{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV4PEM03N6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV4PEM03N6","canonicalUrl":"https://aoctrl.com/schneider/GV4PEM03N6","factsUrl":"https://aoctrl.com/api/mcp/products/GV4PEM03N6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys GV4 motor circuit breaker, GV4PEM03N6, 3-pole, 3.5 A line rated current, electronic thermal-magnetic trip, AC-3 duty, breaking capacity 100 kA at 240 V.","salesMarkdown":"TeSys GV4 motor circuit breaker GV4PEM03N6 is a 3-pole device rated 3.5 A line current, designed for motor protection under AC-3 utilization (IEC 60947-4-1). Its electronic thermal-magnetic trip unit provides phase failure sensitivity and adjustable magnetic tripping at 59 A. Dimensions 81 mm wide x 155 mm high x 116 mm deep (3.2 x 6.1 x 4.6 in). Connects via lug-ring terminals; tightening torque 5 N·m for 1.5–10 mm² and 9 N·m for 16–95 mm². Connection pitch is 27 mm (1.06 in) without spreaders, 35 mm (1.4 in) with. Pollution degree 3 rated, IP40 front panel protection, IK07 impact resistance. Operating altitude to 5000 m, any mounting position allowed. Climatic withstand per IACS. ## Operational Constraints & Electrical Durability Maximum operating rate 25 cyc/h, electrical durability 40000 cycles at AC-3 440 V, mechanical durability 40000 cycles, and power dissipation per pole 4.6 W. Rated for continuous duty IEC 60947-4-1 and suitability for isolation IEC 60947-1.","metaTitle":"Schneider GV4PEM03N6 TeSys GV4 Motor Circuit Breaker, 3.5 A,","metaDescription":"GV4PEM03N6 motor circuit breaker, 3.5 A rated current, AC-3 utilization, 100 kA breaking capacity at 240 V. Active lifecycle. Sourced to order. Complies with UL/CSA/IEC 60947.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Gray RAL 7016)","Depth":"4.6 in (116 mm)","Range":"TeSys Deca","Width":"3.2 in (81 mm)","Height":"6.1 in (155 mm)","Category":"US10I1122365","Standards":"CSA C22.2 No 60947-4-1 UL 60947-4-1 EN/IEC 60947-4-1 EN/IEC 60947-2","Rated duty":"Continuous IEC 60947-4-1","Control Type":"Toggle","Product name":"TeSys GV4","Motor power kW":"0.55 kW 400...415 V AC 50/60 Hz 0.75 kW 400...415 V AC 50/60 Hz 0.75 kW 500 V AC 50/60 Hz 1.1 kW 500 V AC 50/60 Hz 1.1 kW 660...690 V AC 50/60 Hz 1.5 kW 660...690 V AC 50/60 Hz 1.5 kW 500 V AC 50/60 Hz 2.2 kW 660...690 V AC 50/60 Hz 1.1 kW 400...415 V AC 50/60 Hz 1.5 kW 400...415 V AC 50/60 Hz","Fire resistance":"1760 °F (960 °C) IEC 60695-2-11","lifecycle_stage":"current","Connection pitch":"1.06 in (27 mm) without spreaders 1.4 in (35 mm) with spreaders","Pollution degree":"3","Range of Product":"TeSys GV4","Breaking capacity":"100 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 50 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 50 kA Icu 440 V AC 50/60 Hz IEC 60947-2 15 kA Icu 525 V AC 50/60 Hz IEC 60947-2 65 kA 208Y/120 V AC 50/60 Hz UL 60947 65 kA 240 V AC 50/60 Hz UL 60947 35 kA 480Y/277 V AC 50/60 Hz UL 60947 8 kA Icu 660...690 V AC 50/60 Hz IEC 60947-2 25 kA Icu 500 V AC 50/60 Hz IEC 60947-2 18 kA 600Y/347 V AC 50/60 Hz UL 60947","Device short name":"GV4PEM","Poles description":"3P","Tightening torque":"79.7 lbf.in (9 N.m) 0.02...0.1 in² (16...95 mm²) 44.3 lbf.in (5 N.m) 0.002...0.02 in² (1.5...10 mm²)","Climatic withstand":"IACS E10","Device Application":"Motor protection","Line Rated Current":"3.5 A","Operating altitude":"5000 m","Operating position":"Any position","Trip unit technology":"Electronic Thermal-magnetic","Utilisation category":"Category A IEC 60947-2 AC-3 IEC 60947-4-1","Electrical durability":"40000 cycles AC-3 440 V In/2 40000 cycles AC-3 440 V In","Mechanical durability":"40000 cycles","Mechanical robustness":"Vibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 Vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 Shocks 15 gn 11 ms IEC 60068-2-27","Nbr. of units in pkg.":"1","Maximum Operating Rate":"25 cyc/h","Connections - terminals":"Lugs-ring terminals","IK degree of protection":"IK07 IEC 62262","IP degree of protection":"IP40 IEC 60529","Magnetic tripping current":"59 A","Phase failure sensitivity":"Yes IEC 60947-4-1","Product or Component Type":"Motor circuit breaker","Suitability for isolation":"Yes IEC 60947-1","Power dissipation per pole":"4.6 W","[Ui] rated insulation voltage":"800 V AC 50/60 Hz IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz IEC 60947-2","Ambient Air Temperature for Storage":"-58...185 °F (-50...85 °C)","Ambient air temperature for operation":"-13...158 °F (-25...70 °C)","[Uimp] rated impulse withstand voltage":"8 kV IEC 60947-2","[Ith] conventional free air thermal current":"115 A IEC 60947-4-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/cc88fe9e394965dc167bdd644d7f3983.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/GV4PEM03N6/alternatives.json"},"ai":{"faq":[{"question":"What compliance certifications does GV4PEM03N6 hold?","answer":"It is certified to CSA C22.2 No 60947-4-1, UL 60947-4-1, EN/IEC 60947-4-1, and EN/IEC 60947-2."},{"question":"What is the depth dimension of this motor circuit breaker?","answer":"The depth is 4.6 in (116 mm)."},{"question":"What is the listed color for GV4PEM03N6?","answer":"The housing color is Gray RAL 7016."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV4PEM03N6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV4PEM03N6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}