{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV4PB115N","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV4PB115N","canonicalUrl":"https://aoctrl.com/schneider/GV4PB115N","factsUrl":"https://aoctrl.com/api/mcp/products/GV4PB115N","rawCanonicalId":null},"summary":{"shortDescription":"Schneider TeSys GV4, Motor circuit breaker, GV4PB115N, 115 A, 3-pole, 65 kA SCCR UL, electronic thermal-magnetic trip.","salesMarkdown":"## What the GV4PB115N Is and Does The GV4PB115N is a 115 A, 3-pole motor circuit breaker in the TeSys GV4 range. It provides combined overload and short-circuit protection via an electronic thermal-magnetic trip unit with fixed magnetic tripping at 1955 A. The utilization category AC-3 matches motor switching duty. Breaking capacity reaches 65 kA SCCR at 240 V AC (UL 489) and 100 kA Icu at 220/240 V AC (IEC), allowing direct installation on high-fault-capacity industrial panels without upstream fusing in many cases. The 115 A line-rated current sets the continuous load limit. The magnetic trip is fixed at 1955 A. EverLink screw terminals accept up to 95 mm² rigid bottom connection and 70 mm² top. Torque settings are 44.3 lbf·in for smaller conductors and 79.7 lbf·in for the main power circuit. With IP40 enclosure and IK07 impact resistance, the unit is suitable for clean industrial cabinet environments. Pollution degree 3 confirms operation in typical factory atmospheres. Dual-certified under UL 489 and CSA C22.2 No 5 for North America, plus IEC 60947-1/-2/-4-1 for global panels. Fire resistance tested at 960 °C (IEC 60695-2-11).","metaTitle":"Schneider GV4PB115N TeSys GV4 115A 3P Motor Circuit Breaker","metaDescription":"Active motor circuit breaker, 115 A, 3-pole. TeSys GV4. UL 489, IEC. 65 kA SCCR. Gray RAL 7016. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Gray RAL 7016)","Depth":"4.6 in (116 mm)","Range":"TeSys Deca","Width":"3.2 in (81 mm)","Height":"6.7 in (171 mm)","Category":"US10I1122365","Standards":"EN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-4-1 UL 489 CSA C22.2 No 5","Rated duty":"Continuous IEC 60947-4-1","Control Type":"Toggle","Product name":"TeSys GV4","Fire resistance":"1760 °F (960 °C) IEC 60695-2-11","lifecycle_stage":"current","Pollution degree":"3","Range of Product":"TeSys GV4","Breaking capacity":"65 kA SCCR 240 V AC 60 Hz UL 489 35 kA SCCR 480Y/277 V AC 60 Hz UL 489 18 kA SCCR 600Y/347 V AC 60 Hz UL 489 100 kA Icu 220/240 V AC 50/60 Hz IEC 60947-2 50 kA Icu 380/415 V AC 50/60 Hz IEC 60947-2 50 kA Icu 440 V AC 50/60 Hz IEC 60947-2 25 kA Icu 500 V AC 50/60 Hz IEC 60947-2 15 kA Icu 525 V AC 50/60 Hz IEC 60947-2 8 kA Icu 660/690 V AC 50/60 Hz IEC 60947-2","Device short name":"GV4PB","Poles description":"3P","Tightening torque":"79.7 lbf.in (9 N.m) 0.02...0.1 in² (16...95 mm²) 44.3 lbf.in (5 N.m) 0.002...0.02 in² (1.5...10 mm²)","Climatic withstand":"IACS E10","Device Application":"Motor protection","Line Rated Current":"115 A","Operating altitude":"5000 m","Operating position":"Any position","Trip unit technology":"Electronic Thermal-magnetic","Utilisation category":"Category A IEC 60947-2 AC-3 IEC 60947-4-1","Electrical durability":"10000 cycles AC-3 440 V In/2 5000 cycles AC-3 440 V In","Mechanical durability":"40000 cycles","Mechanical robustness":"Vibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 Vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 Shocks 15 gn 11 ms IEC 60068-2-27","Nbr. of units in pkg.":"1","Maximum Operating Rate":"25 cyc/h","Connections - terminals":"EverLink BTR screw connectors top) 1 0.002...0.1 in² (1.5...70 mm²) - rigid EverLink BTR screw connectors top) 1 0.002...0.08 in² (1.5...50 mm²) - flexible EverLink BTR screw connectors bottom) 1 0.004...0.1 in² (2.5...95 mm²) - rigid EverLink BTR screw connectors bottom) 1 0.004...0.1 in² (2.5...70 mm²) - flexible","IK degree of protection":"IK07 IEC 62262","IP degree of protection":"IP40 IEC 60529","Magnetic tripping current":"1955 A","Phase failure sensitivity":"Yes IEC 60947-4-1","Product or Component Type":"Motor circuit breaker","Suitability for isolation":"Yes IEC 60947-1","Power dissipation per pole":"4.6 W","[Ui] rated insulation voltage":"800 V AC 50/60 Hz IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz IEC 60947-2 600Y/347 V AC 60 Hz UL 489","Ambient Air Temperature for Storage":"-58...185 °F (-50...85 °C)","Ambient air temperature for operation":"-13...158 °F (-25...70 °C)","[Uimp] rated impulse withstand voltage":"8 kV IEC 60947-2","[Ith] conventional free air thermal current":"115 A IEC 60947-4-1","[Ics] rated service short-circuit breaking capacity":"100 % 220/240 V AC 50/60 Hz IEC 60947-2 100 % 380/415 V AC 50/60 Hz IEC 60947-2 100 % 440 V AC 50/60 Hz IEC 60947-2 100 % 500 V AC 50/60 Hz IEC 60947-2 100 % 525 V AC 50/60 Hz IEC 60947-2 25 % 660/690 V AC 50/60 Hz IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$217.17 – $610.00","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/4e4a39c769e275c6627b9e82f2951eb7.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/GV4PB115N/alternatives.json"},"ai":{"faq":[{"question":"What is the color of the GV4PB115N?","answer":"Gray RAL 7016."},{"question":"What is the depth of the GV4PB115N?","answer":"4.6 inches (116 mm)."},{"question":"What compliance certifications does the GV4PB115N carry?","answer":"It carries UL 489, CSA C22.2 No 5, and IEC 60947-1/-2/-4-1 certifications."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV4PB115N","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV4PB115N when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}