{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV4PEM115N","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV4PEM115N","canonicalUrl":"https://aoctrl.com/schneider/GV4PEM115N","factsUrl":"https://aoctrl.com/api/mcp/products/GV4PEM115N","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys GV4 motor circuit breaker, GV4PEM115N, 115 A rated current, 3-pole, electronic thermal-magnetic trip, 100 kA breaking capacity at 240 V AC, IP40, gray RAL 7016.","salesMarkdown":"## Active production, 115 A motor circuit breaker for 37–110 kW range The GV4PEM115N: The electronic thermal-magnetic trip unit combines adjustable overload protection with a fixed magnetic trip set at 1955 A — 17× In — so it clears short-circuits fast without nuisance tripping on motor inrush. Phase-failure sensitivity per IEC 60947-4-1 means it drops the load when one phase opens, preventing single-phasing damage. Under UL 60947 it delivers 65 kA at 240 V and 35 kA at 480Y/277 V. ## DIN-rail footprint and EverLink terminals — panel build notes The GV4PEM115N measures 155 mm high × 81 mm wide × 116 mm deep — a compact 3-pole footprint that clips onto standard DIN rail. The EverLink BTR screw terminals accept solid copper up to 95 mm² on the load side and 70 mm² on the line side, with a tightening torque of 9 N·m for the main power connections. That's enough cross-section for the 115 A feed without parallel conductors. IP40 enclosure with IK07 impact resistance handles normal panel environments; the gray RAL 7016 housing is the standard industrial finish. Power dissipation is 4.6 W per pole at rated current — about 14 W total for the three poles — so thermal rise inside a sealed enclosure stays manageable without forced ventilation. ## Electrical and mechanical endurance — cycle life for frequent starting For a motor starter seeing frequent starts — conveyors, pumps, compressors — that translates to years of service before contact maintenance is needed. Shock rating is 15 gn for 11 ms. The breaker holds calibration and trip accuracy under these conditions, which matters for mobile equipment or machinery mounted near rotating unbalance.","metaTitle":"Schneider Electric GV4PEM115N TeSys GV4 Motor Circuit","metaDescription":"Schneider Electric GV4PEM115N TeSys GV4 motor circuit breaker, 115 A rated current, 100 kA breaking capacity at 240 V. Active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Color":"Gray RAL 7016)","Depth":"4.6 in (116 mm)","Range":"TeSys Deca","Width":"3.2 in (81 mm)","title":"GV4PEM115N","Height":"6.1 in (155 mm)","Category":"US10I1122365","Standards":"CSA C22.2 No 60947-4-1 UL 60947-4-1 EN/IEC 60947-4-1 EN/IEC 60947-2","Rated duty":"Continuous IEC 60947-4-1","description":"Motor circuit breaker, TeSys GV4, TeSys GV4, 3P, 115A, Icu 50kA, thermal magnetic multifunction, Everlink terminals","Control Type":"Toggle","Product name":"TeSys GV4","Motor power kW":"37 kW 400...415 V AC 50/60 Hz 45 kW 400...415 V AC 50/60 Hz 55 kW 400...415 V AC 50/60 Hz 45 kW 500 V AC 50/60 Hz 55 kW 500 V AC 50/60 Hz 75 kW 500 V AC 50/60 Hz 75 kW 660...690 V AC 50/60 Hz 90 kW 660...690 V AC 50/60 Hz 110 kW 660...690 V AC 50/60 Hz","Fire resistance":"1760 °F (960 °C) IEC 60695-2-11","lifecycle_stage":"current","Pollution degree":"3","Range of Product":"TeSys GV4","Breaking capacity":"100 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 50 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 50 kA Icu 440 V AC 50/60 Hz IEC 60947-2 15 kA Icu 525 V AC 50/60 Hz IEC 60947-2 65 kA 208Y/120 V AC 50/60 Hz UL 60947 65 kA 240 V AC 50/60 Hz UL 60947 35 kA 480Y/277 V AC 50/60 Hz UL 60947 8 kA Icu 660...690 V AC 50/60 Hz IEC 60947-2 25 kA Icu 500 V AC 50/60 Hz IEC 60947-2 18 kA 600Y/347 V AC 50/60 Hz UL 60947","Device short name":"GV4PEM","Poles description":"3P","Tightening torque":"79.7 lbf.in (9 N.m) 0.02...0.1 in² (16...95 mm²) 44.3 lbf.in (5 N.m) 0.002...0.02 in² (1.5...10 mm²)","Climatic withstand":"IACS E10","Device Application":"Motor protection","Line Rated Current":"115 A","Operating altitude":"5000 m","Operating position":"Any position","Trip unit technology":"Electronic Thermal-magnetic","Utilisation category":"Category A IEC 60947-2 AC-3 IEC 60947-4-1","Electrical durability":"10000 cycles AC-3 440 V In/2 5000 cycles AC-3 440 V In","Mechanical durability":"40000 cycles","Mechanical robustness":"Vibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 Vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 Shocks 15 gn 11 ms IEC 60068-2-27","Nbr. of units in pkg.":"1","Maximum Operating Rate":"25 cyc/h","Connections - terminals":"EverLink BTR screw connectors top) 1 0.002...0.1 in² (1.5...70 mm²) - solid EverLink BTR screw connectors top) 1 0.002...0.08 in² (1.5...50 mm²) - flexible EverLink BTR screw connectors bottom) 1 0.004...0.1 in² (2.5...95 mm²) - solid EverLink BTR screw connectors bottom) 1 0.004...0.1 in² (2.5...70 mm²) - flexible","IK degree of protection":"IK07 IEC 62262","IP degree of protection":"IP40 IEC 60529","Magnetic tripping current":"1955 A","Phase failure sensitivity":"Yes IEC 60947-4-1","Product or Component Type":"Motor circuit breaker","Suitability for isolation":"Yes IEC 60947-1","Power dissipation per pole":"4.6 W","[Ui] rated insulation voltage":"800 V AC 50/60 Hz IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz IEC 60947-2","Ambient Air Temperature for Storage":"-58...185 °F (-50...85 °C)","Ambient air temperature for operation":"-13...158 °F (-25...70 °C)","[Uimp] rated impulse withstand voltage":"8 kV IEC 60947-2","[Ith] conventional free air thermal current":"115 A IEC 60947-4-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$982.06 – $1,225.57","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/au/en/product/GV4PEM115N/motor-circuit-breaker-tesys-gv4-tesys-gv4-3p-115a-icu-50ka-thermal-magnetic-multifunction-everlink-terminals/"},"ai":{"faq":[{"question":"What compliance documentation does this brand provide for GV4PEM115N?","answer":"Fire resistance is tested to 960 °C per IEC 60695-2-11. Climatic withstand follows IACS. Documentation typically includes the declaration of conformity and UL/CSA file numbers."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV4PEM115N","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV4PEM115N when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}