{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV4PE07N","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV4PE07N","canonicalUrl":"https://aoctrl.com/schneider/GV4PE07N","factsUrl":"https://aoctrl.com/api/mcp/products/GV4PE07N","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys GV4 Deca motor circuit breaker, GV4PE07N, 3-pole, 7 A rated current, electronic thermal-magnetic trip, breaking capacity 100 kA at 240 V AC, IP40.","salesMarkdown":"## Breaking capacity — what it takes to clear a fault The GV4PE07N: At 240 V AC it breaks 100 kA — that's enough for most North American 480Y/277 panels without an upstream fuse. If you're working in a 660–690 V plant, the rating drops to 8 kA, so check your fault current before swapping one in. For UL panels: 65 kA at 240 V, 35 kA at 480Y/277. ## What fits and where — field install notes Three-pole, 155 mm tall, 81 mm wide, 116 mm deep — it'll fit most standard disconnects and motor starter layouts. IP40 enclosure, IK07 impact rating, so it's fine inside a panel but not outdoors or washdown zones. Terminals are EverLink screw type: top accepts 1.5–70 mm² solid (or 1.5–50 mm² flexible), bottom goes up to 95 mm² solid. Torque the line and load to 9 N·m (79.7 lbf·in) — use a torque screwdriver, not a gun. The control is a toggle; it's suitable for isolation per IEC 60947-1. Listed to UL 60947-4-1 and CSA C22.2 No 60947-4-1, plus EN/IEC 60947-4-1 and 60947-2. That covers most industrial and commercial installations. Fire resistance tested at 960 °C. Continuous duty rated — no need to derate for continuous motor load.","metaTitle":"Schneider TeSys GV4PE07N Motor Circuit Breaker, 7 A, 3P","metaDescription":"Schneider TeSys GV4PE07N motor circuit breaker, 7 A continuous, 119 A magnetic trip, 100 kA breaking capacity at 240 V. Active production. UL & IEC listed. Sourced to RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Gray RAL 7016)","Depth":"4.6 in (116 mm)","Range":"TeSys Deca","Width":"3.2 in (81 mm)","Height":"6.1 in (155 mm)","Category":"US10I1122365","Standards":"CSA C22.2 No 60947-4-1 UL 60947-4-1 EN/IEC 60947-4-1 EN/IEC 60947-2","Rated duty":"Continuous IEC 60947-4-1","Control Type":"Toggle","Product name":"TeSys GV4","Motor power kW":"1.5 kW 400...415 V AC 50/60 Hz 2.2 kW 400...415 V AC 50/60 Hz 2.5 kW 400...415 V AC 50/60 Hz 3 kW 400...415 V AC 50/60 Hz 2.2 kW 500 V AC 50/60 Hz 2.5 kW 500 V AC 50/60 Hz 3 kW 500 V AC 50/60 Hz 4 kW 500 V AC 50/60 Hz 3 kW 660...690 V AC 50/60 Hz 4 kW 660...690 V AC 50/60 Hz 5.5 kW 660...690 V AC 50/60 Hz 7.5 kW 660...690 V AC 50/60 Hz","Fire resistance":"1760 °F (960 °C) IEC 60695-2-11","lifecycle_stage":"current","Pollution degree":"3","Range of Product":"TeSys GV4","Breaking capacity":"100 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 50 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 50 kA Icu 440 V AC 50/60 Hz IEC 60947-2 15 kA Icu 525 V AC 50/60 Hz IEC 60947-2 65 kA 208Y/120 V AC 50/60 Hz UL 60947 65 kA 240 V AC 50/60 Hz UL 60947 35 kA 480Y/277 V AC 50/60 Hz UL 60947 8 kA Icu 660...690 V AC 50/60 Hz IEC 60947-2 25 kA Icu 500 V AC 50/60 Hz IEC 60947-2 18 kA 600Y/347 V AC 50/60 Hz UL 60947","Device short name":"GV4PE","Poles description":"3P","Tightening torque":"79.7 lbf.in (9 N.m) 0.02...0.1 in² (16...95 mm²) 44.3 lbf.in (5 N.m) 0.002...0.02 in² (1.5...10 mm²)","Climatic withstand":"IACS E10","Device Application":"Motor protection","Line Rated Current":"7 A","Operating altitude":"5000 m","Operating position":"Any position","Trip unit technology":"Electronic Thermal-magnetic","Utilisation category":"Category A IEC 60947-2 AC-3 IEC 60947-4-1","Electrical durability":"40000 cycles AC-3 440 V In/2 40000 cycles AC-3 440 V In","Mechanical durability":"40000 cycles","Mechanical robustness":"Vibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 Vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 Shocks 15 gn 11 ms IEC 60068-2-27","Nbr. of units in pkg.":"1","Maximum Operating Rate":"25 cyc/h","Connections - terminals":"EverLink BTR screw connectors top) 1 0.002...0.1 in² (1.5...70 mm²) - solid EverLink BTR screw connectors top) 1 0.002...0.08 in² (1.5...50 mm²) - flexible EverLink BTR screw connectors bottom) 1 0.004...0.1 in² (2.5...95 mm²) - solid EverLink BTR screw connectors bottom) 1 0.004...0.1 in² (2.5...70 mm²) - flexible","IK degree of protection":"IK07 IEC 62262","IP degree of protection":"IP40 IEC 60529","Magnetic tripping current":"119 A","Phase failure sensitivity":"Yes IEC 60947-4-1","Product or Component Type":"Motor circuit breaker","Suitability for isolation":"Yes IEC 60947-1","Power dissipation per pole":"4.6 W","[Ui] rated insulation voltage":"800 V AC 50/60 Hz IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz IEC 60947-2","Ambient Air Temperature for Storage":"-58...185 °F (-50...85 °C)","Ambient air temperature for operation":"-13...158 °F (-25...70 °C)","[Uimp] rated impulse withstand voltage":"8 kV IEC 60947-2","[Ith] conventional free air thermal current":"115 A IEC 60947-4-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$770.00","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/fc98dd72ff5c86e232662c4f979abdf6.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/GV4PE07N/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings of GV4PE07N?","answer":"Rated current 7 A, magnetic trip 119 A, breaking capacity 100 kA at 240 V AC (65 kA UL at 240 V). Three-pole, used for motor protection. Electronic thermal-magnetic trip with phase failure sensitivity."},{"question":"What compliance documentation does this breaker meet?","answer":"It is UL 60947-4-1 listed, CSA C22.2 No 60947-4-1, and complies with EN/IEC 60947-4-1 and 60947-2. Also suitable for isolation per IEC 60947-1."},{"question":"What wire sizes does the GV4PE07N accept?","answer":"Top terminals accept 1.5–70 mm² solid (1.5–50 mm² flexible); bottom terminals accept 2.5–95 mm² solid (2.5–70 mm² flexible). Torque to 9 N·m."},{"question":"How deep is the GV4PE07N?","answer":"116 mm (4.6 in) deep. Overall height 155 mm, width 81 mm. Not a huge footprint, but check your panel depth before installing."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV4PE07N","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV4PE07N when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}