{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV4PE50B6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV4PE50B6","canonicalUrl":"https://aoctrl.com/schneider/GV4PE50B6","factsUrl":"https://aoctrl.com/api/mcp/products/GV4PE50B6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca GV4PE50B6 motor circuit breaker, 3-pole, 50 A line rated current, 50 kA Icu at 240 V AC, electronic thermal-magnetic trip, IP40, gray RAL 7016.","salesMarkdown":"## 50 A motor circuit breaker with 50 kA interrupting capacity The GV4PE50B6: The trip unit uses an electronic thermal-magnetic hybrid, which means the thermal curve handles overload protection with a programmable-like response while the magnetic element catches short-circuit events at 850 A magnetic tripping current. The electronic side also enables phase failure sensitivity per IEC 60947-4-1 — a feature that drops the breaker when one phase is lost, preventing single-phasing damage on a motor load. ## Motor power coverage and load matching At 400–415 V AC, the GV4PE50B6 covers motor ratings from 11 kW up to 22 kW depending on the voltage tap. At 500 V it handles 15–30 kW, and at 660–690 V it spans 18.5–45 kW. That's a wide power band for a single frame size — the 50 A setting lets you dial in the exact motor FLA within the adjustable range of the TeSys Deca platform. Mechanical durability is 40,000 cycles. The maximum operating rate is 25 cycles per hour — relevant for frequent start-stop applications like conveyors or pump cycling. ## Panel fit and environmental ratings Dimensions are 6.1 x 3.2 x 4.6 inches (155 x 81 x 116 mm). The connection pitch is 27 mm without spreaders, expanding to 35 mm with spreaders — the spreaders give extra clearance for larger cable lugs in a crowded enclosure. Terminal capacity accepts 1.5–95 mm² wire. IK07 impact resistance covers accidental tool drops. ## Certification and compliance coverage That covers the three major regional approval frameworks — UL for North America, CSA for Canada, and IEC/EN for global and European markets. Fire resistance is tested to 960 °C per IEC 60695-2-11.","metaTitle":"Schneider GV4PE50B6 TeSys Deca MPCB, 50 A, 50 kA Icu","metaDescription":"Schneider Electric GV4PE50B6 TeSys Deca motor circuit breaker, 50 A rated current, 50 kA breaking capacity at 240 V. UL/CSA/IEC certified.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Color":"Gray RAL 7016)","Depth":"4.6 in (116 mm)","Width":"3.2 in (81 mm)","Height":"6.1 in (155 mm)","Voltage":"690 V AC 50/60 Hz IEC 60947-2","IP Rating":"IP40","Application":"Motor protection","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"1.06 in (27 mm) without spreaders 1.4 in (35 mm) with spreaders","Trip Unit Type":"Electronic Thermal-magnetic","Pollution Degree":"3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Breaking Capacity":"50 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 25 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 20 kA Icu 440 V AC 50/60 Hz IEC 60947-2 10 kA Icu 500 V AC 50/60 Hz IEC 60947-2 35 kA 208Y/120 V AC 50/60 Hz UL 60947 35 kA 240 V AC 50/60 Hz UL 60947 18 kA 480Y/277 V AC 50/60 Hz UL 60947 14 kA 600Y/347 V AC 50/60 Hz UL 60947","Insulation Voltage Ui":"800 V AC 50/60 Hz IEC 60947-2","Operating Position":"Any position","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-58...185 °F (-50...85 °C)","Utilization Category":"Category A IEC 60947-2 AC-3 IEC 60947-4-1","Electrical Life Cycles":"20000 cycles AC-3 440 V In/2 10000 cycles AC-3 440 V In","Mechanical Life Cycles":"40000 cycles","Main Product Or Component Type":"Motor circuit breaker","Ambient Air Temperature Operation":"-13...158 °F (-25...70 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/au/en/product/GV4PE50B6/motor-circuit-breaker-tesys-gv4-tesys-gv4-3p-50a-icu-25ka-thermal-magnetic-lugs-terminals/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV4PE50B6/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV4PE50B6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV4PE50B6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}