel thermal rise is predictable. With pollution degree 3 and IP40 enclosure, it holds up in industrial electrical rooms. Altitude rated to 5000 m — no derating for high installations. Schneider lists this part as current-production. No NRND or phase-out notices are active. For BOM planning, it is a standard line item — no supply risk from discontinuity. Order-to-RFQ lead times apply per quantity. ## Physical footprint and termination Occupies a 6.1 x 3.2 x 6.5 inch volume with any-position mounting. EverLink BTR screw terminals accept 1.5 to 95 mm² conductors. Tightening torque 9 N·m for mains, 5 N·m for control. Mechanical endurance 40,000 cycles; electrical 10,000 at AC-3 rated load.","metaTitle":"Schneider GV4P115N TeSys GV4 115A Motor Circuit Breaker","metaDescription":"GV4P115N motor circuit breaker, 115A, 3-pole, electronic/thermal-magnetic trip, 100kA breaking at 240V. Active production. UL/CSA/IEC rated. Order via RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Gray RAL 7016)","Depth":"6.5 in (165 mm)","Range":"TeSys Deca","Width":"3.2 in (81 mm)","Height":"6.1 in (155 mm)","Category":"US10I1122365","Standards":"CSA C22.2 No 60947-4-1 UL 60947-4-1 EN/IEC 60947-4-1 EN/IEC 60947-2","Rated duty":"Continuous IEC 60947-4-1","Control Type":"Rotary handle","Product name":"TeSys GV4","Motor power kW":"37 kW 400...415 V AC 50/60 Hz 45 kW 400...415 V AC 50/60 Hz 55 kW 400...415 V AC 50/60 Hz 45 kW 500 V AC 50/60 Hz 55 kW 500 V AC 50/60 Hz 75 kW 500 V AC 50/60 Hz 75 kW 660...690 V AC 50/60 Hz 90 kW 660...690 V AC 50/60 Hz 110 kW 660...690 V AC 50/60 Hz","Fire resistance":"1760 °F (960 °C) IEC 60695-2-11","lifecycle_stage":"current","Pollution degree":"3","Range of Product":"TeSys GV4","Breaking capacity":"100 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 50 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 50 kA Icu 440 V AC 50/60 Hz IEC 60947-2 15 kA Icu 525 V AC 50/60 Hz IEC 60947-2 65 kA 208Y/120 V AC 50/60 Hz UL 60947 65 kA 240 V AC 50/60 Hz UL 60947 35 kA 480Y/277 V AC 50/60 Hz UL 60947 8 kA Icu 660...690 V AC 50/60 Hz IEC 60947-2 25 kA Icu 500 V AC 50/60 Hz IEC 60947-2 18 kA 600Y/347 V AC 50/60 Hz UL 60947","Device short name":"GV4P","Poles description":"3P","Tightening torque":"79.7 lbf.in (9 N.m) 0.02...0.1 in² (16...95 mm²) 44.3 lbf.in (5 N.m) 0.002...0.02 in² (1.5...10 mm²)","Climatic withstand":"IACS E10","Device Application":"Motor protection","Line Rated Current":"115 A","Operating altitude":"5000 m","Operating position":"Any position","Trip unit technology":"Electronic Thermal-magnetic","Utilisation category":"Category A IEC 60947-2 AC-3 IEC 60947-4-1","Electrical durability":"10000 cycles AC-3 440 V In/2 5000 cycles AC-3 440 V In","Mechanical durability":"40000 cycles","Mechanical robustness":"Vibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 Vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 Shocks 15 gn 11 ms IEC 60068-2-27","Nbr. of units in pkg.":"1","Maximum Operating Rate":"25 cyc/h","Connections - terminals":"EverLink BTR screw connectors top) 1 0.002...0.1 in² (1.5...70 mm²) - solid EverLink BTR screw connectors top) 1 0.002...0.08 in² (1.5...50 mm²) - flexible EverLink BTR screw connectors bottom) 1 0.004...0.1 in² (2.5...95 mm²) - solid EverLink BTR screw connectors bottom) 1 0.004...0.1 in² (2.5...70 mm²) - flexible","IK degree of protection":"IK07 IEC 62262","IP degree of protection":"IP40 IEC 60529","Magnetic tripping current":"1955 A","Phase failure sensitivity":"Yes IEC 60947-4-1","Product or Component Type":"Motor circuit breaker","Suitability for isolation":"Yes IEC 60947-1","Power dissipation per pole":"4.6 W","[Ui] rated insulation voltage":"800 V AC 50/60 Hz IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz IEC 60947-2","Ambient Air Temperature for Storage":"-58...185 °F (-50...85 °C)","Ambient air temperature for operation":"-13...158 °F (-25...70 °C)","[Uimp] rated impulse withstand voltage":"8 kV IEC 60947-2","[Ith] conventional free air thermal current":"115 A IEC 60947-4-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$935.00","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/aab7391e2e669fad4488b1127bc29d53.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/GV4P115N/alternatives.json"},"ai":{"faq":[{"question":"What is GV4P115N's listed color?","answer":"Gray RAL 7016."},{"question":"What is GV4P115N's listed depth?","answer":"6.5 in (165 mm)."},{"question":"What compliance documentation does this brand provide for GV4P115N?","answer":"The GV4P115N is certified to CSA C22.2 No 60947-4-1, UL 60947-4-1, and EN/IEC 60947-4-1 and 60947-2."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV4P115N","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV4P115N when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}