{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV4PE115S","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV4PE115S","canonicalUrl":"https://aoctrl.com/schneider/GV4PE115S","factsUrl":"https://aoctrl.com/api/mcp/products/GV4PE115S","rawCanonicalId":null},"summary":{"shortDescription":"Schneider TeSys Deca GV4PE115S motor circuit breaker, 115 A, 3-pole, thermal-magnetic electronic trip, breaking capacity 120 kA at 240 V AC, IP40, gray RAL 7016.","salesMarkdown":"The GV4PE115S is a 3-pole motor circuit breaker from the TeSys Deca range, rated 115 A continuous. It combines thermal-magnetic and electronic trip technology, with a magnetic tripping threshold of 1955 A. The breaker is listed as current production. Breaking capacity is voltage-dependent: 120 kA at 240 V AC, 100 kA at 380-415 V, 70 kA at 440 V, 30 kA at 500 V, and 10 kA at 660-690 V. Under UL 60947, it handles 100 kA at 240 V and 65 kA at 480Y/277 V. These figures cover most industrial panel SCCR requirements. ## Motor power coverage At 400–415 V AC 50/60 Hz, the breaker handles motors from 37 kW up to 55 kW. At 660–690 V, the range extends to 110 kW. This gives flexibility for multi-voltage installations common in export panels. Electrical durability is 10,000 cycles at AC-3 with half rated current, and 5,000 cycles at full rated current. Mechanical endurance is 40,000 cycles. Maximum operating rate is 25 cycles per hour. Dimensions: 6.1 x 3.2 x 4.6 inches (H x W x D). IP40 and IK07 rated. Operating position any, with pollution degree 3. EverLink screw terminals accept solid from 1.5 mm² up to 95 mm² on the load side, flexible from 2.5 to 70 mm². Torque settings: 9 N·m for main conductors, 5 N·m for control wiring. Power dissipation per pole is 4.6 W. Climatic withstand is IACS, and operating altitude up to 5000 m. Designed to EN/IEC 60947-2 and 60947-4-1, plus CSA C22.2 No 60947-4-1 and UL 60947-4-1. Suitability for isolation per IEC 60947-1. Phase failure sensitivity included. Fire resistance tested to 960 °C.","metaTitle":"Schneider TeSys Deca GV4PE115S Motor Circuit Breaker, 115 A,","metaDescription":"Active production. 115 A, 3-pole motor circuit breaker in TeSys Deca range. 120 kA breaking at 240 V AC. Thermal-magnetic electronic trip. UL/CSA/IEC compliant. RFQ sourcing.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Gray RAL 7016)","Depth":"4.6 in (116 mm)","Range":"TeSys Deca","Width":"3.2 in (81 mm)","Height":"6.1 in (155 mm)","Category":"US10I1122365","Standards":"CSA C22.2 No 60947-4-1 UL 60947-4-1 EN/IEC 60947-4-1 EN/IEC 60947-2","Rated duty":"Continuous IEC 60947-4-1","Control Type":"Toggle","Product name":"TeSys GV4","Motor power kW":"37 kW 400...415 V AC 50/60 Hz 45 kW 400...415 V AC 50/60 Hz 55 kW 400...415 V AC 50/60 Hz 45 kW 500 V AC 50/60 Hz 55 kW 500 V AC 50/60 Hz 75 kW 500 V AC 50/60 Hz 75 kW 660...690 V AC 50/60 Hz 90 kW 660...690 V AC 50/60 Hz 110 kW 660...690 V AC 50/60 Hz","Fire resistance":"1760 °F (960 °C) IEC 60695-2-11","lifecycle_stage":"current","Pollution degree":"3","Range of Product":"TeSys GV4","Breaking capacity":"120 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 100 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 70 kA Icu 440 V AC 50/60 Hz IEC 60947-2 30 kA Icu 500 V AC 50/60 Hz IEC 60947-2 18 kA Icu 525 V AC 50/60 Hz IEC 60947-2 100 kA 208Y/120 V AC 50/60 Hz UL 60947 100 kA 240 V AC 50/60 Hz UL 60947 65 kA 480Y/277 V AC 50/60 Hz UL 60947 10 kA Icu 660...690 V AC 50/60 Hz IEC 60947-2 25 kA 600Y/347 V AC 50/60 Hz UL 60947","Device short name":"GV4PE","Poles description":"3P","Tightening torque":"79.7 lbf.in (9 N.m) 0.02...0.1 in² (16...95 mm²) 44.3 lbf.in (5 N.m) 0.002...0.02 in² (1.5...10 mm²)","Climatic withstand":"IACS E10","Device Application":"Motor protection","Line Rated Current":"115 A","Operating altitude":"5000 m","Operating position":"Any position","Trip unit technology":"Thermal-magnetic Electronic","Utilisation category":"Category A IEC 60947-2 AC-3 IEC 60947-4-1","Electrical durability":"10000 cycles AC-3 440 V In/2 5000 cycles AC-3 440 V In","Mechanical durability":"40000 cycles","Mechanical robustness":"Vibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 Vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 Shocks 15 gn 11 ms IEC 60068-2-27","Nbr. of units in pkg.":"1","Maximum Operating Rate":"25 cyc/h","Connections - terminals":"EverLink BTR screw connectors top) 1 0.002...0.1 in² (1.5...70 mm²) - solid EverLink BTR screw connectors top) 1 0.002...0.08 in² (1.5...50 mm²) - flexible EverLink BTR screw connectors bottom) 1 0.004...0.1 in² (2.5...95 mm²) - solid EverLink BTR screw connectors bottom) 1 0.004...0.1 in² (2.5...70 mm²) - flexible","IK degree of protection":"IK07 IEC 62262","IP degree of protection":"IP40 IEC 60529","Magnetic tripping current":"1955 A","Phase failure sensitivity":"Yes IEC 60947-4-1","Product or Component Type":"Motor circuit breaker","Suitability for isolation":"Yes IEC 60947-1","Power dissipation per pole":"4.6 W","[Ui] rated insulation voltage":"800 V AC 50/60 Hz IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz IEC 60947-2","Ambient Air Temperature for Storage":"-58...185 °F (-50...85 °C)","Ambient air temperature for operation":"-13...158 °F (-25...70 °C)","[Uimp] rated impulse withstand voltage":"8 kV IEC 60947-2","[Ith] conventional free air thermal current":"115 A IEC 60947-4-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$149.86","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0e0640073751c655467e0b465cbac9ca.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/GV4PE115S/alternatives.json"},"ai":{"faq":[{"question":"What is the listed color of the GV4PE115S?","answer":"The enclosure color is gray RAL 7016."},{"question":"What is the depth of the GV4PE115S?","answer":"The depth is 4.6 inches (116 mm)."},{"question":"What compliance certifications does the GV4PE115S carry?","answer":"It is certified to CSA C22.2 No 60947-4-1, UL 60947-4-1, EN/IEC 60947-4-1, and EN/IEC 60947-2."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV4PE115S","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV4PE115S when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}