{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV4PE50N6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV4PE50N6","canonicalUrl":"https://aoctrl.com/schneider/GV4PE50N6","factsUrl":"https://aoctrl.com/api/mcp/products/GV4PE50N6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys GV4 motor circuit breaker, GV4PE50N6, 50 A rated current, 3-pole, thermal-magnetic and electronic trip, 100 kA breaking capacity at 240 V, IP40, gray RAL 7016.","salesMarkdown":"The GV4PE50N6: At 480Y/277 V UL drops to 35 kA; at 600Y/347 V UL it is 18 kA. The IEC ratings follow a similar derating: 50 kA at 380–415 V, 15 kA at 525 V, and 8 kA at 660–690 V. ## Motor power and trip technology Rated 50 A line current, the GV4PE50N6 covers motor power from 11 kW at 400 V up to 45 kW at 690 V (AC-3 duty). ## Standards and physical fit The 3-pole device measures 81 mm wide, 155 mm high, 116 mm deep, with a connection pitch of 27 mm (35 mm with spreaders). IP40 front protection, IK07 impact resistance, and pollution degree 3 suit it for standard industrial enclosures.","metaTitle":"Schneider Electric GV4PE50N6 Motor Circuit Breaker, 50 A","metaDescription":"Schneider Electric GV4PE50N6 motor circuit breaker, 50 A rated, 100 kA breaking capacity at 240 V, UL/CSA/IEC certified. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Gray RAL 7016)","Depth":"4.6 in (116 mm)","Width":"3.2 in (81 mm)","Height":"6.1 in (155 mm)","Voltage":"690 V AC 50/60 Hz IEC 60947-2","IP Rating":"IP40","Application":"Motor protection","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"1.06 in (27 mm) without spreaders 1.4 in (35 mm) with spreaders","Trip Unit Type":"Thermal-magnetic Electronic","Pollution Degree":"3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Breaking Capacity":"100 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 50 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 50 kA Icu 440 V AC 50/60 Hz IEC 60947-2 15 kA Icu 525 V AC 50/60 Hz IEC 60947-2 65 kA 208Y/120 V AC 50/60 Hz UL 60947 65 kA 240 V AC 50/60 Hz UL 60947 35 kA 480Y/277 V AC 50/60 Hz UL 60947 8 kA Icu 660...690 V AC 50/60 Hz IEC 60947-2 25 kA Icu 500 V AC 50/60 Hz IEC 60947-2 18 kA 600Y/347 V AC 50/60 Hz UL 60947","Insulation Voltage Ui":"800 V AC 50/60 Hz IEC 60947-2","Operating Position":"Any position","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-58...185 °F (-50...85 °C)","Utilization Category":"Category A IEC 60947-2 AC-3 IEC 60947-4-1","Electrical Life Cycles":"20000 cycles AC-3 440 V In/2 10000 cycles AC-3 440 V In","Mechanical Life Cycles":"40000 cycles","Main Product Or Component Type":"Motor circuit breaker","Ambient Air Temperature Operation":"-13...158 °F (-25...70 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/ca/en/product/GV4PE50N6/motor-circuit-breaker-tesys-gv4-3p-50a-icu-50ka-thermal-magnetic-lugs-terminals/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV4PE50N6/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV4PE50N6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV4PE50N6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}