{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV4PB03N","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV4PB03N","canonicalUrl":"https://aoctrl.com/schneider/GV4PB03N","factsUrl":"https://aoctrl.com/api/mcp/products/GV4PB03N","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca GV4PB03N, motor circuit breaker, 3.5 A rated current, 3 poles, thermal-magnetic electronic trip, UL 489 / IEC 60947-2/4-1.","salesMarkdown":"The Schneider GV4PB03N is a 3.5 A, 3-pole motor circuit breaker from the TeSys GV4 family (TeSys Deca range). It combines thermal-magnetic and electronic trip technology for motor protection in both UL and IEC panels. Rated operational voltage goes to 690 V AC and it carries a 65 kA SCCR at 240 V AC (UL 489) and 100 kA Icu at 220/240 V AC (IEC 60947-2). The case is Gray RAL 7016 with IP40 protection and IK07 impact resistance. ## Mounting and wiring integration Dimensions: 171 mm high, 81 mm wide, 116 mm deep. Accepts any mounting orientation. Top terminals accept 1.5–70 mm² rigid or 1.5–50 mm² flexible; bottom terminals accept 2.5–95 mm² rigid or 2.5–70 mm² flexible. EverLink BTR screw connectors – tighten to 9 N·m (79.7 lbf·in) for the main power terminals and 5 N·m for the control/tap terminals. Power dissipation per pole is 4.6 W. Rated for continuous duty, maximum operating rate is 25 cyc/h. Certified to UL 489, CSA C22.2 No 5, EN/IEC 60947-1/2/4-1. Fire resistance rated at 960 °C (1760 °F) per IEC 60695-2-11. Pollution degree 3. Climatic withstand per IACS. The product is suitable for isolation and meets phase failure sensitivity requirements.","metaTitle":"Schneider GV4PB03N TeSys Deca Motor Circuit Breaker, 3.5 A","metaDescription":"Schneider Electric GV4PB03N motor circuit breaker, 3.5 A, 3-pole, thermal-magnetic, 65 kA SCCR at 240 V UL. Active production. Gray RAL 7016. Order to RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Gray RAL 7016)","Depth":"4.6 in (116 mm)","Range":"TeSys Deca","Width":"3.2 in (81 mm)","Height":"6.7 in (171 mm)","Category":"US10I1122365","Standards":"EN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-4-1 UL 489 CSA C22.2 No 5","Rated duty":"Continuous IEC 60947-4-1","Control Type":"Toggle","Product name":"TeSys GV4 TeSys Deca","Fire resistance":"1760 °F (960 °C) IEC 60695-2-11","lifecycle_stage":"current","Pollution degree":"3","Range of Product":"TeSys GV4","Breaking capacity":"65 kA SCCR 240 V AC 60 Hz UL 489 35 kA SCCR 480Y/277 V AC 60 Hz UL 489 18 kA SCCR 600Y/347 V AC 60 Hz UL 489 100 kA Icu 220/240 V AC 50/60 Hz IEC 60947-2 50 kA Icu 380/415 V AC 50/60 Hz IEC 60947-2 50 kA Icu 440 V AC 50/60 Hz IEC 60947-2 25 kA Icu 500 V AC 50/60 Hz IEC 60947-2 15 kA Icu 525 V AC 50/60 Hz IEC 60947-2 8 kA Icu 660/690 V AC 50/60 Hz IEC 60947-2","Device short name":"GV4PB","Poles description":"3P","Tightening torque":"79.7 lbf.in (9 N.m) 0.02...0.1 in² (16...95 mm²) 44.3 lbf.in (5 N.m) 0.002...0.02 in² (1.5...10 mm²)","Climatic withstand":"IACS E10","Device Application":"Motor protection","Line Rated Current":"3.5 A","Operating altitude":"5000 m","Operating position":"Any position","Trip unit technology":"Thermal-magnetic Electronic","Utilisation category":"Category A IEC 60947-2 AC-3 IEC 60947-4-1","Electrical durability":"40000 cycles AC-3 440 V In/2 40000 cycles AC-3 440 V In","Mechanical durability":"40000 cycles","Mechanical robustness":"Vibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 Vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 Shocks 15 gn 11 ms IEC 60068-2-27","Nbr. of units in pkg.":"1","Maximum Operating Rate":"25 cyc/h","Connections - terminals":"EverLink BTR screw connectors top) 1 0.002...0.1 in² (1.5...70 mm²) - rigid EverLink BTR screw connectors top) 1 0.002...0.08 in² (1.5...50 mm²) - flexible EverLink BTR screw connectors bottom) 1 0.004...0.1 in² (2.5...95 mm²) - rigid EverLink BTR screw connectors bottom) 1 0.004...0.1 in² (2.5...70 mm²) - flexible","IK degree of protection":"IK07 IEC 62262","IP degree of protection":"IP40 IEC 60529","Magnetic tripping current":"60 A","Phase failure sensitivity":"Yes IEC 60947-4-1","Product or Component Type":"Motor circuit breaker","Suitability for isolation":"Yes IEC 60947-1","Power dissipation per pole":"4.6 W","[Ui] rated insulation voltage":"800 V AC 50/60 Hz IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz IEC 60947-2 600Y/347 V AC 60 Hz UL 489","Ambient Air Temperature for Storage":"-58...185 °F (-50...85 °C)","Ambient air temperature for operation":"-13...158 °F (-25...70 °C)","[Uimp] rated impulse withstand voltage":"8 kV IEC 60947-2","[Ith] conventional free air thermal current":"115 A IEC 60947-4-1","[Ics] rated service short-circuit breaking capacity":"100 % 220/240 V AC 50/60 Hz IEC 60947-2 100 % 380/415 V AC 50/60 Hz IEC 60947-2 100 % 440 V AC 50/60 Hz IEC 60947-2 100 % 500 V AC 50/60 Hz IEC 60947-2 100 % 525 V AC 50/60 Hz IEC 60947-2 25 % 660/690 V AC 50/60 Hz IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$545.00","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a05a82a3ae2300646129ea792a9a98ec.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/GV4PB03N/alternatives.json"},"ai":{"faq":[{"question":"What is the color of the GV4PB03N?","answer":"The breaker housing is Gray RAL 7016."},{"question":"What is the depth of the GV4PB03N?","answer":"Depth is 4.6 inches (116 mm)."},{"question":"What compliance standards does the GV4PB03N meet?","answer":"It complies with UL 489, CSA C22.2 No 5, EN/IEC 60947-1, EN/IEC 60947-2, and EN/IEC 60947-4-1. Also meets fire resistance at 960 °C and pollution degree 3."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV4PB03N","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV4PB03N when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}