{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV4PE115N","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV4PE115N","canonicalUrl":"https://aoctrl.com/schneider/GV4PE115N","factsUrl":"https://aoctrl.com/api/mcp/products/GV4PE115N","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca GV4PE115N motor circuit breaker, 115 A line rated, 3-pole, electronic thermal-magnetic trip, gray RAL 7016.","salesMarkdown":"The Schneider GV4PE115N is a 3-pole motor circuit breaker from the TeSys Deca range, rated for continuous duty at 115 A line current. It provides motor protection via an electronic thermal-magnetic trip unit, with magnetic tripping set at 1955 A. Rated for AC-3 duty per IEC 60947-4-1, it's built for switching motor loads under running conditions. The 115 A frame covers motors up to 55 kW at 400 V or 110 kW at 690 V, depending on supply voltage. Breaking capacity: 100 kA at 240 V AC (IEC) and 65 kA at 480Y/277 V (UL). That puts it in a strong selectivity class for most industrial panels — you can coordinate with upstream 100 kA rated MCCBs without extra current-limiting fuses. For motor protection, pair it with a motor FLA equal to or slightly below that — typical for 37–55 kW motors at 400 V. Tripping is electronic thermal-magnetic: the thermal curve handles overloads, the magnetic element acts at 1955 A (17x Iₙ) for short-circuit. Phase failure sensitivity is built in per IEC 60947-4-1. Suitable for isolation (toggle on/off with visible break) and rated pollution degree 3, so it can live in a standard industrial panel without special derating for heavy dust or conductive contamination. Dimensions: 6.1 x 3.2 x 4.6 in (155 x 81 x 116 mm). Connectors are EverLink BTR screw terminals: accept up to 95 mm² solid on the load side, 70 mm² flexible. Torque range 5–9 Nm. IP40 with IK07 impact resistance. Operating in any position, up to 5000 m altitude without derating.","metaTitle":"Schneider TeSys GV4PE115N Motor Circuit Breaker, 115 A","metaDescription":"GV4PE115N TeSys Deca motor circuit breaker, 115 A rated, AC-3 duty, 100 kA breaking capacity at 240 V. Active, sourced to order. UL/IEC listed.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Gray RAL 7016)","Depth":"4.6 in (116 mm)","Range":"TeSys Deca","Width":"3.2 in (81 mm)","Height":"6.1 in (155 mm)","Category":"US10I1122365","Standards":"CSA C22.2 No 60947-4-1 UL 60947-4-1 EN/IEC 60947-4-1 EN/IEC 60947-2","Rated duty":"Continuous IEC 60947-4-1","Control Type":"Toggle","Product name":"TeSys GV4","Motor power kW":"37 kW 400...415 V AC 50/60 Hz 45 kW 400...415 V AC 50/60 Hz 55 kW 400...415 V AC 50/60 Hz 45 kW 500 V AC 50/60 Hz 55 kW 500 V AC 50/60 Hz 75 kW 500 V AC 50/60 Hz 75 kW 660...690 V AC 50/60 Hz 90 kW 660...690 V AC 50/60 Hz 110 kW 660...690 V AC 50/60 Hz","Fire resistance":"1760 °F (960 °C) IEC 60695-2-11","lifecycle_stage":"current","Pollution degree":"3","Range of Product":"TeSys GV4","Breaking capacity":"100 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 50 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 50 kA Icu 440 V AC 50/60 Hz IEC 60947-2 15 kA Icu 525 V AC 50/60 Hz IEC 60947-2 65 kA 208Y/120 V AC 50/60 Hz UL 60947 65 kA 240 V AC 50/60 Hz UL 60947 35 kA 480Y/277 V AC 50/60 Hz UL 60947 8 kA Icu 660...690 V AC 50/60 Hz IEC 60947-2 25 kA Icu 500 V AC 50/60 Hz IEC 60947-2 18 kA 600Y/347 V AC 50/60 Hz UL 60947","Device short name":"GV4PE","Poles description":"3P","Tightening torque":"79.7 lbf.in (9 N.m) 0.02...0.1 in² (16...95 mm²) 44.3 lbf.in (5 N.m) 0.002...0.02 in² (1.5...10 mm²)","Climatic withstand":"IACS E10","Device Application":"Motor protection","Line Rated Current":"115 A","Operating altitude":"5000 m","Operating position":"Any position","Trip unit technology":"Electronic Thermal-magnetic","Utilisation category":"Category A IEC 60947-2 AC-3 IEC 60947-4-1","Electrical durability":"10000 cycles AC-3 440 V In/2 5000 cycles AC-3 440 V In","Mechanical durability":"40000 cycles","Mechanical robustness":"Vibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 Vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 Shocks 15 gn 11 ms IEC 60068-2-27","Nbr. of units in pkg.":"1","Maximum Operating Rate":"25 cyc/h","Connections - terminals":"EverLink BTR screw connectors top) 1 0.002...0.1 in² (1.5...70 mm²) - solid EverLink BTR screw connectors top) 1 0.002...0.08 in² (1.5...50 mm²) - flexible EverLink BTR screw connectors bottom) 1 0.004...0.1 in² (2.5...95 mm²) - solid EverLink BTR screw connectors bottom) 1 0.004...0.1 in² (2.5...70 mm²) - flexible","IK degree of protection":"IK07 IEC 62262","IP degree of protection":"IP40 IEC 60529","Magnetic tripping current":"1955 A","Phase failure sensitivity":"Yes IEC 60947-4-1","Product or Component Type":"Motor circuit breaker","Suitability for isolation":"Yes IEC 60947-1","Power dissipation per pole":"4.6 W","[Ui] rated insulation voltage":"800 V AC 50/60 Hz IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz IEC 60947-2","Ambient Air Temperature for Storage":"-58...185 °F (-50...85 °C)","Ambient air temperature for operation":"-13...158 °F (-25...70 °C)","[Uimp] rated impulse withstand voltage":"8 kV IEC 60947-2","[Ith] conventional free air thermal current":"115 A IEC 60947-4-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$132.08","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0e0640073751c655467e0b465cbac9ca.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/GV4PE115N/alternatives.json"},"ai":{"faq":[{"question":"What color is the GV4PE115N?","answer":"Gray RAL 7016."},{"question":"What are the key compliance standards for the GV4PE115N?","answer":"It meets UL 60947-4-1, CSA C22.2 No 60947-4-1, and EN/IEC 60947-4-1 for motor protection, plus IEC 60947-2 for circuit breaker performance."},{"question":"What is the breaking capacity of the GV4PE115N?","answer":"Up to 100 kA at 240 V AC (IEC) and 65 kA at 480Y/277 V (UL)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV4PE115N","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV4PE115N when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}