{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV4P115N6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV4P115N6","canonicalUrl":"https://aoctrl.com/schneider/GV4P115N6","factsUrl":"https://aoctrl.com/api/mcp/products/GV4P115N6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider TeSys GV4 series, motor circuit breaker, GV4P115N6, 115 A, 3-pole, electronic thermal-magnetic, 100 kA Icu at 240 V, IP40, Gray RAL 7016.","salesMarkdown":"The GV4P115N6 is a 3-pole motor circuit breaker from Schneider's TeSys GV4 range, rated 115 A line current and built for motor protection under IEC and UL standards. It uses an electronic thermal-magnetic trip unit that combines adjustable overload protection with a fixed magnetic trip of 1955 A, so it clears a bolted fault fast while letting inrush ride through cleanly. ## Where it sits in a panel At 165 mm deep, 81 mm wide, and 155 mm tall, it fits a standard 3-pole breaker footprint in the TeSys Deca frame. The connection pitch is 27 mm without spreaders, 35 mm with, and the lugs accept ring terminals up to 95 mm². Mount it in any orientation, but pollution degree 3 means it's fine for a typical control panel environment — just don't drop it into a washdown zone without an extra enclosure; the IP40 front keeps fingers off terminals but won't stop hose spray. ## Electrical performance that matters The breaking capacity drops with voltage — that's normal, but the numbers here are worth noting because they cover the common industrial bus voltages in one device: 100 kA Icu at 240 V AC (IEC), 50 kA at 415 V, and 35 kA under UL at 480Y/277 V. That last figure is the one most US plants will care about; it exceeds the typical 25 kA fault duty on a 480 V MCC bucket.","metaTitle":"Schneider GV4P115N6 TeSys GV4 Motor Circuit Breaker, 115 A","metaDescription":"Schneider TeSys GV4P115N6 motor circuit breaker, 115 A rated current, 3-pole, electronic thermal-magnetic trip, 35 kA at 480Y/277 V UL. Active production, sourced to RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Gray RAL 7016)","Depth":"6.5 in (165 mm)","Range":"TeSys Deca","Width":"3.2 in (81 mm)","Height":"6.1 in (155 mm)","Category":"US10I1122365","Standards":"CSA C22.2 No 60947-4-1 UL 60947-4-1 EN/IEC 60947-4-1 EN/IEC 60947-2","Rated duty":"Continuous IEC 60947-4-1","Control Type":"Rotary handle","Product name":"TeSys GV4","Motor power kW":"37 kW 400...415 V AC 50/60 Hz 45 kW 400...415 V AC 50/60 Hz 55 kW 400...415 V AC 50/60 Hz 45 kW 500 V AC 50/60 Hz 55 kW 500 V AC 50/60 Hz 75 kW 500 V AC 50/60 Hz 75 kW 660...690 V AC 50/60 Hz 90 kW 660...690 V AC 50/60 Hz 110 kW 660...690 V AC 50/60 Hz","Fire resistance":"1760 °F (960 °C) IEC 60695-2-11","lifecycle_stage":"current","Connection pitch":"1.06 in (27 mm) without spreaders 1.4 in (35 mm) with spreaders","Pollution degree":"3","Range of Product":"TeSys GV4","Breaking capacity":"100 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 50 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 50 kA Icu 440 V AC 50/60 Hz IEC 60947-2 15 kA Icu 525 V AC 50/60 Hz IEC 60947-2 65 kA 208Y/120 V AC 50/60 Hz UL 60947 65 kA 240 V AC 50/60 Hz UL 60947 35 kA 480Y/277 V AC 50/60 Hz UL 60947 8 kA Icu 660...690 V AC 50/60 Hz IEC 60947-2 25 kA Icu 500 V AC 50/60 Hz IEC 60947-2 18 kA 600Y/347 V AC 50/60 Hz UL 60947","Device short name":"GV4P","Poles description":"3P","Tightening torque":"79.7 lbf.in (9 N.m) 0.02...0.1 in² (16...95 mm²) 44.3 lbf.in (5 N.m) 0.002...0.02 in² (1.5...10 mm²)","Climatic withstand":"IACS E10","Device Application":"Motor protection","Line Rated Current":"115 A","Operating altitude":"5000 m","Operating position":"Any position","Trip unit technology":"Electronic Thermal-magnetic","Utilisation category":"Category A IEC 60947-2 AC-3 IEC 60947-4-1","Electrical durability":"10000 cycles AC-3 440 V In/2 5000 cycles AC-3 440 V In","Mechanical durability":"40000 cycles","Mechanical robustness":"Vibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 Vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 Shocks 15 gn 11 ms IEC 60068-2-27","Nbr. of units in pkg.":"1","Maximum Operating Rate":"25 cyc/h","Connections - terminals":"Lugs-ring terminals","IK degree of protection":"IK07 IEC 62262","IP degree of protection":"IP40 IEC 60529","Magnetic tripping current":"1955 A","Phase failure sensitivity":"Yes IEC 60947-4-1","Product or Component Type":"Motor circuit breaker","Suitability for isolation":"Yes IEC 60947-1","Power dissipation per pole":"4.6 W","[Ui] rated insulation voltage":"800 V AC 50/60 Hz IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz IEC 60947-2","Ambient Air Temperature for Storage":"-58...185 °F (-50...85 °C)","Ambient air temperature for operation":"-13...158 °F (-25...70 °C)","[Uimp] rated impulse withstand voltage":"8 kV IEC 60947-2","[Ith] conventional free air thermal current":"115 A IEC 60947-4-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$990.00","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/aab7391e2e669fad4488b1127bc29d53.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/GV4P115N6/alternatives.json"},"ai":{"faq":[{"question":"What is the color of the GV4P115N6?","answer":"The enclosure is finished in gray RAL 7016, per the specification."},{"question":"What is the depth of the GV4P115N6?","answer":"Depth is 165 mm (6.5 in), which is the front-to-back dimension including the rotary handle mechanism."},{"question":"What compliance standards does the GV4P115N6 meet?","answer":"It is certified to CSA C22.2 No 60947-4-1, UL 60947-4-1, EN/IEC 60947-4-1, and EN/IEC 60947-2. It also carries an IK07 impact rating and IP40 ingress protection, and passed glow-wire testing at 960 °C per IEC 60695-2-11."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV4P115N6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV4P115N6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}