{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV4PEM115S","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV4PEM115S","canonicalUrl":"https://aoctrl.com/schneider/GV4PEM115S","factsUrl":"https://aoctrl.com/api/mcp/products/GV4PEM115S","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca GV4PEM115S, 115 A 3-pole motor circuit breaker, thermal-magnetic and electronic trip, breaking capacity 120 kA at 240 V AC.","salesMarkdown":"It's designed for motor protection and isolation (IEC 60947-1). The trip unit combines thermal-magnetic overload protection with electronic short-circuit detection, giving you adjustable curves and a magnetic tripping current of 1955 A. Breaking capacity is substantial: 120 kA Icu at 220–240 V AC (IEC 60947-2), 100 kA at 380–415 V, and 70 kA at 440 V. Under UL 60947 it carries 100 kA at 240 V and 65 kA at 480Y/277 V. That covers high-fault panels without an upstream fuse. Standards compliance includes CSA C22.2 No 60947-4-1, UL 60947-4-1, EN/IEC 60947-4-1, and EN/IEC 60947-2. The part also carries a 960 °C glow-wire rating (IEC 60695-2-11) and is rated for isolation. Pollution degree 3 suits industrial environments. Dimensions: 6.1 x 3.2 x 4.6 in (155 x 81 x 116 mm). IP40, IK07. Tightening torque of 79.7 lbf.in (9 N·m) on the main power terminals, which accept solid conductors up to 95 mm² on the bottom. The EverLink BTR screw connectors handle solid and flexible cable — top side up to 70 mm² solid. Operates in any position. Mechanical durability is 40,000 cycles; electrical durability 10,000 cycles at AC-3 (440 V, In/2). Maximum operating rate of 25 cycles per hour keeps thermal stress under control during repetitive start/stop. ## Selection Notes Rated for motor power up to 37 kW at 400–415 V AC, 75 kW at 660–690 V. Insulation voltage Ui 800 V AC. Phase failure sensitivity is included per IEC 60947-4-1. The utilisation category is both Category A (IEC 60947-2) and AC-3 (IEC 60947-4-1). Power dissipation is 4.6 W per pole — worth accounting for in enclosed panels to avoid derating. Climatic withstand per IACS ensures reliability in humid or salt-laden environments.","metaTitle":"GV4PEM115S TeSys Deca Motor Circuit Breaker, 115 A","metaDescription":"Schneider Electric GV4PEM115S motor circuit breaker, 115 A, 3-pole. Current production. Breaking capacity up to 120 kA at 240 V. Sourced to order. RFQ for availability.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Color":"Gray RAL 7016)","Depth":"4.6 in (116 mm)","Range":"TeSys Deca","Width":"3.2 in (81 mm)","Height":"6.1 in (155 mm)","Category":"US10I1122365","Standards":"CSA C22.2 No 60947-4-1 UL 60947-4-1 EN/IEC 60947-4-1 EN/IEC 60947-2","Rated duty":"Continuous IEC 60947-4-1","Control Type":"Toggle","Product name":"TeSys GV4","Motor power kW":"37 kW 400...415 V AC 50/60 Hz 45 kW 400...415 V AC 50/60 Hz 55 kW 400...415 V AC 50/60 Hz 45 kW 500 V AC 50/60 Hz 55 kW 500 V AC 50/60 Hz 75 kW 500 V AC 50/60 Hz 75 kW 660...690 V AC 50/60 Hz 90 kW 660...690 V AC 50/60 Hz 110 kW 660...690 V AC 50/60 Hz","Fire resistance":"1760 °F (960 °C) IEC 60695-2-11","lifecycle_stage":"current","Pollution degree":"3","Range of Product":"TeSys GV4","Breaking capacity":"120 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 100 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 70 kA Icu 440 V AC 50/60 Hz IEC 60947-2 30 kA Icu 500 V AC 50/60 Hz IEC 60947-2 18 kA Icu 525 V AC 50/60 Hz IEC 60947-2 100 kA 208Y/120 V AC 50/60 Hz UL 60947 100 kA 240 V AC 50/60 Hz UL 60947 65 kA 480Y/277 V AC 50/60 Hz UL 60947 10 kA Icu 660...690 V AC 50/60 Hz IEC 60947-2 25 kA 600Y/347 V AC 50/60 Hz UL 60947","Device short name":"GV4PEM","Poles description":"3P","Tightening torque":"79.7 lbf.in (9 N.m) 0.02...0.1 in² (16...95 mm²) 44.3 lbf.in (5 N.m) 0.002...0.02 in² (1.5...10 mm²)","Climatic withstand":"IACS E10","Device Application":"Motor protection","Line Rated Current":"115 A","Operating altitude":"5000 m","Operating position":"Any position","Trip unit technology":"Thermal-magnetic Electronic","Utilisation category":"Category A IEC 60947-2 AC-3 IEC 60947-4-1","Electrical durability":"10000 cycles AC-3 440 V In/2 5000 cycles AC-3 440 V In","Mechanical durability":"40000 cycles","Mechanical robustness":"Vibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 Vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 Shocks 15 gn 11 ms IEC 60068-2-27","Nbr. of units in pkg.":"1","Maximum Operating Rate":"25 cyc/h","Connections - terminals":"EverLink BTR screw connectors top) 1 0.002...0.1 in² (1.5...70 mm²) - solid EverLink BTR screw connectors top) 1 0.002...0.08 in² (1.5...50 mm²) - flexible EverLink BTR screw connectors bottom) 1 0.004...0.1 in² (2.5...95 mm²) - solid EverLink BTR screw connectors bottom) 1 0.004...0.1 in² (2.5...70 mm²) - flexible","IK degree of protection":"IK07 IEC 62262","IP degree of protection":"IP40 IEC 60529","Magnetic tripping current":"1955 A","Phase failure sensitivity":"Yes IEC 60947-4-1","Product or Component Type":"Motor circuit breaker","Suitability for isolation":"Yes IEC 60947-1","Power dissipation per pole":"4.6 W","[Ui] rated insulation voltage":"800 V AC 50/60 Hz IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz IEC 60947-2","Ambient Air Temperature for Storage":"-58...185 °F (-50...85 °C)","Ambient air temperature for operation":"-13...158 °F (-25...70 °C)","[Uimp] rated impulse withstand voltage":"8 kV IEC 60947-2","[Ith] conventional free air thermal current":"115 A IEC 60947-4-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/cc88fe9e394965dc167bdd644d7f3983.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/GV4PEM115S/alternatives.json"},"ai":{"faq":[{"question":"What color is the GV4PEM115S?","answer":"The enclosure is Gray RAL 7016."},{"question":"What is the depth of the GV4PEM115S?","answer":"Depth is 4.6 inches (116 mm)."},{"question":"What compliance documentation does this breaker carry?","answer":"It complies with CSA C22.2 No 60947-4-1, UL 60947-4-1, EN/IEC 60947-4-1, and EN/IEC 60947-2."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV4PEM115S","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV4PEM115S when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}