{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV4P80N6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV4P80N6","canonicalUrl":"https://aoctrl.com/schneider/GV4P80N6","factsUrl":"https://aoctrl.com/api/mcp/products/GV4P80N6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys GV4 series, motor circuit breaker, GV4P80N6, 80 A, 3-pole, electronic thermal-magnetic, rotary handle, IP40.","salesMarkdown":"## TeSys GV4 motor circuit breaker – 80 A, 3-pole The Schneider Electric GV4P80N6 is a current-production 3-pole motor circuit breaker from the TeSys GV4 series, rated 80 A line current and 37 kW at 400-415 V AC. Rated for continuous duty per IEC 60947-4-1, it uses an electronic thermal-magnetic trip with a magnetic tripping current of 1360 A and supports motor protection in AC-3 utilization category. At 240 V AC, it breaks up to 100 kA (IEC 60947-2); worst-case at 690 V AC it still manages 8 kA, giving solid headroom for high-fault installations. Dimensions: 6.5 in (165 mm) depth, 3.2 in (81 mm) width, 6.1 in (155 mm) height – panel-mount footprint suits standard motor starter layouts. IP40 enclosure keeps out dust, and IK07 impact resistance protects against accidental contact. Gray RAL 7016 finish is the typical TeSys Deca color. Lugs accept 16–95 mm² cable; tightening torque is 9 N.m for the main terminals. ## Production status and sourcing Meets UL 60947-4-1, CSA C22.2 No 60947-4-1, and EN/IEC 60947-2 and 60947-4-1. Compliance documentation (RoHS, REACH) is available from the manufacturer pack; we can provide the declaration on request.","metaTitle":"Schneider Electric GV4P80N6 Motor Circuit Breaker, 80A, 3P","metaDescription":"GV4P80N6 is an active current-production motor circuit breaker from Schneider's TeSys GV4 series. Rated 80 A, 37 kW at 400 V AC. 3-pole, electronic thermal-magnetic. Sourced to ord","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Gray RAL 7016)","Depth":"6.5 in (165 mm)","Range":"TeSys Deca","Width":"3.2 in (81 mm)","Height":"6.1 in (155 mm)","Category":"US10I1122365","Standards":"CSA C22.2 No 60947-4-1 UL 60947-4-1 EN/IEC 60947-4-1 EN/IEC 60947-2","Rated duty":"Continuous IEC 60947-4-1","Control Type":"Rotary handle","Product name":"TeSys GV4","Motor power kW":"37 kW 400...415 V AC 50/60 Hz 45 kW 500 V AC 50/60 Hz 22 kW 400...415 V AC 50/60 Hz 30 kW 500 V AC 50/60 Hz 37 kW 660...690 V AC 50/60 Hz 45 kW 660...690 V AC 50/60 Hz 55 kW 660...690 V AC 50/60 Hz 30 kW 400...415 V AC 50/60 Hz 37 kW 500 V AC 50/60 Hz","Fire resistance":"1760 °F (960 °C) IEC 60695-2-11","lifecycle_stage":"current","Connection pitch":"1.06 in (27 mm) without spreaders 1.4 in (35 mm) with spreaders","Pollution degree":"3","Range of Product":"TeSys GV4","Breaking capacity":"100 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 50 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 50 kA Icu 440 V AC 50/60 Hz IEC 60947-2 15 kA Icu 525 V AC 50/60 Hz IEC 60947-2 65 kA 208Y/120 V AC 50/60 Hz UL 60947 65 kA 240 V AC 50/60 Hz UL 60947 35 kA 480Y/277 V AC 50/60 Hz UL 60947 8 kA Icu 660...690 V AC 50/60 Hz IEC 60947-2 25 kA Icu 500 V AC 50/60 Hz IEC 60947-2 18 kA 600Y/347 V AC 50/60 Hz UL 60947","Device short name":"GV4P","Poles description":"3P","Tightening torque":"79.7 lbf.in (9 N.m) 0.02...0.1 in² (16...95 mm²) 44.3 lbf.in (5 N.m) 0.002...0.02 in² (1.5...10 mm²)","Climatic withstand":"IACS E10","Device Application":"Motor protection","Line Rated Current":"80 A","Operating altitude":"5000 m","Operating position":"Any position","Trip unit technology":"Electronic Thermal-magnetic","Utilisation category":"Category A IEC 60947-2 AC-3 IEC 60947-4-1","Electrical durability":"14000 cycles AC-3 440 V In/2 7000 cycles AC-3 440 V In","Mechanical durability":"40000 cycles","Mechanical robustness":"Vibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 Vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 Shocks 15 gn 11 ms IEC 60068-2-27","Nbr. of units in pkg.":"1","Maximum Operating Rate":"25 cyc/h","Connections - terminals":"Lugs-ring terminals","IK degree of protection":"IK07 IEC 62262","IP degree of protection":"IP40 IEC 60529","Magnetic tripping current":"1360 A","Phase failure sensitivity":"Yes IEC 60947-4-1","Product or Component Type":"Motor circuit breaker","Suitability for isolation":"Yes IEC 60947-1","Power dissipation per pole":"4.6 W","[Ui] rated insulation voltage":"800 V AC 50/60 Hz IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz IEC 60947-2","Ambient Air Temperature for Storage":"-58...185 °F (-50...85 °C)","Ambient air temperature for operation":"-13...158 °F (-25...70 °C)","[Uimp] rated impulse withstand voltage":"8 kV IEC 60947-2","[Ith] conventional free air thermal current":"115 A IEC 60947-4-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$111.76","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/aab7391e2e669fad4488b1127bc29d53.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/GV4P80N6/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation does GV4P80N6 have?","answer":"It complies with UL 60947-4-1, CSA C22.2 No 60947-4-1, and EN/IEC 60947-2 and 60947-4-1. RoHS and REACH declarations are available upon request."},{"question":"What is the color of GV4P80N6?","answer":"The enclosure is Gray RAL 7016, the standard TeSys Deca color."},{"question":"What is the depth of GV4P80N6?","answer":"The depth is 6.5 inches (165 mm)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV4P80N6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV4P80N6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}