{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV4PB80B","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV4PB80B","canonicalUrl":"https://aoctrl.com/schneider/GV4PB80B","factsUrl":"https://aoctrl.com/api/mcp/products/GV4PB80B","rawCanonicalId":null},"summary":{"shortDescription":"TeSys GV4 motor circuit breaker, 80 A, 3-pole, electronic thermal-magnetic trip, GV4PB80B.","salesMarkdown":"The GV4PB80B is a TeSys GV4 motor circuit breaker — 80 A, three poles, electronic thermal-magnetic trip. It's the part you slot into a TeSys Deca panel for motor branch protection. Rated for continuous duty (IEC 60947-4-1), it sits alongside the rest of the GV4 family on the same frame. Breaking capacity is where this breaker earns its keep. Under UL 489: 35 kA at 240 V AC, 18 kA at 480Y/277 V, 14 kA at 600Y/347 V. Under IEC 60947-2: Icu of 50 kA at 220/240 V, stepping down to 10 kA at 500 V. That covers most industrial motor panels without extra upstream fusing. The magnetic trip is fixed at 1360 A — not adjustable, so coordination with the upstream overcurrent device needs to be checked at the board level. Phase failure sensitivity per IEC 60947-4-1 is included; the breaker will drop the motor on a lost phase. Power dissipation per pole is 4.6 W — that's a data point for panel thermal calculations. Mounting is any position; the housing is IP40 (fingers) and IK07 (impact). Pollution degree 3. Operating altitude goes to 5000 m — fine for most plant floors and elevated installations. The EverLink BTR screw terminals accept up to 95 mm² rigid on the bottom, 70 mm² flexible on the top. Tightening torque is 9 N·m for the main conductors, 5 N·m for the control wiring. Climatic withstand per IACS. If you're filling a BOM line for a motor control center or a TeSys Deca panel, this order code fits the slot. Send an RFQ with your target quantity and delivery window; we'll quote against the open manufacturing line. No need to source through brokers — this one is still a catalog item.","metaTitle":"TeSys GV4PB80B Motor Circuit Breaker, 80 A, 3-Pole","metaDescription":"TeSys GV4 motor circuit breaker, 80 A, 3-pole, electronic thermal-magnetic trip. Active production. UL 489 / IEC 60947-2. 35 kA SCCR at 240 V. Enquire via RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Gray RAL 7016)","Depth":"4.6 in (116 mm)","Range":"TeSys Deca","Width":"3.2 in (81 mm)","Height":"6.7 in (171 mm)","Category":"US10I1122365","Standards":"EN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-4-1 UL 489 CSA C22.2 No 5","Rated duty":"Continuous IEC 60947-4-1","Control Type":"Toggle","Product name":"TeSys GV4","Fire resistance":"1760 °F (960 °C) IEC 60695-2-11","lifecycle_stage":"current","Pollution degree":"3","Range of Product":"TeSys GV4","Breaking capacity":"35 kA SCCR 240 V AC 60 Hz UL 489 18 kA SCCR 480Y/277 V AC 60 Hz UL 489 14 kA SCCR 600Y/347 V AC 60 Hz UL 489 50 kA Icu 220/240 V AC 50/60 Hz IEC 60947-2 25 kA Icu 380/415 V AC 50/60 Hz IEC 60947-2 20 kA Icu 440 V AC 50/60 Hz IEC 60947-2 10 kA Icu 500 V AC 50/60 Hz IEC 60947-2","Device short name":"GV4PB","Poles description":"3P","Tightening torque":"79.7 lbf.in (9 N.m) 0.02...0.1 in² (16...95 mm²) 44.3 lbf.in (5 N.m) 0.002...0.02 in² (1.5...10 mm²)","Climatic withstand":"IACS E10","Device Application":"Motor protection","Line Rated Current":"80 A","Operating altitude":"5000 m","Operating position":"Any position","Trip unit technology":"Electronic Thermal-magnetic","Utilisation category":"Category A IEC 60947-2 AC-3 IEC 60947-4-1","Electrical durability":"14000 cycles AC-3 440 V In/2 7000 cycles AC-3 440 V In","Mechanical durability":"40000 cycles","Mechanical robustness":"Vibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 Vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 Shocks 15 gn 11 ms IEC 60068-2-27","Nbr. of units in pkg.":"1","Maximum Operating Rate":"25 cyc/h","Connections - terminals":"EverLink BTR screw connectors top) 1 0.002...0.1 in² (1.5...70 mm²) - rigid EverLink BTR screw connectors top) 1 0.002...0.08 in² (1.5...50 mm²) - flexible EverLink BTR screw connectors bottom) 1 0.004...0.1 in² (2.5...95 mm²) - rigid EverLink BTR screw connectors bottom) 1 0.004...0.1 in² (2.5...70 mm²) - flexible","IK degree of protection":"IK07 IEC 62262","IP degree of protection":"IP40 IEC 60529","Magnetic tripping current":"1360 A","Phase failure sensitivity":"Yes IEC 60947-4-1","Product or Component Type":"Motor circuit breaker","Suitability for isolation":"Yes IEC 60947-1","Power dissipation per pole":"4.6 W","[Ui] rated insulation voltage":"800 V AC 50/60 Hz IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz IEC 60947-2 600Y/347 V AC 60 Hz UL 489","Ambient Air Temperature for Storage":"-58...185 °F (-50...85 °C)","Ambient air temperature for operation":"-13...158 °F (-25...70 °C)","[Uimp] rated impulse withstand voltage":"8 kV IEC 60947-2","[Ith] conventional free air thermal current":"115 A IEC 60947-4-1","[Ics] rated service short-circuit breaking capacity":"100 % 220/240 V AC 50/60 Hz IEC 60947-2 100 % 380/415 V AC 50/60 Hz IEC 60947-2 100 % 440 V AC 50/60 Hz IEC 60947-2 100 % 500 V AC 50/60 Hz IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$257.81 – $515.00","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9452d3fadf03721aed02d04f12e2005c.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/GV4PB80B/alternatives.json"},"ai":{"faq":[{"question":"What is GV4PB80B's listed color?","answer":"The color is Gray RAL 7016."},{"question":"What is GV4PB80B's depth?","answer":"The depth is 4.6 inches (116 mm)."},{"question":"What compliance documentation does this brand provide for GV4PB80B?","answer":"It is certified to UL 489, CSA C22.2 No 5, IEC 60947-1, IEC 60947-2, and IEC 60947-4-1. The product is also fire-resistant to 960 °C per IEC 60695-2-11."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV4PB80B","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV4PB80B when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}