{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV4PB03S","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV4PB03S","canonicalUrl":"https://aoctrl.com/schneider/GV4PB03S","factsUrl":"https://aoctrl.com/api/mcp/products/GV4PB03S","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca, Motor circuit breaker, GV4PB03S, 3.5 A, 3P, Gray RAL 7016, 100 kA SCCR 240 V AC UL, 120 kA Icu 220/240 V IEC.","salesMarkdown":"The GV4PB03S is a TeSys Deca motor circuit breaker, rated 3.5 A continuous on a 3-pole frame. It packs a 100 kA SCCR at 240 V AC under UL 489, with a symmetrical breaking capacity up to 120 kA Icu at 220/240 V under IEC 60947-2. That places it in a class above typical 3.5 A motor protectors—designed for panels where fault current levels would otherwise force a larger frame or upstream fuse coordination. ## Key ratings The electronic thermal-magnetic trip unit offers both overload and short-circuit protection, with a magnetic trip threshold set at 60 A. The 25 cycles per hour maximum operating rate fits standard motor starting duty. For panel builders, the EverLink screw terminals accept up to 95 mm² (rigid) on the bottom, and the IP40 front face with IK07 impact resistance suits enclosed installations. Current production, with a broad base of international approvals—UL 489, CSA C22.2 No 5, and EN/IEC 60947-4-1—that smooth regional acceptance without custom variants. Sourced to order through standard distribution; supply-demand balance is stable for this TeSys Deca platform.","metaTitle":"Schneider Electric GV4PB03S Motor Circuit Breaker, 3.5 A, 3P","metaDescription":"TeSys Deca motor circuit breaker, 3.5 A, 3-pole. High SCCR up to 100 kA (240 V UL). Current production, multi-standard approvals. Source to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Gray RAL 7016)","Depth":"4.6 in (116 mm)","Range":"TeSys Deca","Width":"3.2 in (81 mm)","Height":"6.7 in (171 mm)","Category":"US10I1122365","Standards":"EN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-4-1 UL 489 CSA C22.2 No 5","Rated duty":"Continuous IEC 60947-4-1","Control Type":"Toggle","Product name":"TeSys GV4","Fire resistance":"1760 °F (960 °C) IEC 60695-2-11","lifecycle_stage":"current","Pollution degree":"3","Range of Product":"TeSys GV4","Breaking capacity":"100 kA SCCR 240 V AC 60 Hz UL 489 65 kA SCCR 480Y/277 V AC 60 Hz UL 489 25 kA SCCR 600Y/347 V AC 60 Hz UL 489 120 kA Icu 220/240 V AC 50/60 Hz IEC 60947-2 100 kA Icu 380/415 V AC 50/60 Hz IEC 60947-2 70 kA Icu 440 V AC 50/60 Hz IEC 60947-2 30 kA Icu 500 V AC 50/60 Hz IEC 60947-2 18 kA Icu 525 V AC 50/60 Hz IEC 60947-2 10 kA Icu 660/690 V AC 50/60 Hz IEC 60947-2","Device short name":"GV4PB","Poles description":"3P","Tightening torque":"79.7 lbf.in (9 N.m) 0.02...0.1 in² (16...95 mm²) 44.3 lbf.in (5 N.m) 0.002...0.02 in² (1.5...10 mm²)","Climatic withstand":"IACS E10","Device Application":"Motor protection","Line Rated Current":"3.5 A","Operating altitude":"5000 m","Operating position":"Any position","Trip unit technology":"Electronic Thermal-magnetic","Utilisation category":"Category A IEC 60947-2 AC-3 IEC 60947-4-1","Electrical durability":"40000 cycles AC-3 440 V In/2 40000 cycles AC-3 440 V In","Mechanical durability":"40000 cycles","Mechanical robustness":"Vibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 Vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 Shocks 15 gn 11 ms IEC 60068-2-27","Nbr. of units in pkg.":"1","Maximum Operating Rate":"25 cyc/h","Connections - terminals":"EverLink BTR screw connectors top) 1 0.002...0.1 in² (1.5...70 mm²) - rigid EverLink BTR screw connectors top) 1 0.002...0.08 in² (1.5...50 mm²) - flexible EverLink BTR screw connectors bottom) 1 0.004...0.1 in² (2.5...95 mm²) - rigid EverLink BTR screw connectors bottom) 1 0.004...0.1 in² (2.5...70 mm²) - flexible","IK degree of protection":"IK07 IEC 62262","IP degree of protection":"IP40 IEC 60529","Magnetic tripping current":"60 A","Phase failure sensitivity":"Yes IEC 60947-4-1","Product or Component Type":"Motor circuit breaker","Suitability for isolation":"Yes IEC 60947-1","Power dissipation per pole":"4.6 W","[Ui] rated insulation voltage":"800 V AC 50/60 Hz IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz IEC 60947-2 600Y/347 V AC 60 Hz UL 489","Ambient Air Temperature for Storage":"-58...185 °F (-50...85 °C)","Ambient air temperature for operation":"-13...158 °F (-25...70 °C)","[Uimp] rated impulse withstand voltage":"8 kV IEC 60947-2","[Ith] conventional free air thermal current":"115 A IEC 60947-4-1","[Ics] rated service short-circuit breaking capacity":"100 % 220/240 V AC 50/60 Hz IEC 60947-2 100 % 380/415 V AC 50/60 Hz IEC 60947-2 100 % 440 V AC 50/60 Hz IEC 60947-2 100 % 500 V AC 50/60 Hz IEC 60947-2 100 % 525 V AC 50/60 Hz IEC 60947-2 25 % 660/690 V AC 50/60 Hz IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a05a82a3ae2300646129ea792a9a98ec.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/GV4PB03S/alternatives.json"},"ai":{"faq":[{"question":"What is GV4PB03S's listed color?","answer":"Gray RAL 7016."},{"question":"What is GV4PB03S's listed depth?","answer":"4.6 inches (116 mm)."},{"question":"What compliance documentation does this brand provide for GV4PB03S?","answer":"The breaker is designed to EN/IEC 60947-1, EN/IEC 60947-2, EN/IEC 60947-4-1, UL 489, and CSA C22.2 No 5, and has a fire resistance rating of 1760 °F (960 °C) per IEC 60695-2-11."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV4PB03S","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV4PB03S when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}