{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV4PE02S","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV4PE02S","canonicalUrl":"https://aoctrl.com/schneider/GV4PE02S","factsUrl":"https://aoctrl.com/api/mcp/products/GV4PE02S","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys GV4PE02S motor circuit breaker, 2 A line rated current, 3 poles, electronic thermal-magnetic trip, Gray RAL 7016.","salesMarkdown":"The Schneider GV4PE02S is a TeSys Deca-series motor circuit breaker rated for 2 A continuous line current with three poles. It uses a combined electronic thermal-magnetic trip unit and is rated for motor protection under AC-3 utilization. It ships in Gray RAL 7016, measures 3.2\" wide × 6.1\" tall × 4.6\" deep, and mounts in any position. Dual-zone EverLink screw terminals handle top leads up to 70 mm² solid, bottom up to 95 mm². The 2 A rating governs the motor FLA it protects — pair it with a motor drawing up to that full-load current. Magnetic trip fires at 34 A, which covers start-up inrush without nuisance trips. Phase failure sensitivity means it will drop the load if one leg opens, which matters for three-phase motor protection. Rated continuous duty and pollution degree 3 suit industrial environments where dust and conductive deposits are expected. The IK07 impact rating and IP40 enclosure mean it can take a knock and keep out tools and fingers in a panel. The toggle control provides manual on/off; it isolates on the line side so you can safely work downstream. Maximum operating rate is 25 cycles per hour — fine for manual switching, not for high-speed cycling.","metaTitle":"Schneider TeSys GV4PE02S Motor Circuit Breaker, 2 A, 3 Pole","metaDescription":"Schneider TeSys GV4PE02S motor circuit breaker, 2 A rated, 3 poles, 100 kA breaking capacity at 240 V. Active production. UL/CSA/IEC compliant. Order today.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Color":"Gray RAL 7016)","Depth":"4.6 in (116 mm)","Range":"TeSys Deca","Width":"3.2 in (81 mm)","Height":"6.1 in (155 mm)","Category":"US10I1122365","Standards":"CSA C22.2 No 60947-4-1 UL 60947-4-1 EN/IEC 60947-4-1 EN/IEC 60947-2","Rated duty":"Continuous IEC 60947-4-1","Control Type":"Toggle","Product name":"TeSys GV4","Motor power kW":"0.25 kW 400...415 V AC 50/60 Hz 0.37 kW 400...415 V AC 50/60 Hz 0.55 kW 400...415 V AC 50/60 Hz 0.75 kW 400...415 V AC 50/60 Hz 0.37 kW 500 V AC 50/60 Hz 0.55 kW 500 V AC 50/60 Hz 0.75 kW 500 V AC 50/60 Hz 1.1 kW 500 V AC 50/60 Hz 0.55 kW 660...690 V AC 50/60 Hz 0.75 kW 660...690 V AC 50/60 Hz 1.1 kW 660...690 V AC 50/60 Hz 1.5 kW 660...690 V AC 50/60 Hz","Fire resistance":"1760 °F (960 °C) IEC 60695-2-11","lifecycle_stage":"current","Pollution degree":"3","Range of Product":"TeSys GV4","Breaking capacity":"120 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 100 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 70 kA Icu 440 V AC 50/60 Hz IEC 60947-2 30 kA Icu 500 V AC 50/60 Hz IEC 60947-2 18 kA Icu 525 V AC 50/60 Hz IEC 60947-2 100 kA 208Y/120 V AC 50/60 Hz UL 60947 100 kA 240 V AC 50/60 Hz UL 60947 65 kA 480Y/277 V AC 50/60 Hz UL 60947 10 kA Icu 660...690 V AC 50/60 Hz IEC 60947-2 25 kA 600Y/347 V AC 50/60 Hz UL 60947","Device short name":"GV4PE","Poles description":"3P","Tightening torque":"79.7 lbf.in (9 N.m) 0.02...0.1 in² (16...95 mm²) 44.3 lbf.in (5 N.m) 0.002...0.02 in² (1.5...10 mm²)","Climatic withstand":"IACS E10","Device Application":"Motor protection","Line Rated Current":"2 A","Operating altitude":"5000 m","Operating position":"Any position","Trip unit technology":"Electronic Thermal-magnetic","Utilisation category":"Category A IEC 60947-2 AC-3 IEC 60947-4-1","Electrical durability":"40000 cycles AC-3 440 V In/2 40000 cycles AC-3 440 V In","Mechanical durability":"40000 cycles","Mechanical robustness":"Vibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 Vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 Shocks 15 gn 11 ms IEC 60068-2-27","Nbr. of units in pkg.":"1","Maximum Operating Rate":"25 cyc/h","Connections - terminals":"EverLink BTR screw connectors top) 1 0.002...0.1 in² (1.5...70 mm²) - solid EverLink BTR screw connectors top) 1 0.002...0.08 in² (1.5...50 mm²) - flexible EverLink BTR screw connectors bottom) 1 0.004...0.1 in² (2.5...95 mm²) - solid EverLink BTR screw connectors bottom) 1 0.004...0.1 in² (2.5...70 mm²) - flexible","IK degree of protection":"IK07 IEC 62262","IP degree of protection":"IP40 IEC 60529","Magnetic tripping current":"34 A","Phase failure sensitivity":"Yes IEC 60947-4-1","Product or Component Type":"Motor circuit breaker","Suitability for isolation":"Yes IEC 60947-1","Power dissipation per pole":"4.6 W","[Ui] rated insulation voltage":"800 V AC 50/60 Hz IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz IEC 60947-2","Ambient Air Temperature for Storage":"-58...185 °F (-50...85 °C)","Ambient air temperature for operation":"-13...158 °F (-25...70 °C)","[Uimp] rated impulse withstand voltage":"8 kV IEC 60947-2","[Ith] conventional free air thermal current":"115 A IEC 60947-4-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$935.00","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/fc98dd72ff5c86e232662c4f979abdf6.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/GV4PE02S/alternatives.json"},"ai":{"faq":[{"question":"What is the GV4PE02S's listed color?","answer":"The housing is Gray RAL 7016, per the specification."},{"question":"What is the GV4PE02S depth?","answer":"Depth is 4.6 inches (116 mm), with a width of 3.2 in and height of 6.1 in."},{"question":"What compliance documentation does Schneider provide for the GV4PE02S?","answer":"The breaker is certified to CSA C22.2 No 60947-4-1, UL 60947-4-1, EN/IEC 60947-4-1, and EN/IEC 60947-2. Fire resistance is tested to 960 °C per IEC 60695-2-11."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV4PE02S","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV4PE02S when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}