{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV4PEM115B6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV4PEM115B6","canonicalUrl":"https://aoctrl.com/schneider/GV4PEM115B6","factsUrl":"https://aoctrl.com/api/mcp/products/GV4PEM115B6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys GV4 motor circuit breaker, GV4PEM115B6, 3-pole, 115 A line rated, thermal-magnetic and electronic trip, 50 kA breaking capacity at 240 V AC, IP40, gray RAL 7016.","salesMarkdown":"## 115 A motor circuit breaker for TeSys Deca panels The GV4PEM115B6: It combines thermal-magnetic and electronic trip technology to protect motors against overload, short-circuit, and phase failure — the electronic element provides adjustable protection curves that a purely thermal device cannot. At 415 V the rating drops to 25 kA, still adequate for typical motor branch circuits. ## Motor power coverage and trip coordination This breaker covers motors from 37 kW up to 110 kW depending on supply voltage — for example, 37 kW at 400 V, 55 kW at 500 V, and 110 kW at 690 V. The wide power range means a single frame size handles multiple motor ratings, simplifying panel stock. Magnetic trip threshold is fixed at 1955 A, which is 17× the line rating — this prevents nuisance tripping on motor inrush while still clearing a bolted fault quickly. Phase failure sensitivity per IEC 60947-4-1 ensures the breaker opens if one phase drops out, avoiding single-phase motor burnup. Mechanical durability is 40,000 cycles. Dimensions are 6.1 in (155 mm) high, 3.2 in (81 mm) wide, and 4.6 in (116 mm) deep — fits standard 35 mm DIN rail. Connection pitch is 27 mm without spreaders, expanding to 35 mm with spreaders for larger cable lugs up to 95 mm². IP40 front protection and IK07 impact resistance suit indoor panel environments. Pollution degree 3 means it tolerates conductive dust and occasional condensation — typical for factory-floor enclosures without climate control. The fire resistance rating of 960 °C per IEC 60695-2-11 supports global panel certification requirements.","metaTitle":"Schneider Electric GV4PEM115B6 TeSys GV4 MPCB, 115 A, 3-Pole","metaDescription":"Schneider Electric GV4PEM115B6 TeSys GV4 motor circuit breaker, 115 A line rated, 3-pole, thermal-magnetic & electronic trip. UL/CSA/IEC. Active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Color":"Gray RAL 7016)","Depth":"4.6 in (116 mm)","Range":"TeSys Deca","Width":"3.2 in (81 mm)","Height":"6.1 in (155 mm)","Category":"US10I1122365","Standards":"CSA C22.2 No 60947-4-1 UL 60947-4-1 EN/IEC 60947-4-1 EN/IEC 60947-2","Rated duty":"Continuous IEC 60947-4-1","Control Type":"Toggle","Product name":"TeSys GV4","Motor power kW":"37 kW 400...415 V AC 50/60 Hz 45 kW 400...415 V AC 50/60 Hz 55 kW 400...415 V AC 50/60 Hz 45 kW 500 V AC 50/60 Hz 55 kW 500 V AC 50/60 Hz 75 kW 500 V AC 50/60 Hz 75 kW 660...690 V AC 50/60 Hz 90 kW 660...690 V AC 50/60 Hz 110 kW 660...690 V AC 50/60 Hz","Fire resistance":"1760 °F (960 °C) IEC 60695-2-11","lifecycle_stage":"current","Connection pitch":"1.06 in (27 mm) without spreaders 1.4 in (35 mm) with spreaders","Pollution degree":"3","Range of Product":"TeSys GV4","Breaking capacity":"50 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 25 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 20 kA Icu 440 V AC 50/60 Hz IEC 60947-2 10 kA Icu 500 V AC 50/60 Hz IEC 60947-2 35 kA 208Y/120 V AC 50/60 Hz UL 60947 35 kA 240 V AC 50/60 Hz UL 60947 18 kA 480Y/277 V AC 50/60 Hz UL 60947 14 kA 600Y/347 V AC 50/60 Hz UL 60947","Device short name":"GV4PEM","Poles description":"3P","Tightening torque":"79.7 lbf.in (9 N.m) 0.02...0.1 in² (16...95 mm²) 44.3 lbf.in (5 N.m) 0.002...0.02 in² (1.5...10 mm²)","Climatic withstand":"IACS E10","Device Application":"Motor protection","Line Rated Current":"115 A","Operating altitude":"5000 m","Operating position":"Any position","Trip unit technology":"Thermal-magnetic Electronic","Utilisation category":"Category A IEC 60947-2 AC-3 IEC 60947-4-1","Electrical durability":"10000 cycles AC-3 440 V In/2 5000 cycles AC-3 440 V In","Mechanical durability":"40000 cycles","Mechanical robustness":"Vibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 Vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 Shocks 15 gn 11 ms IEC 60068-2-27","Nbr. of units in pkg.":"1","Maximum Operating Rate":"25 cyc/h","Connections - terminals":"Lugs-ring terminals","IK degree of protection":"IK07 IEC 62262","IP degree of protection":"IP40 IEC 60529","Magnetic tripping current":"1955 A","Phase failure sensitivity":"Yes IEC 60947-4-1","Product or Component Type":"Motor circuit breaker","Suitability for isolation":"Yes IEC 60947-1","Power dissipation per pole":"4.6 W","[Ui] rated insulation voltage":"800 V AC 50/60 Hz IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz IEC 60947-2","Ambient Air Temperature for Storage":"-58...185 °F (-50...85 °C)","Ambient air temperature for operation":"-13...158 °F (-25...70 °C)","[Uimp] rated impulse withstand voltage":"8 kV IEC 60947-2","[Ith] conventional free air thermal current":"115 A IEC 60947-4-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/ie/en/product/GV4PEM115B6/motor-circuit-breaker-tesys-gv4-3p-115a-icu-25ka-thermal-magnetic-multifunction-lugs-terminals/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV4PEM115B6/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of GV4PEM115B6 at 480 V?","answer":"Under UL 60947, the breaking capacity at 480Y/277 V AC is 18 kA. Under IEC 60947-2, at 440 V it is 20 kA."},{"question":"How can I order GV4PEM115B6 and check availability?","answer":"The GV4PEM115B6 is quoted to order against your BOM quantity. Submit an RFQ for current pricing and lead time — availability is confirmed at quote time through authorized distribution."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV4PEM115B6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV4PEM115B6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}