{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV4PE80N6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV4PE80N6","canonicalUrl":"https://aoctrl.com/schneider/GV4PE80N6","factsUrl":"https://aoctrl.com/api/mcp/products/GV4PE80N6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca GV4PE80N6 motor circuit breaker, 3-pole, 80 A, thermal-magnetic/electronic trip, gray RAL 7016.","salesMarkdown":"The GV4PE80N6 is a 3-pole motor circuit breaker from the TeSys Deca range, rated 80 A continuous for AC-3 motor protection per IEC 60947-4-1. Its trip unit merges thermal-magnetic and electronic elements, providing phase-failure sensitivity per IEC 60947-4-1. Lifecycle stage is 'current' — active in production. With an interrupting capacity of 100 kA at 240 V AC (IEC 60947-2) and 50 kA at 415 V, the GV4PE80N6 provides substantial SCCR headroom for most industrial distribution panels — the 100 kA figure at 240 V is the high end for a 3-pole motor circuit breaker in this frame. Dimensions: width 81 mm, depth 116 mm, height 155 mm. IP40 enclosure protection, IK07 impact resistance. Operating position any; altitude 5000 m max. Connection via lugs/ring terminals. Tightening torque 9 N·m for conductors up to 95 mm² (0.02–0.1 in²), 5 N·m for control wires 1.5–10 mm² — the 79.7 lbf·in value for the main power circuit is within spec. Mechanical endurance: 40,000 operations. Electrical endurance at AC-3 440 V: 14,000 cycles at In/2, 7,000 cycles at In. Maximum operating rate 25 cycles per hour.","metaTitle":"Schneider GV4PE80N6 TeSys Deca Motor Circuit Breaker, 80A, 3","metaDescription":"Schneider GV4PE80N6 TeSys Deca motor circuit breaker, 80 A rated, 3-pole, suitable for motor protection. Active production, compliant with CSA, UL, IEC. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Gray RAL 7016)","Depth":"4.6 in (116 mm)","Range":"TeSys Deca","Width":"3.2 in (81 mm)","Height":"6.1 in (155 mm)","Category":"US10I1122365","Standards":"CSA C22.2 No 60947-4-1 UL 60947-4-1 EN/IEC 60947-4-1 EN/IEC 60947-2","Rated duty":"Continuous IEC 60947-4-1","Control Type":"Toggle","Product name":"TeSys GV4","Motor power kW":"37 kW 400...415 V AC 50/60 Hz 45 kW 500 V AC 50/60 Hz 22 kW 400...415 V AC 50/60 Hz 30 kW 500 V AC 50/60 Hz 37 kW 660...690 V AC 50/60 Hz 45 kW 660...690 V AC 50/60 Hz 55 kW 660...690 V AC 50/60 Hz 30 kW 400...415 V AC 50/60 Hz 37 kW 500 V AC 50/60 Hz","Fire resistance":"1760 °F (960 °C) IEC 60695-2-11","lifecycle_stage":"current","Connection pitch":"1.06 in (27 mm) without spreaders 1.4 in (35 mm) with spreaders","Pollution degree":"3","Range of Product":"TeSys GV4","Breaking capacity":"100 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 50 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 50 kA Icu 440 V AC 50/60 Hz IEC 60947-2 15 kA Icu 525 V AC 50/60 Hz IEC 60947-2 65 kA 208Y/120 V AC 50/60 Hz UL 60947 65 kA 240 V AC 50/60 Hz UL 60947 35 kA 480Y/277 V AC 50/60 Hz UL 60947 8 kA Icu 660...690 V AC 50/60 Hz IEC 60947-2 25 kA Icu 500 V AC 50/60 Hz IEC 60947-2 18 kA 600Y/347 V AC 50/60 Hz UL 60947","Device short name":"GV4PE","Poles description":"3P","Tightening torque":"79.7 lbf.in (9 N.m) 0.02...0.1 in² (16...95 mm²) 44.3 lbf.in (5 N.m) 0.002...0.02 in² (1.5...10 mm²)","Climatic withstand":"IACS E10","Device Application":"Motor protection","Line Rated Current":"80 A","Operating altitude":"5000 m","Operating position":"Any position","Trip unit technology":"Thermal-magnetic Electronic","Utilisation category":"Category A IEC 60947-2 AC-3 IEC 60947-4-1","Electrical durability":"14000 cycles AC-3 440 V In/2 7000 cycles AC-3 440 V In","Mechanical durability":"40000 cycles","Mechanical robustness":"Vibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 Vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 Shocks 15 gn 11 ms IEC 60068-2-27","Nbr. of units in pkg.":"1","Maximum Operating Rate":"25 cyc/h","Connections - terminals":"Lugs-ring terminals","IK degree of protection":"IK07 IEC 62262","IP degree of protection":"IP40 IEC 60529","Magnetic tripping current":"1360 A","Phase failure sensitivity":"Yes IEC 60947-4-1","Product or Component Type":"Motor circuit breaker","Suitability for isolation":"Yes IEC 60947-1","Power dissipation per pole":"4.6 W","[Ui] rated insulation voltage":"800 V AC 50/60 Hz IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz IEC 60947-2","Ambient Air Temperature for Storage":"-58...185 °F (-50...85 °C)","Ambient air temperature for operation":"-13...158 °F (-25...70 °C)","[Uimp] rated impulse withstand voltage":"8 kV IEC 60947-2","[Ith] conventional free air thermal current":"115 A IEC 60947-4-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$935.00","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1edf2f4feea5ff6b692fb205024a9356.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/GV4PE80N6/alternatives.json"},"ai":{"faq":[{"question":"What is GV4PE80N6's listed color?","answer":"Gray RAL 7016."},{"question":"What is GV4PE80N6's listed depth?","answer":"4.6 in (116 mm)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV4PE80N6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV4PE80N6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}