{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV4P50N6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV4P50N6","canonicalUrl":"https://aoctrl.com/schneider/GV4P50N6","factsUrl":"https://aoctrl.com/api/mcp/products/GV4P50N6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca GV4P50N6 motor circuit breaker, 3-pole, 50 A rated line current, electronic thermal-magnetic trip, 100 kA breaking capacity at 240 V AC, IP40, gray RAL 7016.","salesMarkdown":"## Breaking capacity that covers the fault-current map The GV4P50N6: At 240 V AC the Icu is 100 kA per IEC 60947-2, dropping to 50 kA at 415 V and 25 kA at 500 V. Under UL 60947 the 480Y/277 V rating is 35 kA. These are not theoretical maximums — they are the tested interrupting ratings that let you coordinate downstream without cascading failure. The 50 A line current coupled with an 850 A magnetic trip threshold means the short-circuit release is set at 17× In, which sits above motor inrush but below the fault current the supply can deliver. That selectivity window is what keeps a single motor fault from taking out the whole panel. ## AC-3 motor duty and thermal budget Rated utilisation category AC-3 per IEC 60947-4-1 — this is the standard for squirrel-cage motors with starting currents up to 8× In. The GV4P50N6 covers 11 kW at 400 V and up to 45 kW at 690 V, which brackets the common IEC motor frame sizes from 132 to 225. Power dissipation is 4.6 W per pole. In a closed panel with multiple breakers ganged, that 13.8 W three-phase heat adds up — the IP40 enclosure assumes free air, so derate the grouping factor if you pack them tighter than the 27 mm pole pitch without spreaders. Dimensions are 3.2 in wide × 6.1 in tall × 6.5 in deep (81 × 155 × 165 mm). The 27 mm pole pitch matches the standard TeSys Deca busbar grid; with spreaders it opens to 35 mm for larger cable lugs. Terminals accept lugs or ring terminals: the main circuit takes 16–95 mm² at 9 N·m, the control circuit 1.5–10 mm² at 5 N·m. That covers both the motor feeder and the control wiring in one terminal block. ## Approvals and compliance for global panels The fire-resistance glow-wire test passes at 960 °C per IEC 60695-2-11. Pollution degree 3 means it is rated for the conductive-dust environment inside a typical industrial enclosure.","metaTitle":"Schneider GV4P50N6 Motor Circuit Breaker, 50 A, TeSys Deca","metaDescription":"GV4P50N6 Schneider TeSys Deca motor circuit breaker, 50 A rated current, 100 kA breaking capacity at 240 V. Active production, sourced per RFQ. UL/CSA/IEC.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Gray RAL 7016)","Depth":"6.5 in (165 mm)","Width":"3.2 in (81 mm)","Height":"6.1 in (155 mm)","Voltage":"690 V AC 50/60 Hz IEC 60947-2","IP Rating":"IP40","Application":"Motor protection","Control Type":"Rotary handle","Product Status":"Active","Terminal Pitch":"1.06 in (27 mm) without spreaders 1.4 in (35 mm) with spreaders","Trip Unit Type":"Electronic Thermal-magnetic","Pollution Degree":"3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Insulation Voltage Ui":"800 V AC 50/60 Hz IEC 60947-2","Operating Position":"Any position","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-58...185 °F (-50...85 °C)","Utilization Category":"Category A IEC 60947-2 AC-3 IEC 60947-4-1","Electrical Life Cycles":"20000 cycles AC-3 440 V In/2 10000 cycles AC-3 440 V In","Mechanical Life Cycles":"40000 cycles","Main Product Or Component Type":"Motor circuit breaker","Ambient Air Temperature Operation":"-13...158 °F (-25...70 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,031.03","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/ie/en/product/GV4P50N6/motor-circuit-breaker-tesys-gv4-3p-50a-icu-50ka-thermal-magnetic-lugs-terminals/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV4P50N6/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV4P50N6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV4P50N6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}