{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV4P80N","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV4P80N","canonicalUrl":"https://aoctrl.com/schneider/GV4P80N","factsUrl":"https://aoctrl.com/api/mcp/products/GV4P80N","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca GV4P80N, 3-pole motor circuit breaker, 80 A rated, 100 kA breaking capacity at 240 V AC, gray RAL 7016.","salesMarkdown":"The GV4P80N is a 3-pole motor circuit breaker from the TeSys Deca range, rated 80 A continuous and listed as current production. The 100 kA breaking capacity at 240 V AC covers high-fault panels; at 480Y/277 V it still delivers 35 kA under UL 60947. ## Trip and protection logic Trip technology combines thermal-magnetic overload elements with an electronic magnetic adjustment. The magnetic trip is set at 1360 A, and phase failure sensitivity per IEC 60947-4-1 is built in. Lifecycle stage is current — this is the active variant in the GV4P series. No official successor listed, so the GV4P80N is the part to specify for new BOM lines or replacement of failed units. We can quote firm lead times against an RFQ. ## Mounting and wiring envelope Dimensions are 6.1 x 3.2 x 6.5 in (155 x 81 x 165 mm), IP40 front face with IK07 impact resistance. EverLink BTR screw terminals on the line side accept 1.5–70 mm² solid or 1.5–50 mm² flexible; load side terminals accept up to 95 mm² solid or 70 mm² flexible. Tightening torques are 79.7 lbf·in (9 N·m) for the main power terminals. The device can be operated in any position. ## Durability and environment Mechanical durability is 40,000 cycles; electrical durability under AC-3 at 440 V is 14,000 cycles at In/2 and 7,000 cycles at In. Maximum operating rate is 25 cycles per hour. The unit withstands vibration per IEC 60068-2-6 (0.7 gn, 13.2–100 Hz) and shock 15 gn for 11 ms. Climatic withstand is IACS, and pollution degree 3 applies.","metaTitle":"Schneider GV4P80N Motor Circuit Breaker, 80A, 100kA","metaDescription":"Schneider TeSys GV4P80N 3-pole motor circuit breaker, 80 A rated current, 100 kA breaking capacity at 240 V AC. Current production. Thermal-magnetic/electronic trip. RFQ to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Gray RAL 7016)","Depth":"6.5 in (165 mm)","Range":"TeSys Deca","Width":"3.2 in (81 mm)","Height":"6.1 in (155 mm)","Category":"US10I1122365","Standards":"CSA C22.2 No 60947-4-1 UL 60947-4-1 EN/IEC 60947-4-1 EN/IEC 60947-2","Rated duty":"Continuous IEC 60947-4-1","Control Type":"Rotary handle","Product name":"TeSys GV4","Motor power kW":"37 kW 400...415 V AC 50/60 Hz 45 kW 500 V AC 50/60 Hz 22 kW 400...415 V AC 50/60 Hz 30 kW 500 V AC 50/60 Hz 37 kW 660...690 V AC 50/60 Hz 45 kW 660...690 V AC 50/60 Hz 55 kW 660...690 V AC 50/60 Hz 30 kW 400...415 V AC 50/60 Hz 37 kW 500 V AC 50/60 Hz","Fire resistance":"1760 °F (960 °C) IEC 60695-2-11","lifecycle_stage":"current","Pollution degree":"3","Range of Product":"TeSys GV4","Breaking capacity":"100 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 50 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 50 kA Icu 440 V AC 50/60 Hz IEC 60947-2 15 kA Icu 525 V AC 50/60 Hz IEC 60947-2 65 kA 208Y/120 V AC 50/60 Hz UL 60947 65 kA 240 V AC 50/60 Hz UL 60947 35 kA 480Y/277 V AC 50/60 Hz UL 60947 8 kA Icu 660...690 V AC 50/60 Hz IEC 60947-2 25 kA Icu 500 V AC 50/60 Hz IEC 60947-2 18 kA 600Y/347 V AC 50/60 Hz UL 60947","Device short name":"GV4P","Poles description":"3P","Tightening torque":"79.7 lbf.in (9 N.m) 0.02...0.1 in² (16...95 mm²) 44.3 lbf.in (5 N.m) 0.002...0.02 in² (1.5...10 mm²)","Climatic withstand":"IACS E10","Device Application":"Motor protection","Line Rated Current":"80 A","Operating altitude":"5000 m","Operating position":"Any position","Trip unit technology":"Thermal-magnetic Electronic","Utilisation category":"Category A IEC 60947-2 AC-3 IEC 60947-4-1","Electrical durability":"14000 cycles AC-3 440 V In/2 7000 cycles AC-3 440 V In","Mechanical durability":"40000 cycles","Mechanical robustness":"Vibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 Vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 Shocks 15 gn 11 ms IEC 60068-2-27","Nbr. of units in pkg.":"1","Maximum Operating Rate":"25 cyc/h","Connections - terminals":"EverLink BTR screw connectors top) 1 0.002...0.1 in² (1.5...70 mm²) - solid EverLink BTR screw connectors top) 1 0.002...0.08 in² (1.5...50 mm²) - flexible EverLink BTR screw connectors bottom) 1 0.004...0.1 in² (2.5...95 mm²) - solid EverLink BTR screw connectors bottom) 1 0.004...0.1 in² (2.5...70 mm²) - flexible","IK degree of protection":"IK07 IEC 62262","IP degree of protection":"IP40 IEC 60529","Magnetic tripping current":"1360 A","Phase failure sensitivity":"Yes IEC 60947-4-1","Product or Component Type":"Motor circuit breaker","Suitability for isolation":"Yes IEC 60947-1","Power dissipation per pole":"4.6 W","[Ui] rated insulation voltage":"800 V AC 50/60 Hz IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz IEC 60947-2","Ambient Air Temperature for Storage":"-58...185 °F (-50...85 °C)","Ambient air temperature for operation":"-13...158 °F (-25...70 °C)","[Uimp] rated impulse withstand voltage":"8 kV IEC 60947-2","[Ith] conventional free air thermal current":"115 A IEC 60947-4-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$662.74 – $935.00","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/aab7391e2e669fad4488b1127bc29d53.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/GV4P80N/alternatives.json"},"ai":{"faq":[{"question":"What is the GV4P80N's color?","answer":"The enclosure is gray RAL 7016."},{"question":"What is the depth of the GV4P80N?","answer":"Depth is 6.5 inches (165 mm)."},{"question":"What compliance documentation is available for GV4P80N?","answer":"The breaker is certified to CSA C22.2 No 60947-4-1, UL 60947-4-1, EN/IEC 60947-4-1, and EN/IEC 60947-2."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV4P80N","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV4P80N when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}